0.06 Guidance Note 3 Inspection & Testing Updated to BS7671:2018+A2.2O22 IET Wiring Regulations Guidance Note The Institution of Engineering and Technology of The Institution Engineering and Technology 0.06 Guidance Note 3 Inspection & Testing Updated to BS 7671:2018+A2:2022 lETWiring Regulations Published by the Institution of Engineering and Technology, London, United Kingdom The Institution of Engineering and Technology is registered as a Charity in England & Wales (no. 211014) and Scotland (no. SC038698). | The Institution of Engineering a n d Technology is the institution formed by the joining together o f the IEE(The Institution of Electrical Engineers) and the HE (The Institution of Incorporated Engineers). © 1992, 1995, 1997, 2002The Institution of Electrical Engineers © 2008, 2012, 2015, 2018, 2022The Institution o f Engineering and Technology First published 1992 (0 85296 537 0) Reprinted (with amendments to Section 17) 1993 Second edition (incorporating Amendment No. 1 to BS7671:1992) 1995 (0 8 5 2 9 6 867 1) Third edition (incorporating Amendment No. 2 to BS7671:1992) 1997 (0 85296 956 2) Fourth edition (incorporating Amendment No. 1 to BS7671:2001) 2 0 0 2 ( 0 85296 991 0) Reprinted (with new cover) 2003 Reprinted (incorporating Amendment No. 2 to BS 7671:2001) 2 0 0 4 Reprinted (with amendments to imprint page) 2006 Fifth edition (incorporating BS 7671 :2008) 2008 (978-0-86341-857-0) Reprinted 2009, 2010 Sixth edition (incorporating Amendment No. 1 to BS 7671:2008) 2012 (978-1-84919-275-0) Seventh edition (incorporating Amendment Nos. 2 and 3 to BS7671:2008) 2015 (978-1-84919-873-8) Reprinted (with minor corrections) 2015 Eighth edition (incorporating BS 7671:2018) 2018 (978-1-78561-452-1) Ninth edition (incorporating Amendment No. 2 to BS 7671:2018) 2 0 2 2 (978-1-83953-236-8) This publication is copyright under the Berne Convention and the Universal Copyright Convention. All rights reserved. Apart from any fair dealing for the purposes of research or private study, or criticism or review, as permitted under the Copyright, Designs and Patents Act, 1988, this publication may be reproduced, stored or transmitted, in any form or by any means, only with the prior permission in writing of the publishers, or in the case of reprographic reproduction in accordance with the terms o f licences issued by the Copyright Licensing Agency. Enquiries concerning reproduction outside those terms should be sent to the publishers at The Institution of Engineering and Technology, Michael FaradayHouse, Six Hills Way, Stevenage, SGI 2AY, United Kingdom. Copies of this publication m a y b e obtained from: The Institution of Engineering and Technology PO Box 96, Stevenage, S G I 2SD, UK Tel: + 4 4 (0)1438 767328 Email: [email protected] https //elect rical.theiet.org While the author, publisher and contributors believe that the information a n d guidance given i n this work are correct, all parties must rely upon their own skill and judgement when making use of them. The author, publisher and contributors d o n o t assume any liability to anyone for any loss or damage caused by any error or omission in the work, whether such a n error or omission is the result of negligence or any other cause. Where reference is m a d e to legislation it is n o t to be considered as legal advice. Any and all such liability is disclaimed. Permission to reproduce extracts from British Standards is granted by BSI. No other use of this material is permitted. British Standards can be obtained i n PDF or hard copy formats from the BSI online shop: https://shop.bsigroup.com/. ISBN 978-1-83953-236-8 (paperback) ISBN 978-1-83953-238-2 (vitalsource) Typeset in the UK by The Institution o f Engineering a n d Technology, Stevenage Printed i n the UK by Sterling Press Ltd, Kettering Contents Cooperating organizations 6 Acknowledgements 7 Preface 8 Introduction 11 Chapter 1 General requirements 13 1.1 Safety 13 1.2 1.3 Required competence The client 15 16 1.3.1 Certificates and reports 16 1.3.2 Rented domestic and residential accommodation 16 1.3.3 The Construction 17 (Design a n d Management) Regulations 2015 1.4 Additions and alterations 17 1.5 Departures and non-compliance 18 1.6 Record-keeping 18 1.7 Installations requiring specialist knowledge, training or experience 19 Chapter 2 Initial verification 21 2.1 Purpose o f initial verification 21 2.2 Certificates 22 2.3 Required information 23 2.4 Frequency of subsequent inspections 24 2.5 Initial inspection 25 2.6 2.5.1 General procedure 25 2.5.2 Comments o n individual items to b e inspected 25 2.5.3 Inspection checklist Tests associated with initial verification 2.6.1 Test results 46 54 54 2.6.2 Electrical Installation Certificate (EIC) 55 2.6.3 Model forms 55 2.6.4 The sequence of tests 55 2.6.5 Continuity o f protective conductors, including main and supplementary bonding 56 2.6.6 Continuity o f ring final circuit conductors 2.6.7 Insulation resistance 62 67 2.6.8 Confirming SELVor PELV circuits by insulation resistance testing 73 2.6.9 Testing of electrically separated circuits 74 2.6.10 Testing of functional extra-low voltage (FELV) circuits 2.6.11 Proving and testing o f non-conducting (insulation resistance/impedance 75 location of floors and walls) 76 2.6.12 Polarity testing 78 2.6.13 Earth electrode resistance testing 79 G u i d a n c e N o t e 3: I n s p e c t i o n & Testing © The Institution of Engineering and Technology 3 2.6.14 Protection by automatic disconnection 2.6.15 Earth fault loop impedance o f supply (ADS) (EFLI) verification 85 85 2.6.16 Prospective fault current (Ipf) 88 2.6.17 Phase sequence testing 93 2.6.18 Operation a n d functional testing o f RCDs 95 2.6.19 Other functional testing 2.6.20 Verification o f voltage drop 102 102 2.6.21 Verification o f protection of low voltage (LV) installations against temporary overvoltages due to faults i n the high voltage (HV) or LV system 103 2.6.22 Verification o f protection against overvoltages of atmospheric origin or due to switching 104 2.6.23 Verification of measures against electromagnetic disturbances 105 2.6.24 Prosumer's electrical installations (PEIs) 106 Chapter 3 Periodic inspection and testing 109 3.1 Purpose of periodic inspection and testing 109 3.2 Necessity for periodic inspection and testing 109 3.3 Electricity at Work Regulations (EAWR) 110 3.4 3.3.1 3.3.2 The need for appropriate inspection and testing Safety in inspection and testing 3.3.3 Diverted neutral currents 111 Design 111 3.5 Routine checks 112 3.6 Required information 113 3.7 Frequency of periodic inspections 114 3.8 Requirements for periodic inspection and testing 3.8.1 Process: prior to carrying out inspection a n d testing 117 117 3.8.2 General procedure 3.8.3 Setting inspection and testing samples 3.9 Periodic inspection 3.10 Periodic testing 3.10.1 General 3.9.1 118 Example checklist of items that require inspection 123 128 128 3.10.2 Tests to be made 128 3.10.3 Additional notes on periodic testing 130 3.11 Electrical Installation Condition Report (EICR) 3.12 Periodic inspection of installations constructed Chapter 4 133 to an earlier edition Test instruments and equipment 135 137 4.1 Instrument standard 137 4.2 Instrument accuracy 138 4.3 Low-resistance ohmmeters 139 4.4 Insulation resistance testers 140 4.5 EFLItesters 140 4.6 Earth electrode resistance testers 143 4.7 RCD testers 143 4.8 Phase rotation instruments 144 4.9 Thermographic equipment 144 Chapter 5 5.1 5.2 G u i d a n c e Note 119 123 of BS 7671 or the IEE Wiring Regulations 4 110 111 Forms Initial verification (inspection Minor works 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology 149 and testing) forms 149 150 5.3 Periodic inspection and testing 150 5.4 Examples of completed model forms for certification and reporting 151 Appendix A Maximum permissible measured earth fault loop impedance (EFLI) 171 Al Tables 171 A2 Appendix 3 of BS 7671 176 A3 Methods of adjusting tabulated values of Zs 177 Appendix B Resistance of copper and aluminium conductors 181 Bl Standard overcurrent devices B2 Steel wire armour (SWA), steel conduit a n d steel trunking 184 B3 Mineral-insulated 184 Appendix C Appendix D copper-sheathed 183 cable Use of a n earth leakage current clamp meter t o provide an indication of the state of insulation 185 Safety check for diverted neutral currents 187 DI Dangers associated with diverted neutral currents 187 D2 H o w to check for diverted neutral currents 187 Index 191 Guidance © The Institution Note 3 : Inspection & Testing of Engineering a n d Technology 5 Cooperating organizations The Institution o f E n g i n e e r i n g a n d Technology m a d e by the following a c k n o w l e d g e s the invaluable in the preparation individuals o f t h i s Guidance contribution Note: Institution of Engineering and Technology H. R . Lovegrove IEng FIET R. Wickens M. Peace CEng M E T MCIBSE Eur Ing L. Markwell R. Giddings Eng MSc BSc(Hons) CEng M E T MCIBSE L C G I M E T ACIBSE G. G u n d r y M E T We would like to thank the following organizations for their continued support: BEAMA Ltd BCA Certsure, t r a d i n g as NICEIC City & Guilds EAL ECA Electrical C o n t r a c t o r s ' A s s o c i a t i o n of S c o t l a n d (SELECT) Electrical Safety First Health a n d Safety Executive (HSE) IHEEM NAPIT Revised, compiled and edited: Eur Ing G. Kenyon BEng (Hons) Guidance N o t e 3 : I n s p e c t i o n & Testing © The Institution o f Engineering a n d Technology CEng MIETTechlOSH Acknowledgements References to British Standards, CENELEC Harmonization Documents and International Electrotechnical Commission (IEC) Standards are made with the kind permission of the British Standards Institution (BSI). Complete copies can b e obtained by post from: BSI Customer Services 389 Chiswick High Road London, W4 4AL Tel: + 4 4 0345 080 9 0 0 0 Email: [email protected] BSI also maintains stocks of international and foreign standards, with many English translations. Up-to-date information o n BSI Standards can b e obtained from the BSI website: www.bsigroup.com Illustrations of test instruments were provided by G Kenyon Technology Ltd. Other illustrations, from different sources, are acknowledged Cover design a n d illustration http://studiostuntdouble.com/. within the text. were created by Ken Dobson at Studio Stunt Double: It is strongly recommended that anyone involved in work o n or near electrical installations possesses a copy of The Electricity at Work Regulations 1989. Guidance o n Regulations (HSR25) published by the Health and Safety Executive (HSE). Copies of Health and Safety Executive documents and approved codes o f practice (ACOP) c a n be obtained from: HSE Books Customer Services PO Box 2 9 Norwich, NR3 1GN Tel: + 4 4 (0)333 202 5070 Email: [email protected] Web: http://books.hse.gov.uk G u i d a n c e N o t e 3: I n s p e c t i o n & Testing © The Institution o f Engineering and Technology 7 Preface This Guidance Note is one of a number of publications prepared by the Institution of Engineering and Technology (IET) t o explain a n d enlarge upon the requirements in BS 7671:2018+A2:2022, Requirements Regulations. BS 7671 is a joint publication for Electrical Installations, IET Wiring o f the British Standards Institution and the Institution of Engineering and Technology. All references to B S 7 6 7 1 in the text o f this Guidance Note are references t o the current 18th Edition o f the IET Wiring Regulations, unless otherwise noted. From herein, BS 7671 :2018+A2:2022 is referred to as BS7671. T h e year reference will only b e included where there is a need to reference a requirement m a d e in an earlier edition, such as BS 7671:2008. Note that use of this Guidance Note does alone n o t provide compliance withBS7671. Its content is intended to explain some of the requirements should always consult BS 7671 to satisfy themselves of BS 7671. Readers of compliance and must rely upon their o w n skill and judgement w h e n making use of the guidance provided within this publication. The scope generally follows that of BS7671; t h e relevant regulations and appendices are noted in the margin. Due to the introduction in 2 0 1 6 of CENELEC Harmonized Document (HD) 6 0 3 6 4 - 6 covering inspection and testing, the clause numbering in B S 7 6 7 1 aligns with that in the HD. As a result, Chapters 61 to 6 3 are n o t used; the text o f Part 6 of BS 7 6 7 1 starts at Chapter 6 4 . Apart f r o m the testing of insulation resistance a n d residual current devices (RCDs), the requirements for inspection and testing have not significantly changed f r o m BS 7671 :201 8. Some Guidance Notes also contain material not currently included i n BS 7671, but which was present in earlier editions of the Wiring Regulations. All o f the Guidance Notes contain references to other relevant sources of information. Electrical installations in the United Kingdom that comply w i t h BS 7671 are likely to satisfy the relevant parts o f statutory regulations such as the Electricity at Work Regulations 1989 (EAWR). However, this cannot be guaranteed. It is stressed that it is essential to establish which statutory and other regulations apply and to install accordingly. For example, a n installation in premises subject t o licensing may have requirements different f r o m or additional to those of BS 7671, and these will take precedence. 8 Guidance Note 3: Inspection & Testing © The Institution of Engineering and Technology BS 7671 applies to the design, erection including additions a n d verification of electrical installations, and alterations to existing installations and to the inspection, testing and reporting of existing installations. Existing installations that have been installed in accordance with earlier editions of the Regulations may not comply with the current edition in every respect, but this does n o t necessarily mean that they are unsafe for continued use or that they require upgrading. The person or persons carrying out the inspection and testing of such an installation must decide whether the installation is safe and suitable for continued use. Inspection and testing can only be conducted according to the requirements o f the current version of BS 7671. The inspector must determine whether any shortcomings are classified as safety issues or recommendations for improvement. Other related electrical installations, such as emergency lighting, fire alarms and information and communication technology (ICT) systems, have their own installation requirement standards such as BS 5266, BS 5839 and BS 6701 respectively. These may have installation, inspection, testing and certification requirements over and above those required i n BS 7671. It is the responsibility of the duty holder to maintain all their installations appropriately, and the extent of the inspection and testing, and the standards to which it is conducted, should b e agreed before any work is undertaken. The inspector is reminded that for a periodic inspection and test of a n existing installation, their duty is to assess the suitability of the existing installation for continued use, subject to any agreed limitations and exclusions. They must therefore make sufficient inspection and tests to enable them to make that assessment. In addition, it is the duty of the building or site dutyholder to maintain their installation so that it is safe and to undertake such maintenance as is necessary to achieve this. Users of this Guidance Note should assure themselves that they have complied with any relevant legislation, including, where applicable, legislation that post-dates the publication. G u i d a n c e N o t e 3: I n s p e c t i o n & Testing © The Institution of Engineering and Technology 9 NOTES 10 G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology Introduction This Guidance Note is concerned primarily with Part 6 of BS 7671 (Inspection testing) along with Appendix 6 (Model forms for certification and reporting). and Neither BS 7671 nor the Guidance Notes are design guides. It is essential to prepare a full design and specification prior to commencement or alteration of an electrical installation. 514.9 The design and specification should set out the requirements and provide sufficient information to enable competent persons to carryout the installation and to commission it. The specification must include a description of how the system is to operate and all the design and operational parameters. It must provide for all the commissioning procedures that will b e required a n d for the provision of adequate information user. This will be by means of a n operational and maintenance to the (O&M) manual or schedule, and 'as-built' drawings, if necessary. It must be noted that it is a matter of contract as to which person or organization is responsible for, i n turn, the design, specification, construction and verification of the installation a n d any operational information. The persons or organizations who m a y b e concerned i n the preparation of the works include: (a) the designer (see the Construction (CDM) for information (Design and Management) Regulations 2015 o n designers' duties); (b) the installer (contractor or if there is m o r e than one, principal contractor and contractors); (c) the verifier; (d) specialist commissioning engineers; (e) the distributor of electricity (the distribution network operator (DNO)); (f) the installation owner and/or user (and, where applicable for CDM, the client. Where there is a domestic client, the client's duties are undertaken by the contractor or, if there is more than o n e contractor, the principal contractor); (g) the architect (and, where CDM applies, the principal designer); (h) the fire risk assessor; (i) specialist manufacturers or suppliers; ( j ) area Building Control bodies; ( k ) any regulatory authority: (l) any licensing authority; (m) any specialist insurers; and (n) the Health a n d Safety Executive (HSE). Guidance Note 3 : Inspection & Testing © The Institution of Engineering and Technology 11 The revision o f the CDM Regulations has given guidance on the duties required of a designer. Aswell ascarrying out the actual design layout and calculations and specifying the materials and installation requirements: "Designers are those, who as part of a business, prepare or modify designs for a building, product or system relating to construction work. When preparing or modifying designs, to eliminate, reduce or control foreseeable risks that m a y arise during: 1 2 construction; and the maintenance and use of a building once it is built. Provide information to other members of the project team to help them fulfil their duties." Details of each i t e m of equipment sect 51 should b e obtained f r o m the manufacturer and/or supplier and compliance with appropriate standardsconfirmed. Health and safety o f all installation a n d inspection a n d testing staff and any other persons i n the premises is vital and a work plan including risk assessments a n d method statements must b e agreed with all parties and put in place before any work is undertaken. The installation operational manual must include a description as installed is to operate, maintenance of how the system provisions and all test and commissioning records. The manual should also include manufacturers’ technical data for all items of switchgear, luminaires, accessories, etc. and any special instructions that may b e needed. The Health and Safety at Work etc. Act 1974 Section 6 and the Construction (Design and Management) Regulations 2015 are concerned with the provision of information, and guidance o n the preparation of technical manuals is given i n BS EN IEC/IEEE 82079-1 Preparation of information of products - Principles and general requirements information o n construction and services. The size and complexity of the products for use (instructions and BS 4940 for use) series Technical installation will dictate the nature and extent of the manual. With regard to the inspection a n d testing of an existing installation, it is necessary to agree a detailed specification of the requirements of the client, including any limitations. 12 G u i d a n c e Note 3: I n s p e c t i o n & Testing © The Institution of Engineering a n d Technology 1 General requirements 1.1 Safety Before any work can begin, a work programme should b e agreed with the client and a health a n d safety plan, including risk assessments and method statements, agreed and put in place. It m a y be that work has to be carried out when the premises is operating and staff are present, and they must not b e exposed to any safety risks. Work areas should b e fenced off w i t h temporary be left unattended barriers a n d electrical equipment should not when open. There should be adequate workspace, access and lighting appropriate to t h e work being carried out, and during electrical testing it is often necessary to provide temporary task lighting as parts, or all, of the installation m a y be isolated. Escape routes must be kept open at all times or temporary alternatives arranged. Where supplies have to b e isolated, it is necessary that this is planned i n advance with the premises management. Health and safety guidance (HSG) Electricity a t work: Safe working practices (HSC85) recommends managers establish a system of rules and procedures wherever electrical work is to b e carried out, or ensure that contractors brought in to d o electrical work have appropriate rules and procedures. Initial verification, and some maintenance activities, o f fixed electrical installations fall within the scope of the Construction (Design and Management) Regulations 2015 (CDM). For private domestic clients, the contractor, or, if there is m o r e than one, the principal contractor, undertakes the client's duties. Electrical inspection a n d testing inherently involves some degree of hazard. It is therefore the inspector's d u t y to provide for their o w n safety, and that of others, in the performance of the test procedures. The testing safety procedures detailed in the Health and Safety Executive Guidance Note Electrical test equipment for use on low voltage electrical systems (CS38) should be observed. Where testing does not require the equipment or part of an installation to be live, it should be made dead and safely isolated. Guidance on live and dead working can b e found i n the HSE publication The Electricity at Work Regulations 1989. Guidance on Regulations (HSR25). Guidance o n safe isolation procedures can be found i n Best Practice Guide No.2. Guidance o n the management of electrical safety and safe isolation procedures for low voltage installations, published by Electrical Safety First. G u i d a n c e Note 3 : Inspection © T h e Institution o f Engineering & Testing and Technology 13 When using test instruments, (a) understanding safety can b e achieved by precautions such as: the equipment to b e used, its rating and the characteristics of the installation upon which it is proposed to use the equipment. (b) checking that the instruments to be used conform to the appropriate British Standard safety specifications. These are BS EN 61010 series Safety requirements for electrical equipment for measurement, control, and laboratory use and BS 5458:1977 (IEC 141:1973) Specification for safety requirements for indicating and recording electrical measuring instruments BS 5 4 5 8 has n o w been is the standard instruments withdrawn, but and their accessories. to which older should have been manufactured. (c) checking any test equipment before use to see that it is complete and not damaged. (d) checking that test leads, including any probes or clips used, are i n good order, are clean and have no cracked or broken insulation. Where appropriate, the guidance given i n GS38 should b e observed for test leads. This recommends the use of adequately insulated test equipment, probes, connectors, a n d test leads, suitable for the insulation overvoltage category in which tests are being conducted (see Table 1.1). Suitable high breaking capacity (HBC) fuses o r other means of limiting current, should be provided i n test leads o r test equipment. Such measures help reduce the risks associated w i t h both accidental contact, a n d arcing under fault conditions. ▼ Table 1.1 Explanation of installation overvoltage category (CAT) markings on test equipment, leads, probes and other connecting equipment Installation overvoltage category marking Note: Description of where test equipment with this marking can be used in an electrical installation (see HSE Guidance Note GS38, and Annex K to BSEN 61010-1:2010+A1:2019) CATII Equipment intended to b e supplied from the building wiring. This overvoltage category applies to both plug-connected equipment and permanently connected equipment. CATIII As CATII, plus equipment intended to form part of the building wiring installation. Such equipment includes socket-outlets, distribution boards. CATIV As CATIII, plus equipment installed at or near the origin o f the electricity supply to a building, between the building entrance and the primary distribution board (consumer unit). Such equipment may include electricity meters and primary overcurrent protective devices. The equivalent overvoltage category for a test arrangement is the lowest overvoltage category of any equipment, including test instruments, leads, probes, connectors, and similar, connected in the test arrangement. Particular attention should b e paid to the safety aspects associated w i t h any tests performed with instruments capable o f generating a test voltage greater t h a n 5 0 V AC o r 120 V DC in dry conditions, or 2 5 V AC or 6 0 V DC i n wet or damp conditions, or which use the supply voltage for the purposes of testing earth electrode, earth fault loop impedance and operation of residual current device(s) (RCD). Note the warnings given in Section 2.6.16 through to Section 2.6.19 of this Guidance Note. 14 G u i d a n c e N o t e 3 : I n s p e c t i o n & Testing © The Institution of Engineering a n d Technology Electric shock hazards can arise from, for example, capacitive loads, such as when cables become charged in the process of an insulation resistance test, or voltages o n t h e earthed metalwork whilst conducting a loop test or RCDtest. The test limits quoted in these guidelines are intended to minimize the chances of receiving anelectric shock during tests. Under some conditions, such as when working at height, particular care needs to be taken even with touch voltages below 5 0 V A C or 120 V DC. A spark, or contact with touch current at the limit of perception, m a y cause an inspector or test equipment operator to be startled and jump or physically jolt away f r o m the contact, resulting in a fall or other serious incident. It is important to address such hazards when carrying out risk assessments before work begins. 1.2 Required competence 641.6 Skilled persons carrying out the inspection 651.5 must as, appropriate to their function, have a sound knowledge and experience relevant to the nature of the installation being inspected and tested, and of B S 7 6 7 1 and other and testing of any electrical installation relevant technical standards. (Such persons are generally referred t o in this Guidance Note as 'the inspector'; this may b e o n e or more persons, depending o n the work being undertaken.) Inspectors must also have the relevant education a n d experience to enable them to perceive risks and avoid the dangers that electricity can create, and be fully versed in the inspection and testing procedures. This can best be shown by the inspector holding a recognized inspection and testing qualification, along with a current level 3 certificate in the requirements for electrical installations BS 7671. Furthermore, the inspector must employ suitable test equipment during t h e inspection and testing process, be familiar with its operation, and have sufficient experience in interpreting the results with regard to the requirements inspection of BS 7671. It is worth noting that the person responsible for inspection and testing may b e required to formally demonstrate competence by means of registration/certif ication under a recognized scheme or membership of a recognized trade body, or, for example, as a condition of contract and/or as a requirement of the Local Authority Building Control (LABC). It is the responsibility of the inspector, for either the initial or periodic inspection and testing, as appropriate, to: 641.4 (a) prevent danger to any person or livestock and prevent property damage; 641.3 (b) compare the inspection and testing results with the design criteria (where available), with BS 7 6 7 1 and/or with previous records, as appropriate; (c) confirm compliance with the current edition of BS 7671, or any non-compliance (non-conformity with BS 7671) that may give rise to danger; (d) take a view on related issues that might constitute or give rise to danger of the installation itself, or its interface with the premises, such as the condition connected electrical equipment, the condition of distributor's condition of building fabric to which electrical equipment equipment, of or the is secured, or through which wiring systems pass (for example, fire stopping); and (e) take a view and report o n the condition of the installation. G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering a n d Technology 15 In the event of a dangerous situation being found, the inspector should recommend the immediate isolation of the defective item of equipment. work should b e informed, in writing, of this recommendation 1.3 The person ordering t h e without delay. The client 1.3.1 Certificates and reports 644.1 653.1 Following the initial verification of a new installation, or changes to an existing installation, an Electrical Installation Certificate (EIC), together with a Schedule(s) of Inspections and a Schedule(s)of Test Results, is required to b e given to the person ordering the installation work. Likewise, following the periodic inspection a n d testing of an existing installation, a n Electrical Installation Condition Report (EICR), together w i t h Condition Report Inspection Schedule, Schedule(s)of Circuit Details and Schedule(s) of Test Results, is required to b e given to the person ordering the inspection. Sometimes the person ordering the work is not the user of the installation. I n such cases, it is necessary for the user (for example, the employer or householder) t o have a copy of the certificate (together with the records o f inspections and test results). It is recommended that those providing documentation to the person ordering the work also recommend that a copy of the forms b e passed to the user, including any purchaser o f a domestic property. For rented accommodation, this m a y b e required by legislation (see Section 1.3.2). Copies of any certificates o r reports along with their associated schedules should b e kept in the operational a n d maintenance (O&M) documentation 1.3.2 for t h e premises. Rented domestic and residential accommodation In England and Wales, Sub-Section (l)(b) of Section 11 of the Landlord and Tenant Act 1985 (Repairing obligations in short leases) implies that a landlord "shall keep in repair and proper working order the installations in the dwelling-house for the supply of water, gas and electricity". Asimilar requirement can b e found in Section 13 of Chapter 4 of the Housing (Scotland) Act 2014, which states that the electrical installation must b e in a reasonable state of repair, in order to comply with the Act. The legislation goes on to state that the installation must b e maintained. The above Acts d o not directly specify periodic inspection a n d testing of a n electrical installation. Periodic inspection a n d testing is a means of demonstrating compliance with the Acts. The Scottish Government has published guidance o n meeting the tolerable standard a n d repairing standard in Scotland, which can b e downloaded from: https://www.gov.scot/publications/electrical-installations-and-appliances-privaterented-properties/. The Electrical Safety Standards i n the Private Rented Sector (England) Regulations 2 0 2 0 apply t o all n e w tenancies i n private rented properties in England f r o m 1 July 2020, a n d all existing tenancies f r o m 1 April 2021. This legislation requires an EICRto b e prepared at an interval o f n o t m o r e than 5 years (or shorter period if the inspector considers it necessary). The legislation also requires specific persons, such as tenants, new tenants before they occupy the premises, or, o n written request, local authority 16 G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology housing authority, to receive copies o f the EICR (or EIC if an EICR has not b e e n conducted within 5 years of an EIC for the entire installation being issued). Inspection and testing of rented properties is also required in Scotland. Whilst over a n d above t h e requirements in legislation, landlords should b e aware that damage may occur to parts o f the electrical installation, and, where practicable, can consider an electrical inspection o n change of tenancy. Any repairs m u s t b e carried out by an electrically skilled person or an electrically competent person under their supervision. The landlord is responsible for confirming the competency of any contractors carrying out such work. Advice for landlords on the legislation, including guidance o n n o w to find a competent person t conduct the test, can b e found o n the UK Government website a t the following address: https://www.gov.uk/government/publications/electrical-safety-standards-in-theprivate-rented-sector-guidance-for-landlords-tenants-and-local-authorities/guide-forlandlords-electrical-safety-standards-in-the-private-rented-sector. 1.3.3 The Construction (Design and Management) Regulations 2015 The client a n d contractors have duties for health, safety a n d welfare according to t h e CDM Regulations. F o r a private domestic client, the contractor (or, if more than o n e contractor, the principal contractor) assumes the client's duties. 1.4 644.1 641.3 Additions and alterations Every addition or alteration to an existing installation must comply with the current edition of B S 7671 and must not impair the safety of the existing installation. The relevant inspection and testing requirements of Chapter 64 also apply to additions and alterations and, in particular, to the replacement o f a distribution board or consumer unit. In order to verify that an addition o r alteration to an electrical installation complies with BS 7671, the relevant parts of the existing installation must b e inspected and tested to confirm the safety of the addition or alteration, including, for example, the: (a) circuit ratings; (b) circuit conductor sizes; (c) means of earthing; (d) protective conductor continuity; and (e) earth fault loop impedance (EFLI). 644.1 .2 While there is no obligation to inspect and test any part of the existing installation that does not affect and is not affected by the addition o r alteration, any defects with the existing installation that are observed during the course of the works, that may give rise to danger, b u t d o n o t affect the safety of the addition or alteration, are required to be noted in the ’Comments on existing installation’ section of an EIC (single-signature or multiple-signature) or o n Minor Electrical Installation Works Certificates (MElWCs). If there is insufficient space to complete this information, a separate document could b e used and referred to in the certificate. Guidance Note 3 : Inspection & Testing © The Institution of Engineering and Technology 17 1 1.5 Departures and non-compliance These terms are now frequently used in certificates and reports a n d are defined in Part 2 of BS 7671. "Departure. Deliberate decision not to comply fully w i t h the requirement of BS 7671, for which the designer must declare that the resultant degree o f safety is not less than that achievable by full compliance." "Non-compliance. A non-conformity that may give rise to danger." Note: A non-conformity is a failure to meet a requirement of a standard. 1.6 Record-keeping 132.13 It is a requirement that the appropriate documentation called for in Regulation 514.9, 514.9 Part 6 and (where applicable) Part 7 o f BS 7671 is provided for every electrical installation. Chapter 6 5 Records of all checks, inspections and tests, including test results, should be kept Appx6 - throughout the working life of an electrical installation. This will enable deterioration to guidanceto recipents b e identified, a n d could also be used as a management tool to ensure that maintenance checks are being carried o u t and to assess their effectiveness. For non-domestic Management) installations, Regulation 12 o f the Construction (Design and Regulations 2015 (CDM) requires a record known as 'the health and safety file' to b e prepared, reviewed, updated and revised from t i m e to time to take account of the work and any changes that have occurred. This file should contain any information relating to the project that is likely to b e needed during any subsequent construction work to provide for the health and safety of persons. The CDM Regulations require that the health a n d safety file is passed o n t o the client o n completion construction work to assist with ongoing management of the of the building. The CDM Regulations also require that once the construction work has been completed, the health and safety file remains available for inspection by any person who might need it to comply with any relevant legal requirements. It also requires that the file is revised and updated as often as may b e appropriate to incorporate any relevant new information. EICs, MElWCs and EICRs (as appropriate) would constitute relevant information in relation to this requirement. For domestic installations, NHBC (National House-Building Council) guidance recommends that all instructions for services are passed to t h e building owner. In both domestic and non-domestic cases, there may also be insurance requirements that imply or specify records. The Electromagnetic Compatibility the client keep the information electromagnetic compatibility 18 G u i d a n c e N o t e 3 : I n s p e c t i o n & Testing © The Institution of Engineering a n d Technology Regulations 2016 are statutory a n d require that provided by the installer relating to compliance w i t h (EMC) criteria for the life of the installation. 1.7 Installations requiring specialist knowledge, training or experience This Guidance Note mainly covers the general requirements of BS7671. The following publications provide further guidance o n types of installation, or special location, that require additional information, experience, and/or training, for initial verification periodic inspection, testing and certification: 710 (a) Medical 710.64 locations: refer to t h e IET Guide to Electrical Installations and in Medical Locations, IET Guidance Note 7 Special Locations along with relevant English, Scottish and Welsh Health Technical Memoranda; ( b ) Solar photovoltaic (PV) installations: refer to the IET Code Grid-Connected Solar Photovoltaic Installations; 722 (c) Electric vehicle charging equipment installations: of Practice for IET Code of refer to the Practice for Electric Vehicle Charging Equipment Installation; (d) Electrical energy storage systems: refer to the IET Code of Practice for Electrical Energy Storage Systems; (e) Fuel filling stations: Modification, refer to the Maintenance AREA Guidance and Decommissioning for Design, Construction, of Filling Stations (also known as the Blue Book), and the IET/APEA publication Electric Vehicle Charging Installations at Filling Stations; (f) Other locations with explosive atmospheres: see BS EN 60079; (g) Temporary power systems within the scope of BS 7909: refer to the IET Temporary Power Systems: A guide to the application for temporary events and the IET Practitioner's of BS 7671 and BS 7909 Guide to Temporary Power Systems; (h) Fire protection and fire stopping: Against Fire; (i) Emergency lighting systems: refer to IET Guidance refer to the Note Electrician's Guide 4 Protection to Emergency Lighting Systems along with BS 5266-1; and (j) Fire detection Fire Detection and fire alarm systems: and Alarm Fire refer to the Electrician's Guide Systems along with BS 5839-1:2017 to and BS 5839-6:20 19+AI:2020. This list is n o t exhaustive. The above publications are not a substitute for suitable experience and/or training in those types o f installation. Guidance Note 3 : Inspection & Testing © The Institution of Engineering and Technology 19 NOTES 20 G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology Initial verification 2.1 2 Purpose of initial verification Verification is defined in BS 7671 as: "All measures by means of which compliance of the electrical installation with the relevant requirements of BS 7671 are checked, comprising inspection, testing and certification." 642.2 Initial verification is carried out on a new installation before it is put into service. The purpose is to confirm by way of inspection and testing, during construction and on completion, that the installation complies with the design and construction BS 7671, in so far as is reasonably practicable. Appx 6, Intro (v) aspects of It is important to recognize the responsibilities o f the signatories for the design, construction and verification. While the inspector is responsible for verifying aspects of b o t h design a n d construction, they cannot, and are not m e a n t to, absolve responsibility for their work elements from the designer and installer nor fix any problems they may find. Example Consider o n e aspect of the design: the inspector should check that the cable sizes, as specified, have been correctly selected and installed. In order to do this, the design criteria is required to be obtained, for example, a cable o r circuit schedule, and will then carryout a visual inspection of the installed cable sizes for comparison. The m o s t logical position to d o so will be at the distribution board housing the cables' protective devices. It would b e unreasonable for the inspector to carry out design cable sizing checks, as this is the responsibility of the designer. At this point, it would also be unreasonable for the inspector to check that each cable size at the distribution point is maintained throughout responsibility of the installer or constructor). the cable's length (this is the This example illustrates the principle a n d the responsibilities of the designer and constructor of the installation. The inspector carries out checks, but only to confirm the work of others. 42.3 The inspector must have adequate information o n the design details to check and inspect against. BS 7671 provides a format list in Regulation 642.3 of items to be checked, although this list is not exhaustive. These items are as follows: (a) installed electrical equipment applicable British or Harmonized is of the correct t y p e and complies w i t h an Standard, or a foreign national standard based o n an International Electrotechnical Commission (IEC) Standard; Guidance © The Institution Note 3 : I n s p e c t i o n & T e s t i n g of Engineering a n d Technology 21 2 (b) the fixed installation is correctly selected and erected, taking into account manufacturers’ instructions; (c) the fixed installation is n o t visibly damaged or otherwise defective so as to impair safety; and (d) the installation is ready a n d safe to be used. Sect 642 Inspections Inspections are an important element of inspection a n d testing and are described in Section 2.5 o f this Guidance Note. Sect 643 Tests The tests are described in Section 2.6 of this Guidance Note. 644.1 Results The results of inspection and tests are to be recorded as appropriate. The HSE's publication HSR25 recommends that records of all maintenance, including test results, b e kept throughout the working life o f an installation (see guidance on the Electricity at Work Regulations 1989 (EAWR), Regulation 4(2)). This can enable the condition of equipment and the effectiveness of maintenance t o be monitored. 643.1 R e l e v a n t c r i t e r i a The relevant criteria are, for the most part, the requirements of the Regulations for the particular inspection or test. Most criteria are given i n Sections 2 and 3 of this Guidance Note. There will b e some instances where the designer has specified requirements are particular to the installation concerned. that For example, the intended impedances may be different from those in BS7671. I n this case, the inspector should either ask for the design criteria or forward the test results to the designer for verification with the intended design. In the absence of such data, t h e inspector should apply the requirements set o u t in BS 7671 . Verification The responsibility for comparing inspection a n d test results w i t h relevant criteria, as required by Regulation 641.3, lies with the party responsible for inspecting and testing t h e installation. This party, which may be the person carrying out the inspection a n d testing, should sign the ’Inspection and testing’ section of the Electrical Installation Certificate (EIC) or the ’Declaration’ section of t h e Minor Electrical Installation Works Certificate (MEIWC). If the person carrying o u t the inspection and testing is also responsible for the ’Design’ and 'Construction' of the installation, the design and construction sections of the EIC should be completed 2.2 by the same person. Certificates Appx 6 Appendix 6 of B S 7671 contains model forms for the initial certification of a new installation or for a n addition or alteration to a n existing installation, as follows: (a) the multiple-signature (b) the MEIWC. 22 Guidance N o t e 3 : Inspection & Testing © The Institution of Engineering and Technology EIC; o r 2 Examples of typical f o r m s a r e given Multiple-signature Electrical The multiple-signature in Section 5 of this Guidance Installation certificate allows C e r t i f i c a t e (EIC) different persons c o n s t r u c t i o n , inspection a n d testing, a n d a l l o w s two signatories i s mutual W h e r e designers responsibility. o f a n installation, the use o f separate a r e responsible f o r m s would sign for design, for identifiably be appropriate. there separate parts W h e r e the design, a n d t e s t i n g are the responsibility of one p e r s o n a Certificate with d e c l a r a t i o n a s shown (v) a single-signature in item 6 in B S 7 6 7 1 may be used in p l a c e of the multiple of the form. Minor Electrical I n s t a l l a t i o n Works C e r t i f i c a t e (MEIWC) T h i s c e r t i f i c a t e i s to be used only include circuit, the provision t o a n existing of a new circuit. f o r individual such For several items items similar but not f o r the replacement of minor to section o f the w o r k s that d o not as a n a d d i t i o n a l socket-outlet or lighting of minor b e used. T h e c e r t i f i c a t e may a l s o be used f o r the replacement or luminaires, Introduction signatures model point works, a n E I C should o f equipment of distribution such a s a c c e s s o r i e s boards, consumer units o r items. 2.3 Required information BS7671 requires o r p e r s o n s carrying 311.1 to for design where c o n s t r u c t i o n , inspection Appendix 641.2 Note. that t h e f o l l o w i n g i n f o r m a t i o n shall be m a d e available to the p e r s o n o u t the inspection and testing: Assessment o f general characteristics ( a ) the expressed maximum demand, in amps, kW or kVA (after d i v e r s i t y i s taken i n t o account); 312.1 ( b ) t h e number a n d t y p e of live conductors circuits used in the i n s t a l l a t i o n ; of the 312.2 (c) the type of s y s t e m e a r t h i n g used by the distributor f o r the user; i n s t a l l a t i o n a n d a n y facilities p r o v i d e d by the source(s) ( d ) t h e nominal voltage(s) a n d i t s characteristics, including (e) the nature o f the c u r r e n t a n d supply frequency; (f) the p r o s p e c t i v e short-circuit the installation; origin Note: harmonic and of the distortion; c u r r e n t at the origin of the installation; (g) the e a r t h f a u l t l o o p impedance ( h ) the type of energy (EFLI) (Z e ) o f that p a r t of the system e x t e r n a l to and a n d r a t i n g o f the overcurrent protective device(s) (OCPDs) a c t i n g at the of the installation. The statutory Electricity Supply, Quality a n d Continuity Regulations (ESQCR) require that these characteristics should be available f r o m the distribution network operator (DNO) for all sources of supply from the public supply network. G u i d a n c e N o t e 3 : I n s p e c t i o n & Testing © The Institution of Engineering a n d Technology 23 Diagrams, charts or tables 514.9.1 T h e Health a n d S a f e t y at Work etc. Act (HSWA) 1974 generally r e q u i r e s relevant i n f o r m a t i o n to b e available a s a n a i d to s a f e use, inspection, testing a n d maintenance. T h i s m a y i n c l u d e t h o s e i t e m s l i s t e d i n R e g u l a t i o n 514.9.1, a s f o l l o w s : (a) the t y p e and c o m p o s i t i o n of e a c h circuit, including a n d size of c o n d u c t o r s a n d t y p e of wiring. points of utilization, This s h o u l d include number the reference m e t h o d s h o w n i n S e c t i o n 7 o f A p p e n d i x 4 of B S 7 6 7 1 ( M e t h o d s o f i n s t a l l a t i o n ) ; (b) the method used for compliance with the requirements for basic and fault protection and, where appropriate, the conditions required for automatic disconnection; (c) t h e information necessary f o r t h e identification of each device p e r f o r m i n g t h e f u n c t i o n s of protection, i s o l a t i o n a n d switching, a n d its location; a n d (d) any circuit or equipment vulnerable to the electrical tests specified in Part 6 of B S 7671. 2.4 Frequency of subsequent Note: T h e term 'periodic inspection' implies the inclusion of any necessary tests. The time intervals between the recommended inspections dates of periodic inspections need consideration. The p e r i o d t o t h e f i r s t p e r i o d i c i n s p e c t i o n a n d t e s t is r e q u i r e d t o b e c o n s i d e r e d a n d r e c o m m e n d e d by t h e i n s t a l l a t i o n d e s i g n e r a n d o t h e r r e l e v a n t p a r t i e s , a s n o t e d i n Regulations 301.1, a n d 341.1, as p a r t of the design. T h e p e r i o d to e a c h subsequent periodic inspection s h o u l d t h e n b e considered a n d r e c o m m e n d e d as p a r t of c a r r y i n g o u t a p e r i o d i c i n s p e c t i o n a n d test, undertaking that p a r t i c u l a r inspection by the p e r s o n a n d test. It h a s n e v e r b e e n c l a r i f i e d w h e t h e r t h e p r o p o s e d p e r i o d t o a s u b s e q u e n t p e r i o d i c inspection s h o u l d b e m e a s u r e d f r o m the t i m e of t h e previous i n s p e c t i o n o r f r o m the t i m e w h e n a n y i d e n t i f i e d r e p a i r s have b e e n c o m p l e t e d (they m a y never be!). The i n s p e c t o r m u s t t a k e a v i e w o n t h i s ; it w o u l d p e r h a p s b e b e s t t o s e t it f r o m t h e t i m e of the p r e v i o u s inspection, e s p e c i a l l y if there a r e significant r e p a i r s identified o r if t h e i n s t a l l a t i o n i s p o o r l y maintained. An inspector must a l s o use t h e i r e x p e r i e n c e a n d skill to i d e n t i f y a s u i t a b l e p e r i o d f o r a s u b s e q u e n t periodic guidance i n s p e c t i o n a n d they m u s t b e c l e a r about their reasoning. Industry i s available, but c a n o n l y b e general, a n d e a c h i n s t a l l a t i o n is d i f f e r e n t a n d h a s d i f f e r e n t f a c t o r s a f f e c t i n g it. Too f r e q u e n t a n i n s p e c t i o n w i l l c a u s e u n n e c e s s a r y costs, but t o o infrequent, a l l o w significant possible especially if the dangers to develop, installation is p o o r l y maintained, e s p e c i a l l y a s a n installation may gets older. Regulation 652.1 gives s o m e guidance, b u t t h e inspector m u s t m a k e a reasonable a n d i n f o r m e d decision, a n d r e c o r d the r e a s o n s f o r t h a t d e c i s i o n o n the E I C o r E I C R , a s they m a y need to j u s t i f y it. S o m e installations, such a s those subject to l o c a l a u t h o r i t y licensing, a r e r e q u i r e d t o b e i n s p e c t e d a t set p e r i o d s . Section 3.7 contains further 24 G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology guidance on the frequency of periodic inspection and testing. 2 2.5 Initial inspection 2.5.1 General procedure Inspection and, where required, testing should b e carried out and it is recommended that a record of the results should b e retained throughout the different stages of erection to enable the issue of relevant certification on completion of the verification process. It should b e noted that Regulation 641.1 requires inspection and testing to b e carried out during the erection stage of the installation. This is to allow the review and inspection of work that may later b e covered and inaccessible; however, t h e inspector will require necessary design information from the designer before any such inspections during construction or installation. A model Schedule of Inspections is shown in Section 5 of this Guidance Note. 2.5.2 Comments on individual items to be inspected 642.3 BS7671 provides a list of items considered as a minimum to be inspected, but t h e list is not exhaustive. The inspector, where necessary, will inspect and compare the items against data provided by the designer and installer and identify any non-compliances or departures. However, it is not for the inspector to decide what installation items are required o r necessary, or to identify any repairs or modifications. Sect526 a The list is as follows: Connection of conductors Every connection between conductors and equipment/other conductors should provide durable electrical continuity and adequate mechanical strength. It is impractical for an inspector t o physically inspect all connections but they should inspect a representative sample of connection types, especially larger connections, such as o n switchgear and busbars. When checking connections, t h e correct torque setting for screw or bolted terminals should b e used. (It is noted that in some cases, such as high current busbar connections, specialist resistance tests may b e required that are outside the scope of BS7671.) There are four stranding classes of conductor described in B S E N 6 0 2 2 8 : (a) Class 1, solid, conductors. These consist of only a single strand of conductor forming the entire csa. (b) Class 2, stranded, conductors. These consist of at least 6 strands, although some applications in Part 7 of BS 7 6 7 1 specify a m i n i m u m of 7 strands are used for stranding class 2 conductors. (c) Class 5, finely stranded (flexible) conductors, These are m o r e finely stranded than Class 2 stranded conductors, and are typically found in appliance cables, or flexible installation cables. (d) Class 6, extra-finely stranded (extra-flexible) conductors, being m o r e finely stranded again. Guidance N o t e 3 : Inspection & Testing © The Institution of Engineering and Technology 25 2 Some terminals are only suitable for certain conductor stranding classes, as described in Table 2.1. ▼ Table 2.1 Suitability of terminals for certain conductor classes Terminal or connection accessory marking Remarks on suitability of terminal for certain conductors no marking Suitable for any stranding class of conductor. Where stranding class 2, 5 or 6 conductors are subject to frequent disconnection and reconnection at screw or cage type terminals, it is recommended that they are protected against spreading or damage using crimp ferrules. Similarly, stranding class 2, 5 or 6 conductors should ideally have an appropriate crimp, such as a ring crimp, when connecting at a stud type terminal. Preparation of stranded conductors by soldering should only be used under the conditions described in Regulation 526.9. Rigid conductors only. r The terminal is only suitable for stranding class 1 and 2 conductors. Some screwless terminals marked 'r' are not suitable for conductors prepared with crimp ferrules, and manufacturer’s instructions should be followed. The terminal is only suitable for stranding class 1 conductors. sol Some screwless terminals marked 'sol' are not suitable for conductors prepared with crimp ferrules, and manufacturer's instructions should be followed. f b The terminal is only suitable for stranding class 5 and 6 conductors. It is not possible to terminate stranding class 1 or 2 conductors in terminals marked f. Identification of cables and conductors It should b e checked that each core or bare conductor is identified as necessary. The single colour green must not b e used for the identification of live conductors in power circuits, protective conductors, or functional earthing and bonding conductors. The bi-colour combination green-and-yellow is only to b e used for protective conductors. Other than protective earth and neutral (PEN) conductors, conductors that are identified with green-and-yellow throughout their length, either as a single-core cable, or as a core in a multicore cable, must not b e overmarked with another colour or with alphanumeric symbols at terminations, except for the purposes of identifying which circuit t h e cpc serves. Again, it is impractical for a n inspector to physically inspect all identifications, but they should inspect a representative sample of types, especially o n larger conductors, such as to switchgear. 26 G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology ▼ Table 2 . 2 Identification of conductors Function Alphanumeric Colour Protective conductor PE Green-and-yellow (GNYE) Protective bonding conductors PB Green-and-yellow (GNYE) Functional earthing conductor FE Pink (PK) Line of single-phase circuit L Brown (BN) Neutral of single- or three-phase circuit N Blue (BU) Line 1 of three-phase AC circuit LI Brown (BN) Line 2 of three-phase AC circuit L2 Black (BK) Line 3 of three-phase AC circuit L3 Grey (GY) Positive of two-wire circuit L+ Red (RD) Negative of two-wire circuit L- White (WH) Positive (of negative earthed) circuit L+ Red (RD) Negative (of negative earthed) circuit M Blue (BU) Positive (of positive earthed) circuit M Blue {BU) Negative (of positive earthed) circuit L- White (WH) Outer positive of two-wire circuit derived f r o m three-wire system L+ Red (RD) Outer negative of two-wire circuit derived from three-wire system L- White (WH) Positive of three-wire circuit L+ Red (RD) Mid-wire of three-wire circuit M Blue (BU) Negative of three-wire circuit L- White (WH) L Black (BK), Brown (BN), Red (RD), Orange (OG), Yellow (YE), Green (GN), Violet (VT), Grey (GY), White (WH), Pink (PK) or Turquoise (TQ) NorM Blue (BU) AC power circuit Two-wire unearthed DC power circuit Two-wire earthed DC power circuit Three-wire DC power circuit Control circuits, ELVand other applications Line conductor Neutral or mid- wire® Notes: (1) Power circuits include lighting circuits. (2) M identifies either t h e mid-wire of a three-wire D C circuit, o r t h e earthed conductor of a t w o - w i r e earthed D C circuit. (3) Only t h e m i d d l e wire of three-wire circuits m a y b e earthed. (4) A n earthed PELV conductor is blue. Guidance Note 3 : Inspection & Testing © The Institution of Engineering and Technology 27 2 c 522.8 Routing of cables Cables a n d their cable management account systems should be designed a n d installed taking into the mechanical stresses that users of the installation will make upon the installation. 522.6.201 A key r e q u i r e m e n t t o note i s for c a b l e s i n s t a l l e d i n a w a l l o r p a r t i t i o n a t a d e p t h o f l e s s 522 6 . 2 0 3 t h a n 5 0 mm f r o m the m e t a l l i c covering; s u r f a c e . If t h e c a b l e u s e d does not i n c o r p o r a t e a n e a r t h e d o r is not i n s t a l l e d i n a n e a r t h e d conduit, t r u n k i n g o r d u c t ; o r i s not p r o v i d e d w i t h m e c h a n i c a l p r o t e c t i o n s u f f i c i e n t t o p r e v e n t d a m a g e b e i n g c a u s e d by nails, screws protective or similar; o r i s not e x t r a - l o w voltage supplied via separated extra-low (PELV), it w i l l b e n e c e s s a r y to provide voltage additional (SELV) o r protection by m e a n s o f a r e s i d u a l c u r r e n t d e v i c e (RCD) h a v i n g a r a t e d r e s i d u a l o p e r a t i n g c u r r e n t not e x c e e d i n g 3 0 m A . This is a requirement prescribed 522.6.20 even c a b l e z o n e s d e s c r i b e d i n Regulation where c a b l e s a r e r u n within A n o t h e r r e q u i r e m e n t relates to c a b l e s i n s t a l l e d in a wall or partition, of which contains metallic component the 522.6.202. the construction p a r t s such a s studs, f r a m e s o r skins. I r r e s p e c t i v e o f t h e d e p t h a t w h i c h t h e c a b l e s h a v e b e e n installed, t h e y a r e r e q u i r e d t o b e p r o v i d e d with additional exceeding protection by a n R C D having a rated 3 0 m A ; o r b e m e c h a n i c a l l y protected residual sufficient o p e r a t i n g current t o avoid damage not t o them d u r i n g construction of t h e wall o r partition a n d d u r i n g t h e installation of t h e cables; o r comply with the requirements referred to in the previous paragraph. C a b l e s s h o u l d b e r o u t e d i n p r e s c r i b e d z o n e s i n w a l l s (as s h o w n below), in Regulation penetration 522.6.202 (especially in dwellings), by n a i l s a n d screws, etc. It should as identified to assist i n a v o i d i n g damage b e n o t e d that t h e requirements by can also a p p l y t o t h e o t h e r s i d e of t h e w a l l . ▼ Figure 2.1 S 3 3 T h e zones prescribed in Regulation 522.6.202 of B S 7671 WHMM o 3 3 150 m m Room 2 Room 1 Furthermore, w h e r e c a b l e s a r e i n s t a l l e d a t a depth of 5 0 mm o r l e s s f r o m the s u r f a c e of t h e w a l l o r p a r t i t i o n , t h e r e q u i r e m e n t s m e n t i o n e d i n t h e p r e v i o u s p a r a g r a p h also apply. It will be far t o o late at the end of the construction so it is vital that the inspector 28 G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology to view and assess a n y of these things, continually i n s p e c t s the installation w o r k d u r i n g construction. 2 Cables routed in buildings must b e fixed such that they cannot c o m e away from their supports during fires and collapse to block escape routes or entangle firefighters searching the building in smoke-filled conditions. Such entanglements have led to fatalities in t h e past, which could have been avoided with s o m e forethought. escape routes in a building are defined and signed: in open-plan Not all office areas, there can b e several possible routes away f r o m a desk or meeting r o o m across an o p e n office area to an escape stair (see BS 9999) and all such routes should b e kept clear f r o m possible entanglement. An escape route is defined i n the Regulations as a "path to follow for access t o a safe area in the event of an emergency". T h e requirement for surface-run wiring systems n o t t o b e subject to premature collapse in the event of a fire applies to all areas, and not just designated escape routes. It is not difficult to look at a proposed installation and consider the possibilities of cables coming away from their fixings: have only plastic ties been used, is cable tray metal or plastic, is t h e tray upside d o w n and so on? If t h e cable supports are metal and t h e cables are laid in or cleated t o t h e m with metal fixings, then the cable cannot go anywhere. Even if a cable is fixed with plastic ties or clips and could drop, it may only require an occasional metal or fire-resistant fixing to restrain it. I n larger industrial or commercial installations, cable ladder or tray and other services may b e suspended together f r o m concrete structural elements 'drop rods' screwed into the concrete. The inspector by steel wires or cannot physically assess the suitability or the loading of such fixings, but may look at the design data provided to see that what is installed is as the design. Where cables run around or d o w n walls - for example, t o a socket-outlet - and are contained in small-section plastic trunking, the cables should b e fixed inside the trunking if it would b e possible for t h e trunking to deform in heat and the lid come off, thus releasing the cables. Appendix 13 The inspector m u s t also assess any fire protection repairs and fire-stopping where cables have been installed through a fire-rated building structural element or wall. The electrical installation designer should provide information in relation to fire safety with regard to cable routes. Regulation 527.2.1 requires that openings remaining after t h e passage of wiring systems are sealed according to the degree of fire-resistance prescribed for the respective element of the building construction before penetration. The seal is required to: (a) resist the products of combustion to t h e same extent as the elements building construction which have been penetrated; (b) provide the same degree of protection f r o m water penetration of as that required for the building construction element in which it has been installed; (c) b e compatible with the material of the wiring system that it is in contact with; (d) permit thermal movement of t h e wiring system without reducing t h e sealing quality; and (e) have adequate mechanical stability to withstand t h e stresses which may arise through damage to the support of the wiring system due to fire. 527.2.3 Appendix 13 Where wiring system containment (conduit, trunking, and busbar trunking systems) passes through a building element that has specific fire resisting properties and has an internal cross-sectional area greater than 710 m m 2 for example, a round hole of around 3 0 m m diameter, it must b e internally sealed in accordance with Regulation 527.2.3. Guidance Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology 29 422 Appendix 13 T h e concept of a protected escape route h a s been introduced i n B S 7 6 7 1 :20 1 8+A2:2022 . A protected escape route is defined i n B S 7 6 7 1 a s follows: Protected e s c a p e r o u t e . A r o u t e e n c l o s e d w i t h specified fire-resisting construction designated f o r e s c a p e to a place of safety i n the event of a n emergency. Appendix 13 Guidance on escape For safe escape, protected routes a n d f i r e p r o t e c t i o n is provided i n Appendix 13 to B S 7671. as w e l l as b e i n g enclosure i n fire a n d smoke-resisting construction, e s c a p e routes need to b e ' f i r e sterile', i.e. not contain c o m b u s t i b l e material t h a t c o u l d cause a hazard to escaping occupants. Wiring systems w i t h i n a protected e s c a p e route s h o u l d b e l i m i t e d to t h a t f o r : (a) l i g h t i n g ; (b) emergency lighting; (c) f i r e detection a n d alarm; a n d (d) o t h e r e s s e n t i a l s a f e t y s y s t e m s f o r high Cables installed i n f i r e resisting hazard premises. e n c l o s u r e s a r e deemed to b e outside protected escape r o u t e s . Electrical accessories, i n c l u d i n g s o c k e t - o u t l e t s , a r e p e r m i t t e d i n p r o t e c t e d e s c a p e routes, provided they d o not c o m p r o m i s e t h e s t r u c t u r e ' s f i r e resistance. S e e S e c t i o n 527 of B S 7671. 422.2.1 Gables i n protected escape routes shall b e as s h o r t a s practicable. C a b l e s encroaching o n e s c a p e routes shall not be i n s t a l l e d within a r m ' s reach unless they a r e provided with a d e q u a t e p r o t e c t i o n against m e c h a n i c a l d a m a g e t h a t m i g h t o c c u r d u r i n g e v a c u a t i o n . C a b l e c o n t a i n m e n t o r s u p p o r t systems in protected e s c a p e routes must b e classified as n o n - f l a m e p r o p a g a t i n g , a c c o r d i n g t o t h e r e l e v a n t p r o d u c t s t a n d a r d : (a) B S 6 1 3 8 6 f o r conduit systems; (b) B S E N 5 0 0 8 5 f o r t r u n k i n g s y s t e m s ; (c) B S E N 6 1 5 3 7 f o r c a b l e t r a y o r c a b l e l a d d e r systems; and (d) B S E N 6 1 5 3 4 f o r p o w e r t r a c k systems. 132.7 d S e l e c t i o n of c o n d u c t o r s Sect 523 T h e s p e c i f i c a t i o n of c a b l e s u s e d - B S t y p e a n d designation, t e m p e r a t u r e ratings, selection for environmental conditions, c o n d u c t o r category a n d material, certification to a n d c o m p l i a n c e with the r e q u i r e d C o n s t r u c t i o n P r o d u c t s Regulations, b e c h e c k e d , b a s e d o n the d a t a s u p p l i e d by t h e designer etc. - must a n d installer. 422.2.1 Cables in protected e s c a p e r o u t e s must have a minimum 60 °/o light transmittance when tested in accordance with B S E N 61034-2, a n d b e selected f r o m o n e of the following: (a) c a b l e s m e e t i n g the requirements of Regulation 560.8.1 f o r wiring systems of s a f e t y s e r v i c e s r e q u i r e d to o p e r a t e i n f i r e c o n d i t i o n s ; (b) c a b l e s w i t h r e s i s t a n c e t o f l a m e p r o p a g a t i o n a c c o r d i n g t o t h e r e l e v a n t p a r t s o f B S E N 60332-3 series; o r (c) cables i n p e r m i t t e d cable m a n a g e m e n t systems m e e t i n g BS EN 60332-1-2. B S 8 5 1 9 requires cables for both primary a n d secondary supplies to safety services to be f i r e - r e s i s t a n t a n d t o f o l l o w d i v e r s e r o u t e s t h r o u g h t h e building. 30 G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology 2 The cross-sectional area (csa) of conductors should be assessed against the overcurrent protective arrangement and the requirements for limitation of voltage drop, based Sect 525 upon information provided by the installation designer (where available), such as a cable schedule or schematic diagram. Sect 523 Sect 524 Reference should be made, as appropriate, to Appendix 4 of BS7671. Verification of polarity: single-pole device in a TN or TT system 132.14.1 e 530.3.2 must be checked that single-pole devices for protection or switching are installed in line conductors only, and that Edison screw (ES) lampholders are correctly connected. f Accessories and equipment Correct connection (suitability, polarity, environmental factors, etc.) must be checked. 553.1.3 Table 55.1 of BS 7671 sets out the three different types of plug and socket-outlet recognized, their ratings and their associated British Standards. 553.2.2 Particular attention should be made to the correct connection of cable couplers so that pins of connectors (which would be accessible when the couplers are disconnected) are connected to the load or downstream side of the connection. Couplers for cables in which current may flow in either directions, such as some circuits in prosumer’s electrical installations (PEIs), appropriate couplers having live parts protected to at least IP2X on both parts of the coupler when disconnected should be used. 559.5.1.204 Bayonet lampholders B15 and B22 should comply with BS EN 61184 and have a temperature rating T2, as described in that standard. With the exception of E14 and E27 lampholders complying with BS EN 60238, ES lampholders used in TN and TT systems should have the line of the supply connected to their centre contact, and neutral connected to the outer contact. Lighting circuits incorporating B15, B22, E14, E27 or E40 lampholders are only to b e used in a lighting circuit rated up to 16 A. 559.5.1.205 Sect 527 g Selection and erection to minimize the spread of fire Fire barriers, suitable seals and/or protection againstthermal effects should be provided, if necessary, to meet the requirements of BS7671. These are good examples of items which can and should be inspected during the erection stage. Each sealing arrangement built around services penetrations through a fire-rated building element should be labelled by the specialist installer to state its fire rating and inspected to verify that it conforms to the manufacturer's erection instructions and required rating. It is essential, therefore, that inspection should be carried out at the appropriate stage of the work, and that this is recorded at the time for incorporation in the inspection and test documents. A wiring system such as conduit, trunking or ducting that penetrates a building element that has a specified fire rating is to be sealed both internally and externally to the degree of fire resistance of the external element. Fire barrier requirements are detailed in Regulations 527.2.2 and 527.2.3. Products classified as 'non-flame propagating' in accordance with BS EN 61386-1 or BS EN 50085 are liable to catch fire as a result of an applied flame, but in which the flame does not propagate, and which extinguish themselves within a limited time after the flame is removed. The test to classify products as 'non-flame propagating' is a self-extinguishing test, not a fire resistance test. The product cannot be assumed to Guidance N o t e 3 : Inspection & Testing ©The Institution of Engineering and Technology 31 2 protect t h e cable inside it f r o m the effects of afire. The cable should h a v e its own fire/ s m o k e classification. B o t h metallic a n d non-metallic products c a n b e classed a s ' n o n f l a m e propagating1. For f u r t h e r details see IET Guidance Note 4 Protection Against Fire. chapter41 h Measures o f protection against electric shock Tables 2.3 to 2.5 list the various measures of protection against electric shock given in B S 7671. T h e measures are discussed in m o r e detail later in this section. The tables divide up t h e measures into t h o s e that are generally permitted, those that are for use o n l y where access is restricted to skilled o r instructed persons, a n d t h o s e t h a t are f o r u s e only where the installation is controlled o r supervised by skilled or instructed persons. The tables also list the provisions f o r basic protection a n d fault p r o t e c t i o n t h a t m a k e up t h e protective measures. Additional protection m a y also b e specified a s p a r t o f a protective m e a s u r e under certain conditions o f external influence a n d in certain o f t h e special installations o r locations. See later in this section. ▼ Table 2.3 Protective measures generally permitted Protective measure 411 Automatic disconnection of supply (ADS) Protective provisions Basic protection by Fault protection by Basic insulation of live parts and/or barriers or enclosures Protective earthing, protective equipotential bonding and automatic disconnection in case of a fault or Class II equipment 412 413 Sect 414 Supplementary insulation Double or reinforced insulation Basic insulation Electrical separation for the supply of one item of current-using equipment Basic insulation of live parts and/or barriers or enclosures Extra-low voltage provided by SELVor PELV Limitation of voltage, protective separation and basic insulation V Table 2 . 4 or reinforced insulation Protective measures for use only where access is controlled or supervised by skilled persons Protective provisions Protective measure Basic protection by 32 Simple separation from other circuits and from Earth Fault protection by 417.1 Obstacles Obstacles None 417.2 Placing out of reach Placing out of reach None G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology 2 ▼ Table 2 . 5 Protective measures for use only where the installation is controlled or under the supervision of skilled or instructed persons Protective provisions Protective m e a s u r e Basic p r o t e c t i o n by Fault p r o t e c t i o n b y 418.1 Non-conducting location Basic insulation of live parts and/or barriers or enclosures No protective conductor, insulating floor and walls, spacing/obstacles between exposed-conductive-parts and extraneous-co nducti ve-parts 418.2 Earth-free local equipotential bonding Basic insulation of live parts and/or barriers or enclosures Protective bonding, notices, etc. Electrical separation for the supply of more than one item of current-using equipment Basic insulation of live parts and/or barriers or enclosures Simple separation from other circuits and Earth, to non earthed protective bonding, etc. N o t e s : (1) Not recognized for general application. (2) To be used only in special circumstances. 416 (i) Protective provision of basic protection by insulation of live parts and/or barriers or enclosures This p r o t e c t i v e p r o v i s i o n forms p a r t of a n u m b e r of d i f f e r e n t p r o t e c t i v e m e a s u r e s , a s s h o w n i n t h e previous tables. T h e inspection 4]g damaged of this protective d u r i n g installation provision i s to check that insulation a n d t h a t b a r r i e r s a n d enclosures h a s not been have b e e n selected and i n s t a l l e d to p r o v i d e a t l e a s t a d e g r e e of p r o t e c t i o n o f I P X X B o r 1P2X a n d , f o r a h o r i z o n t a l top s u r f a c e t h a t is r e a d i l y accessible, o f a t l e a s t IPXXD o r IP4X, a n d a r e n o t d a m a g e d ( i n s u l a t i o n r e s i s t a n c e is o f c o u r s e a f u n d a m e n t a l test 2 . 6 of this G u i d a n c e Note). (ii) Protective measures generally permitted Automatic 411.2 to b e carried o u t - Section disconnection see of supply (ADS) T h e provision f o r b a s i c protection in t h i s protective m e a s u r e is b a s i c insulation of l i v e parts and/or barriers or enclosures, the inspection of which i s discussed earlier in this section. T h e p r o v i s i o n f o r f a u l t p r o t e c t i o n is p r o t e c t i v e e a r t h i n g , p r o t e c t i v e b o n d i n g a n d automatic each d i s c o n n e c t i o n of s u p p l y i n c a s e of a fault. Although circuit provides evidence b e met, it i s a l s o important that d i s c o n n e c t i o n times to inspect v e r i f i c a t i o n of EFLI f o r a c c o r d i n g to Chapter o r o t h e r w i s e verify t h e following 41 c a n items. Presence of appropriate protective conductors: (a) e a r t h i n g conductor. (b) circuit protective conductors (cpcs). (c) p r o t e c t i v e b o n d i n g c o n d u c t o r s . (d) m a i n b o n d i n g c o n d u c t o r s . R e g u l a t i o n 411.3.1.2 m e t a l l i c p i p e s w i t h i n t h e b u i l d i n g c o n n e c t e d to non-conductive service p i p e s entering t h e building n e e d n o t b e connected to the protective (e) s u p p l e m e n t a r y bonding equipotential conductors (where bonding. required). Guidance N o t e 3 : Inspection & Testing © The Institution of Engineeringand Technology 33 2 The type of system earthing arrangement m u s t b e stated by t h e designer, for example: (a) TN-C-S; (b) TN-S; or (c) TT (earth electrode(s) used as the means of earthing for t h e installation). The earthing arrangement should b e confirmed by the DNO, and not assumed by visual inspection. 411.5 (TN) For installations that receive a low voltage (LV) supply f r o m the public distribution 411.5 (TT) network, the designer should also ascertain whether protective multiple earthing (PME) conditions apply, as this affects the application of certain requirements of BS 7671, such as t h e sizing of main protective bonding conductors, and earthing for some of the special locations in Part 7 (for example, use of a PME earthing arrangement is precluded for some special locations, such as caravan parks and marinas). Guidance is available from the local DNO and in Energy Networks Association publication G12/4 Requirements for the Application of Protective Multiple Earthing to Low Voltage Networks. PME conditions will normally apply in public LV supplies: (a) with a TN-C-S earthing arrangement; and (b) with a PNB earthing arrangement, where the neutral of supply is earthed at some distance downstream of the LV transformer, rather than at the transformer itself. PNB is used by DNOs where it is necessary t o separate HV and LV earthing systems. The EFLImust b e appropriate for the protective device, i.e. RCD or overcurrent device, and within the values given in the relevant tables in Chapter 41 of BS 7671. Double or reinforced insulation 412.1 For double insulation, basic protection is provided protection is provided by supplementary insulation. For reinforced insulation, both basic protection by basic insulation, a n d fault protection and fault are provided by a single application of reinforced insulation between live parts and accessible parts. Where double or reinforced insulation is to b e employed a s t h e sole protective measure, it is important to confirm that t h e installation or circuit so protected will remain under effective supervision so as to prevent any unauthorized change(s) being m a d e that could impair the effectiveness of t h e measure. Electrical separation for the supply of one item of current-using equipment 413.1.1 Electrical separation is a protective measure where basic protection is provided by basic insulation of live parts and/or by barriers and enclosures, in accordance with Section 416, and fault protection is provided by simple separation o f t h e separated circuit f r o m other circuits and f r o m Earth. 34 G u i d a n c e N o t e 3: I n s p e c t i o n & Testing © The Institution of Engineering and Technology 2 Extra-low voltage (ELV) provided b y S E L V o r P E L V Sect 414 ForSELVand PELV, requirements include: 414.1.1 (a) the nominal voltage must not exceed 5 0 V AC or 120 V DC or the lower limits specified for a special location Regulation 414.1.2); 414.1.2 414.3 (b) 414.1.1 (c ) d a suitable source, for example, a safety isolating transformer to BS EN 61558-2-6 or BS EN 61558-2-8; protective separation f r o m all non-SELVor PELV circuits; 414.1. ;; ( ) f° 414.4.4 according to Part 7 of BS 7 6 7 1 (see note to r SELV, basic insulation between the SELV system and Earth; and e ( ) SELV exposed-conductive-parts must have n o connection with Earth, exposed- conductive-parts or protective conductors of other systems. (iii) Protective measures for use only where access is controlled or supervised by skilled persons Obstacles 41 Protection by obstacles provides basic protection only, n o t fault protection. It protects against unintentional contact with live parts. Where this measure is used, the area must b e accessible only to skilled persons or to instructed persons under their supervision. The measure is not to b e used in some installations and locations of increased shock risk. See Part 7 of BS7671. Placing out of reach 417 Placing out of reach also provides basic protection only. The distances referred to in Regulations 417.3.1 and 417.3.2 should b e increased where long or bulky conducting objects are likely to b e handled in t h e vicinity, taking account of the dimensions of those objects. 410.3.5 Bare live parts are only permitted in areas where access is controlled or supervised by skilled persons. The dimensions of passageways should be checked against the information given in Appendix 3 of t h e HSE's guidance o n HSR25 (see Section 729). Sect 729 Section 7 2 9 (Operating and maintenance gangways) covers situations where open switchgear or busbars are permitted and where access is restricted to skilled or instructed persons. Inspection for verification in areas covered by Section 7 2 9 requires careful checking, including the measurement of separation distances, for example, those associated with 'arm's reach', as per Figure 417 of BS 7671; these must b e confirmed with the installation isolated. However, it must be noted that the EAWRtake precedence in all cases and their requirements for accessible live conductors must b e followed in all cases. G u i d a n c e N o t e 3: Inspection © T h e Institution of Engineering & Testing and Technology 35 2 (iv) Protective measures for use only where the installation is controlled or under the supervision of skilled or instructed persons Non-conducting location Where this protective measure is employed, such as in a n electronic equipment test area, it must be verified (amongst other things) that all installed electrical equipment m e e t s the requirements of Section 416 with regard to provisions for basic protection. 418J.2 Further, t h e exposed-conductive-parts of t h e installation should b e so arranged that it is not possible for persons to make simultaneous contact with either two exposedconductive-parts, or an exposed-conductive-part and any extraneous-conductive-part under normal operating conditions, if these parts are liable to b e at different potentials as a result of failure of the basic insulation of a live part. The inspector should confirm the achievement of this and check that within t h e location there are n o protective conductors (see also the specific test for this m e t h o d in Section 2.6.12 of this Guidance Note). 418.2 Earth-free local equipotential bonding The use of this protective measure is intended to prevent the appearance of a dangerous touch voltage under fault conditions. In some cases, this protective measure is combined with the protective measure of electrical separation. Where protection by earth-free local equipotential bonding is employed, it must b e verified (amongst other things) that all installed electrical equipment should meet t h e requirements of Section 416 with regard to provisions for basic protection. ’ All simultaneously accessible exposed-conductive-parts and extraneous-conductiveparts should b e interconnected by local protective bonding conductors. 418.2.3 Measures m u s t b e taken to ensure that the local protective bonding conductors are not connected to Earth either directly or unintentionally via the exposed- and extraneousconductive-parts to which they are connected. A warning notice complying with Regulation 514.13.2 m u s t b e fixed in a prominent position adjacent to every point of access to the location concerned. The inspection, supplemented with tests, should verify that n o item is earthed within the area and that n o earthed services or conductors enter or traverse the area, including t h e floor and ceiling. Inspection should confirm whether or n o t this has b e e n achieved. Electrical separation for the supply to more than o n e item of current-using equipment 418.3 Sect 413 it is intended to supply more than one item of current-using equipment using electrical separation, it will b e necessary to m e e t the requirements of Regulation 418.3. This is in addition to meeting the requirements of Section 413, some of which are referred to earlier in this section of this Guidance Note in relation to the use of electrical separation for the supply of one item of current-using equipment. 418.3.3 The separated circuit should b e protected f r o m damage and insulation failure. Any exposed-conductive-parts of t h e separated circuit should b e connected together by insulated, non-earthed protective bonding conductors, which should n o t b e connected to the protective conductor or exposed-conductive-parts extraneous-conductive-parts. 36 G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology of any other circuit or to any 2 418. Socket-outlets should have a protective conductor contact, which is connected to the protective bonding system described above. All flexible cables should contain a protective conductor for use as a protective bonding conductor, except where such a cable supplies only items of equipment having double or reinforced insulation. If two faults affecting two exposed-conductive-parts occur, and where conductors of different polarity feed these, a protective device should disconnect the supply in accordance with t h e disconnection 418/ time given in Table 41 .1 . The product of t h e nominal voltage (volts) a n d length (metres) of the wiring system should not exceed 100,000 Vm and the length of the wiring system (metres) should n o t exceed 5 0 0 m. (v) Additional protection Additional protection by one o r more RCDs 415.1.1 It should b e confirmed that an RCD selected to provide additional protection has a rated residual operating current not exceeding 3 0 m A and complies with the relevant standards. Generally, all socket-outlets up to and including 3 2 A rating should b e provided with additional protection by a 3 0 m A RCD; however BS 7671 allows this to b e omitted for some socket-outlets in certain locations such as non-domestic installations where a written risk assessment shows that such additional protection is not required. It is not for the inspector to consider or approve the risk assessment, but the inspector should see the assessment to prove that it exists, so that the requirement of the regulation is fulfilled. The assessment should also b e attached to the Electrical Installation or MEIWC, for future reference. 415J.2 It should also b e confirmed that appropriate protective measures in accordance with Sections 411 to 414 are in place, as an RCD m u s t not b e used as the sole means of protection against electric shock. Additional protection by supplementary protective equipotential bonding 415.2.1 Where supplementary bonding is provided, it should encompass all simultaneously accessible exposed-conductive-parts of fixed equipment, extraneous-conductive-parts and the protective conductors of all equipment in the location where this protective measure is being applied. 415.2.2 The effectiveness of supplementary equipotential bonding, as provided, may b e verified where the resistance between simultaneously accessible exposed-conductive-parts and extraneous-conductive-parts fulfils whichever of the following conditions is applicable: (a) for AC systems, R < 5 0 V/I a ; and Note: In medical locations of Group 1 and Group 2, and in fuel filling stations installed in accordance with APEAGuidance for Design, Construction, Modification, Maintenance and Decommissioning of Filling Stations, the voltage is reduced from 50 V to 25 V. G u i d a n c e N o t e 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology 37 2 (b) for DC systems, R < 120 V/I a where la is the operating current of the protective device in amps (for overcurrent devices, this is the 5 s operating current, and for RCDs, | n). 5313 RCDs should be selected in accordance with Regulation 531.3. Selection of RCDs should take into account the residual fault current operating characteristics of loads with respect to DC components. Type AC RCDs shall only be used for fixed equipment, where it is known that the load current contains no DC components. This precludes the use of socket-outlets incorporating Type AC RCD protection (SRCDs)to BS 7288. Note: Type AC RCDs are not p e r m i t t e d i n medical locations. The RCD residual current operating characteristic Type can be identified by the marking provided by the manufacturer. See Figure 2.34. ▼ T a b l e 2 . 6 Types o f RCD currently recognized by B S 7 6 7 1 Description of RCD Abbreviation used in BS 7671 Residual current operating characteristic type (If not from BS 7671) Standard Type AC (Note 1) Residual current circuit-breaker without overcurrent protection B S E N 61008 Type A RCCB Type F BS EN 62423 Type B Type AC (Note 1) Residual current circuit-breaker with overcurrent protection B S E N 61009 Type A RCBO Type F B S E N 62423 Type B Socket-outlet incorporating RCD protection Fused connection unit incorporating RCD protection Circuit-breaker incorporating residual current protection SRCD Type A (Note 2) BS7288 Type AC (Notes 1,2) FCU RCD Type A (Note 2) BS7288 Type AC (Notes 1,3) CBR Type A (Note 3) BS EN 60947-2 Type B (Note 3) Type AC (Notes 1,3) Modular RCD MRCD Type A (Note 3) BS EN 60947-2 Type B (Note 3) Notes: 1 2 3 4 38 O n l y t o b e used for fixed equipment, w h e r e it is k n o w n that t h e load current contains n o DC components. Additional protection only. Cannot b e used to m e e t disconnection times required by Chapter 41 o f BS 7 6 7 1 for automatic disconnection of supply. For operation b y skilled or instructed persons only. RCCBs, RCBOs, CBRs a n d MRCDs are also available w i t h a time-delay option. These are k n o w n as S-Type a n d identified with t h e relevant marking, see Figure 2.34. Guidance N o t e 3: Inspection & Testing © The Institution of Engineering and Technology 2 Sect 515 ' Prevention of m u t u a l detrimental influence Regulations 132.11 and 515.1 require electrical equipment to b e so selected and erected that there will b e no harmful influence (such as electromagnetic interference (EMI) or heat) between t h e electrical installation and other electrical and non-electrical installations. The inspector is advised to give careful thought to this while carrying o u t t h e inspection. 132.5.1 This, however, does not include the detrimental influence of other systems onto t h e electrical installation, such as water leaks or splashing, which are covered by the requirements of Regulation 132.5.1. Sect 537 j Isolating and switching devices BS EN 60947-1 Low voltage switchgear and controlgear. General rules defines standard utilization categories that allow for conditions of service use and t h e switching duty to b e expected. All switch utilization categories must b e appropriate for the nature of the load (see Table 2.7). It would b e part of the design to specify the appropriate t y p e of device. GN2 Guidance Note 2 provides m o r e comprehensive guidance on this subject. It should b e consulted and its contents taken into account. ▼ Table 2 . 7 Examples of utilization categories for alternating current installations Utilization category Frequent operation Infrequent operation Typical applications AC-20a AC-20b Connecting and disconnecting under no-load conditions AC-21a AC-21b Switching of resistive loads, including moderate overloads AC-22a AC-22b Switching o f mixed resistive and inductive loads, including moderate overloads AC-23a AC-23b Switching of motor loads o r other highly inductive loads If switchgear to BS EN 60947-1 is suitable for isolation, it will b e marked with the symbol for isolation (references IEC 60417-6169-1 and IEC 60617-07-01-03) shown in Figure 2.2. ▼ Figure 2 . 2 Basic symbol for isolation function This may b e endorsed with a symbol advising of function, for example, for a switch disconnector providing isolation as illustrated in Figure 2.3. ▼ Figure 2 . 3 Symbol marked on a switch disconnector providing isolation Guidance N o t e 3: I n s p e c t i o n & Testing © The Institution of Engineering and Technology 39 2 Table 537.4 Guidance on the suitability or otherwise of protective, isolation and switching devices t o be employed for one or more of the functions of isolation, emergency switching and functional switching is given in Table 537.4 of B S 7 6 7 1 a n d in Guidance Note 2. The inspector should carry o u t an isolation review to check that effective isolation can b e achieved, b u t it is n o t the inspector's responsibility t o resolve any apparent shortcomings or problems with the isolation and switching design. The review could include, where appropriate, locking-off and inspection or testing to verify that the circuit is dead and n o other source of supply is present. The designer should also identify where it may b e necessary to isolate the neutral conductor. Note (5) to Table 537.4 i n B S 7 6 7 1 points out that circuit-breakers and RCDsare n o t intended for frequent load switching or functional switching unless they are approved by the device manufacturer for this duty. The note gives further guidance relating to this a n d the inspector is at liberty to make a comment o n this use if it is inappropriate. 543.3.3.101 BS 7671 does not allow a switching or isolating device to b e placed in the earth or protective conductor, other than a plug and socket-outlet, except for the special conditions outlined in Regulations 543.3.3.101. k Presence of undervoltage protective devices Suitable precautions should b e in place where a reduction in voltage, or loss and subsequent restoration of voltage, could cause danger. Normally, such a requirement concerns only motor circuits. If precautions are required, they will have been specified by the designer; however, the devices used must b e confirmed as matching the equipment specification and the relevant regulations in Section 445. Chap 4: | Protective a n d monitoring devices Some protective devices have user or on-site configurable settings. The inspector needs to confirm that the installer has correctly set up such protective devices. 421.1.7 Arc fault detection devices (AFDDs) are designed to provide protection by monitoring the change of current f l o w in a final circuit due to a possible cable conductor fault that could cause an arc and possible fire. BS 7671 requires AFDDs t o b e provided for single-phase AC circuits supplying socket-outlets with a rated current not exceeding 3 2 A in electrical installations for: (a) Higher Risk Residential Buildings (HRRBs); Note: HRRBs are assumed to b e residential buildings over 18 m i n height or in excess of six storeys, whichever is met first. It is anticipated that i n m a n y areas higher risk residential buildings will b e defined in legislation which can b e subject to change over time, as well as in risk management procedures adopted by fire a n d rescue services. Current legislation should be applied. (b) Houses in Multiple Occupation (HMOs); (c) Purpose-built student accommodation; and (d) Care homes. For other installations, BS 7 6 7 1 recommends their use for AC final circuits supplying socket-outlets not exceeding 3 2 A, but it is for the designer to decide on their use in other installations, a n d the inspector cannot comment if they are not installed. 40 Guidance Note 3 : Inspection & Testing © The Institution a n d Technology of Engineering 2 Some makes of AFDDs have a manual test button (like an RCD) a n d this should b e pressed at commissioning and user advised to press at six monthly intervals to prove operation. Other AFDDs have an automatic test facility which will trip t h e device in t h e event of a malfunction, this will b e indicated on the device. Sect 443 The guidance for the application revised in BS 7671:2018+A2:2022, of surge protective devices (SPDs) has been providing for protection against switching surges and surges of atmospheric origin (lightning strikes). Except for simple installations for which t h e requirements of Sections 443 and 5 3 4 of BS 7 6 7 1 can b e followed, surge protection, and where applicable lightning protection systems, will usually b e designed and installed, by specialist suppliers i n accordance with the relevant parts of BS EN 6 2 3 0 5 . In these cases, the inspector can only review what is installed against the scheme documentation provided by the specialist suppliers, and review their test and commissioning documentation. Sect m Labelling of protective devices, switches and terminals 514 8 J Each protective device must b e arranged and identified so that the circuit protected 514.9.1 can b e easily identified; a diagram or chart indicating t h e function of each circuit and size of conductors is required. The inspector will need this key document in order to carry out much of their inspection and testing. n Selection of equipment and protective measures appropriate to external influences Equipment must b e selected with regard to its suitability for the environment at its specific location —ambient temperature, heat, water, foreign bodies, corrosion, impact, vibration, flora, fauna, radiation, building use and structure. A careful inspection is necessary to confirm the suitability of each item of equipment. ° Adequacy of accessto switchgear and equipment Sect 513 Every piece of equipment that requires operation or attention by a person m u s t b e so installed that adequate and safe means of access (related to the amount of its use) and sufficient working space are afforded. The inspector should check that these requirements P are met. Warning and instruction notices Warning and instruction notices, suitably located, are required to b e installed for: (i) warning of voltage; (ii) warning of live parts that are not capable of being isolated by a single device; (iii) periodic inspection and testing; (iv) periodic user testing of RCDs; (v) periodic user testing of AFDDs; (vi) earthing and bonding connections; (vii) alternative supplies; (viii) presence of SPDs; (ix) high protective conductor current; and (x) the presence of diagrams, instructions or similar information. Instruction notices (iii), (iv), (v) and (viii) above need not b e applied for installations in domestic (household) premises where t h e information is recorded as part of t h e certification for initial verification, complete with the Guidance for Recipients as detailed in Appendix 6 of BS7671. Guidance Note 3: Inspection & Testing © The Institution of Engineering and Technology 41 2 Appendix 11The minimum size requirements for text o n warning signs and instruction notices have been revised in Amendment 2 : 2 0 2 2 t o BS 7671:2018, and reference is n o w made to BS EN IEC/IEEE 82079-1 Preparation o f information for use (instructions for use) o f products. Principles and general requirements. Warning notices and other safety signs are additionally required to comply with BS ISO 3 8 6 4 series Graphical symbols. Safety colours and safety signs and BS EN ISO 7010 Graphical symbols. Safety colours and safety signs. Registered safety signs. These standards permit far more flexibility in text sizes than t h e requirements of previous versions of BS7671. Guidance and examples are provided in Appendix 11. The warning and instruction notices in Section 514 of B S 7 6 7 1 are discussed below. 514.10.1(j) Voltage ► Warning notices are required where a nominal voltage exceeding 2 3 0 V to earth exists within an item of equipment or enclosure and where the presence of such a voltage would n o t normally b e expected. An example would b e the use of a 6 9 0 V three-phase AC power transformer used on an American air base located in the UK. Examples are shown in Figure 2.4. Note: In m o s t three-phase 2 3 0 / 4 0 0 V systems, t h e voltage t o Earth is 2 3 0 V. It is n o t normally necessary in those installations to provide a voltage warning label for t h e purposes of Regulation 514.10.1. ▼ Figure 2 . 4 Examples of t h e warning notice required b y Regulation 514.10.1 a. general use (font size 14 pt) /X WARNING / 7 \ 400/690 V b. use on surfaces less than 1 0 cm 2 (font size 7 pt) A WARNING / 7 \ 400/690 V 514.11.1(jj) Isolation ► Warning notices are required where live parts are not capable of being isolated by a single device. The location of disconnectors should also b e indicated, except where there is n o possibility of confusion. (iii) Periodic inspection and testing 514.12.1► The wording of t h e required instruction notice is given in Regulation 514.12.1. Examples are shown in Figure 2.5. This notice is not required for installations i n domestic (household) premises where the information is recorded as part of the certification for initial verification, complete with the Guidance for Recipients as detailed in Appendix 6 of BS7671. 42 G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology 2 ▼ Figure 2 . 5 Examples of the instruction notice required by Regulation 514.12.1 a. general use (font size 14 pt) IMPORTANT This installation should be periodically inspected and tested and a report on its condition obtained, as prescribed in BS 7671 Requirements for Electrical Installations. Date of last inspection Recommended date of next inspection b. use on surfaces less than 10 cm2 (font size 7 pt) IMPORTANT This installation should be periodically inspected and tested and a report In its condition obtained, as prescribed in BS 7671 Requirements for Electrical Installations. _ . .. „ T S June 2022 Date of last inspection ................................ .777.77 Recommended date of next inspection (iv) 514.12.2 ► RCDs T h e w o r d i n g of t h e required instruction Examples are shown i n Figure 2.6. This notice is not required n o t i c e is given i n Regulation f o r installations i n domestic (household) 514.12.2. premises w h e r e the i n f o r m a t i o n is r e c o r d e d as p a r t of t h e certification f o r initial verification, c o m p l e t e w i t h t h e G u i d a n c e for Recipients as detailed i n Appendix 6 of B S 7 6 7 1 . ▼ Figure 2 . 6 Examples of the instruction notice required by Regulation 514.12.2 a. general use (font size 14 pt) This installation, or part of it, is protected by a device which automatically switches off the supply if a fault develops. Test six-monthly by pressing the relevant test button(s) which should operate the device. Afterwards, manually switch o n the device. If the device does not operate, indicates a fault, seek expert advice. or b. use on surfaces less than 10 cm 2 (font size 7 pt) This installation, or part of it, is protected by a device which automatically switches off the supply if a fault develops. Test six-monthly by pressing the relevant test button(s) which should operate the device. Afterwards, manually switch on the device. If the device does not operate, or indicates a fault, seek expert advice. Guidance Note 3: Inspection & Testing © The Institution of Engineering and Technology 43 2 (v) AFDDs ► Where AFDDs are installed, those provided with a manual test button (as RCDs) should b e tested every six months by pressing t h e button. An instruction notice t o this effect should be provided. The text of the RCD notice in Regulation 514.12.2 can b e used (see examples in Figure 2.6). Some AFDDs are self-testing. AFDDs may b e provided in a single package also containing overcurrent and/or residual current protective devices. This notice is not required for installations in domestic (household) premises where the information is recorded as part of the certification for initial verification, complete with t h e Guidance for Recipients as detailed in Appendix 6 of BS 7671. (vi) Earthing and bonding connections ► The requirements for t h e warning notice and its wording are given in Regulation 514.13.1. Examples are shown i n Figure 2.7. ▼ Figure 2.7 Examples of the warning notice required by Regulation 514.13.1 ”zz“ Safety Electrical Safety Electrical Connection - Connection - Do Not Remove Do Not Remove BS 7671 permits the notice to b e provided by a clamp complying with BS 951 (Figure 2.8). ▼ Figure 2.8 Example of a warning notice provided on a BS951 clamp Where protection by earth-free local equipotential bonding (Regulation 418.2.5 refers) or by electrical separation for the supply to more than one item of equipment (Regulation 418.3 refers), warning notices with t h e wording given in Regulation 514.13.2 are required. An example is provided in Figure 2.9. ▼ Figure 2.9 Example of the warning notice required by Regulation 514.13.2 The protective bonding conductors in this location MUST NOT BE CONNECTED TO EARTH. Equipment having exposedconductive-parts connected to earth must not be brought into this location 44 Guidance Note 3: Inspection & Testing © The Institution of Engineering and Technology 2 (vii) Alternative supplies ► For installations with alternative or additional voltage sources, a 'multiple-supplies’ warning notice is required at mains positions, points of isolation, distribution boards and at any remote metering. The wording of t h e notice is given in Regulation 514.15.1. An example is shown in Figure 2.10. ▼ Figure 2.10 E x a m p l e of the warning WARNING Multiple Supplies notice r e q u i r e d by Regulation 5 1 4 . 1 5 . 1 Isolate all electrical supplies before carrying out work Isolate primary supply at Isolate alternative sources at Solar PV inverter (outside wall) (viii) Presence of SPDs 514.16=1 ► Regulation 514.16.1 requires a label at or near a distribution board that contains, or supplies circuits with, SPDs.lt is important to identify where SPDs are in the installation, as they may b e damaged by insulation resistance tests, o r affect insulation resistance test results. This notice is not required for installations in domestic (household) premises where t h e information is recorded as part of t h e certification for initial verification, complete with the Guidance for Recipients as detailed in Appendix 6 of B S 7 6 7 1 . The information may b e clearly marked o n SPDs installed at the distribution board o r consumer unit. Some SPDs are supplied with a suitable label. 514.17 543.7.1.205 (jx ) High protective conductor current ► A warning notice must b e provided at the relevant distribution board indicating circuits that have a high protective conductor current, as required by Regulation 543.7.1.205. ▼ Figure 2.11 E x a m p l e of t h e warning notice r e q u i r e d by Regulations 5 1 4 . 1 7 a n d 543.7.1.205 / < A WARNING 7 \ High protective conductor currents y ■ The following circuits may have high protective conductor currents: Ring final circuits iLl and 2.L2. Guidance Note 3: Inspection & Testing ©The Institution of Engineering and Technology 45 2 514.9.1 (x ) Presence of diagrams, instructions and similar information ► The presence of diagrams, charts or tables, or an equivalent f o r m of information for t h e work being inspected, should b e verified. The form of information should b e legible and durable, a n d should indicate all of the following: (a) t h e t y p e and composition of each circuit (including t h e points of utilization served, the number and size of conductors, a n d t h e t y p e of wiring); (b) the m e t h o d used for compliance with Regulation 410.3.2 (that is, t h e protective measures used for basic and fault protection); (c) t h e information necessary for t h e identification of each device performing t h e functions of protection, isolation and switching, and its location; and (d) any circuit o r equipment that is vulnerable to the electrical tests as required by Part 6. For a simple installation, t h e foregoing information can b e given in t h e f o r m of a schedule. An additional copy of t h e Schedule of Circuit Details provided within or adjacent to each distribution board is likely to m e e t this requirement. In domestic (household) premises or similar installations the schedule does not have to b e fixed o n o r near the distribution board or consumer unit, provided that the information is contained along with t h e certification for initial verification, complete with Guidance for Recipients according to Appendix 6 of BS7671. A complex installation would obviously require more comprehensive information, in the f o r m of a record or of 'as-built' drawings and O & M documents. Diagrams, charts, warning and information and instruction notices should comply with the standards specified in Regulation 514.9.2. Non-standard colours Over time, there have been changes in the colours for identification in BS 7671, and, before BS 7671:2001(2004), 1992, previous editions of conductors of the Wiring Regulations. In awarning notice was introduced for installations using conductor identification colours to different versions of BS7671. Regulation 514.14.1 was deleted in BS 7671 :2018+A2:2022 and such a w a r n i n g notice will, in future, n o t b e necessary t o comply with BS 7671 . There is nothing to prevent the continued use of this type of warning notice. q Erection methods Chapter 5 2 contains detailed requirements on selection and erection. Fixings of switchgear, cables, conduit, fittings, etc. must b e adequate for the environment and a detailed visual inspection is required during the erection stages, as well as at completion. Regulation 521.10.202 requires that cables are to b e supported so they will n o t collapse and come away f r o m their fixings in the event of a fire and impede the escape of persons f r o m buildings. This can usually b e achieved by installing a metal cable fixing at reasonable intervals. 2.5.3 Inspection checklist Listed below are requirements to b e checked w h e n carrying out an installation inspection. The list is not exhaustive. The inspector can check against t h e design and installation data provided by the designer and installer and report any non-compliances noted, but cannot make any requirements. 46 Guidance Note 3: Inspection & Testing © The Institution of Engineering and Technology 2 General (a) Equipment complies with a product standard or equivalent (511.1). (b) Equipment is installed using good workmanship (134.1.1). (c) Equipment is accessible for operation, inspection and maintenance (513.1). (d) Equipment is suitable for local atmosphere and ambient temperature (512.2). For installations i n potentially explosive atmospheres, the requirements of BS7671 are supplemented by the requirements or recommendations of other British or Harmonized Standards or by those of the person ordering the work (110.1.3). (e) Final circuits are separate, including t h e neutral conductors (314.4). (f) Protective devices are identified to indicate the circuits they protect (514.8.1). (g) Protective devices are adequate for their intended purpose, including AFDDs and SPDs, where installed (Ch. 53). (h) Disconnection times for protection against electric shock are likely to b e met by installed protective devices (Ch. 41). (i) All circuits are identified (514.1,514.8,514.9). 0) Main switch is provided (462.1.201). (k) Supplies to any safety services are correctly installed, for example, fire alarms to BS 5 8 3 9 and emergency lighting to BS 5 2 6 6 (Ch. 56). This does not include any inspection of the safety systems, which should b e inspected maintained by specialists. and (l) Auxiliary circuits are installed (557). (m) Means of isolation are labelled (514.1, 537.2.7). (n) There is provision for disconnecting the neutral (Ch. 4 6 ; 537.2.8). (o) Main switches t o single-phase installations, intended for use by an ordinary person, for example, domestic, shops and office premises, are to b e double pole (462.1.201). (p) RCDs are provided where required (411.3.3, 411.3.4, 411.4, 411.5, 415.1, 422.3.9, 522.6.201, 703.411.3.3, 522.6.202, 704.410.3.10, 708.415, 708.553.1.14, 532.1, 701.411.3.3, 702.53, 702.55.1, 702.55.4, 704.411.3.2.1, 705.411.1, 705.422.7, 709.531.2, 706.410.3.3, 710.410.3, 710.411.4,710.531.3, 711.410.3.4, 711.411, 712.531.3.5.1, 714.411.3.4, 717.411.6.2, 717.413, 717.415.1, 721.415.1, 722.531.3, 740.410.3, 740.415.1, 753.411.3.2, 753.415.1). (q) Selectivity between RCDs is considered to avoid danger (314.1,314.2, 531.3). (r) Main earthing terminal (MET) is provided (542.4.1), is readily accessible and is identified where separate from switchgear (514.13.1). (s) There is provision for disconnecting t h e earthing conductor (542.4.2). (t) Cables used comply with British or Harmonized Standards and with Construction the Products Regulation (Appendix 4 of BS 7671). (u) Earth tail pots are installed where required o n mineral-insulated cables (543.2.7). (v) Non-conductive finishes o n enclosures are removed where necessary to ensure good electrical connection and, if necessary, made good after connecting (526.1). (w) There are adequately rated distribution boards. Distribution boards to t h e relevant parts of BS EN 6 0 4 3 9 or BS EN 61439 may have a rated diversity factor (RDF) stated by t h e manufacturer for the assembly, or a group of circuits. For example, if an assembly has an RDF of 0.8, any combination of outgoing circuits in the assembly can b e loaded to 8 0 7o of their rated current, provided the total load o n the outgoing circuits does not exceed the rated current of the assembly (642.2). (x) Correct fuses or circuit-breakers are installed (Section 531, Section 533). (y) All connections are secure (134.1). (z) Protection is provided against voltage disturbances, including overvoltages, where required (Ch. 44). Guidance Note 3: Inspection & Testing ©The Institution of Engineering and Technology 47 2 (aa) Measures are taken against electromagnetic disturbances, where required (Ch. 44). (ab) Overcurrent protection is provided, where applicable (Ch. 43). (ac) There is suitable proximity (separation or segregation) of circuits (528). (ad) Label notice for first periodic inspection and test is provided (514.12.1). (ae) Sealing of the wiring system, including fire barriers (527.2). (af) Cables and wiring systems are installed and supported such that they will not b e liable to premature collapse in the event of afire (521.10.202). (ag) There is a suitable degree of protection (IP Code) appropriate to external influences when installed in accordance with the manufacturer's instructions (522.3.1, 559.3.1). Switchgear (a) Meets requirements of the relevant parts of BS EN 61008, BS EN 61009, BS EN 60947-2, BS EN 60898, or BS EN 61439, where applicable, or equivalent (Section 511). (b) Is securely fixed (134.1.1) and suitably labelled (514.1). (c) Switchgear assemblies, including consumer units, are complete with, or additionally housed in, fire protecting enclosures (421.1.201). (d) Non-conductive finishes o n switchgear are removed at protective connections and, if necessary, made good after connecting (526.1). conductor (e) Suitable cable glands and gland plates are used (526.1). (f) Switchgear is correctly earthed (Ch. 54). (g) Account has been taken of environmental conditions likely t o b e encountered, i.e., switchgear is suitable for t h e foreseen environment (512.2). (h) Switchgear is suitable as a means of isolation as design, where applicable (Ch. 46, 537.2). (i) Need for isolation, mechanical maintenance, emergency switching is m e t where required by design (Ch. 4 6 , 537). and functional (j) Firefighters’ switch is provided where required and labelled for identification and operation (537.4). (k) All connections are secure (526). (l) Cables are correctly terminated a n d identified (514, 526). (m) There are n o sharp edges o n cable entries, screw heads, etc., which could cause damage to cables (134.1.1,522.8.11). (n) There is adequate access, lighting a n d working space (132.12 and 513.1). General wiring accessories (a) Complies with appropriate standards, for example, BS 5 7 3 3 (general accessories) or BS EN 6 0 6 7 0 - 2 2 (junction boxes) (511.1). (b) Box or other enclosure is securely fixed (134.1.1). (c) Metal box or other enclosure is earthed where required (Ch. 54). (d) There are n o sharp edges o n cable entries, screw heads, etc. which could cause damage to cables (134.1.1,522.8.11). (e) Non-sheathed cables, and cores of cable f r o m which sheath has been removed, are not exposed outside the enclosure (526.8). (f) Conductors are correctly identified (514.3). (g) Bare protective conductors having a csa of 6 m m 2 or less are to b e sleeved green-and-yellow (514.4.2, 543.3.201). (h) Terminals are tight a n d containing all strands of the conductors (526). (i) Cable grip correctly used, or clips fitted to cables, prevent strain o n the terminals (522.8.5, 526.6). (j) The current rating is adequate (512.1.2). 48 G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology 2 (k) Accessories installed in protected escape routes must n o t compromise t h e structure’s fire resistance. The accessories should, where necessary, have any fire resisting pads installed where these are recommended by t h e manufacturer (Section 527, Appendix 13). Notes: 1 Reference should a l s o be m a d e to B S 8 3 0 0 series a n d t h e recommendations in t h e r e l e v a n t A p p r o v e d D o c u m e n t M of t h e B u i l d i n g R e g u l a t i o n s 2010 W a l e s a n d the contained for England a n d Scottish Building Standards with regard to t h e h e i g h t s a t w h i c h socket-outlets, switches a n d other controls s h o u l d b e installed, in o r d e r to afford c o m p l i a n c e with B u i l d i n g R e g u l a t i o n s . See a l s o the I E T publication Electrician's 2 Guidance o n t h e s e l e c t i o n of protective, Guide to the Building i s o l a t i o n a n d switching Regulations. devices in p r o v i d e d in T a b l e 537.4 o f B S 7 6 7 1 . Lighting controls (a) Lightswitches comply with BS 3 6 7 6 or BS EN 60669-1 (511.1). (b) Lighting controls are selected for external influences (512.2). (c) Single-pole switches are connected in line conductors only (132.14.1). (d) Correct colour coding or marking of conductors is used (514.3). (e) Exposed-conductive-parts, for example, metal switch plate or surface-mounted metal back box, are connected to t h e relevant cpc (Ch. 54). (f) The current rating, allowing for any capacitive or inductive effects as given in the design cable ratings, is adequate (512.1.2). (g) A device that simultaneously disconnects all line conductors is provided where a group of luminaires is divided between three line conductors of a circuit with only one c o m m o n neutral (559.5.5). (h) Switch is labelled to indicate purpose, where this is not obvious (514.1.1). (i) There are appropriate controls suitable for the luminaires (559.5.1.206). ( j ) Standard wall accessory/switches are installed beyond zone 2 in a location containing a bath or shower (701.512.3). Lighting points (a) Lights connected via a recognized accessory (559.5.1), batten lampholders or pendant sets are in compliance with BS EN 6 0 5 9 8 . (b) Ceiling rose complies with BS 67 (559.5.1). (c) Luminaire supporting couplers comply with BS 6972 or BS 7001 (559.5.1). (d) Installation couplers comply with BS EN 61535 (559.5.1). (e) A recognized connecting device is used for luminaires that d o n o t provide a device for connection (f) of t h e supply (559.5.4). Track systems comply with BS EN 60570 (559.3.4 and 715.521.1). (g) Systems for ELV lighting comply w i t h BS EN 60598-2-23 (715.521.1). (h) Bare conductors of ELV lighting installations comply with all requirements of Regulation 715.521.106 (715.521.1). (i) There is not m o r e than one flex, unless designed for multiple pendants (559.5.1.202). ( j ) Flex support devices are used and are suitable for the mass suspended (559.5.2). (k) Switch-lines are identified (514.3.2 and Appendix 7 of BS 7671). For two-core switch wires, blue conductors are overmarked with b r o w n or L a t terminations; for three-, four- or five-core cables, all non-brown line conductors of switch and intermediate strappers are overmarked at terminations w i t h b r o w n or L. (l) Penetrations in fire-rated ceiling are m a d e good. Suitable fire-rated luminaires used where t h e luminaire traverses fire rated ceilings (527.2.1). Recessed downlighters should b e checked for thermal damage. Guidance Note 3: Inspection & Testing © The Institution of Engineering and Technology 49 2 (m) Ceiling roses and similar not used for circuits have a supply exceeding 2 5 0 V (559.5.1.201). (n) Protection f r o m ultraviolet (UV) radiation (if any) is provided to external wiring within or passing through a luminaire (559.5.6). Socket-outlets (a) Socket-outlets comply with BS 5 4 6 , BS 1363-2 or BS EN 6 0 3 0 9 - 2 (553.1.3) and are shuttered for household a n d similar installations (553.1.201). (b) Where used for electric vehicle charging, socket-outlets complying with BS 1363-2 are of a type approved by the socket-outlet manufacturer for such use (722.55.101.0.201.1). (c) Mounting height above t h e floor or working complies surface suitable (553.1.6) (Also with Part M of the Building Regulations and the Scottish equivalent, where relevant - see Note above). (d) Polarity is correct (643.6). (e) If in a location containing a bath or shower, socket-outlets are installed at least 3 m horizontally f r o m t h e bath or shower, w i t h t h e exception of a shaver supply unit or SELV (701.512.3). (f) Socket-outlets are suitably protected against external influences where installed near sinks and cookers. It is recommended that socket-outlets should b e installed at least 3 0 0 m m horizontally from t h e edges of a sink or washbasin (excluding drainer) and at least 1 0 0 m m horizontally f r o m the edge of a h o b or freestanding cooker (see IET Guidance Note 1: Selection and Erection). (g) Socket-outlets are suitably protected against t h e expected external influences where mounted in a floor (512.2). (h) Socket-outlets are not used to supply a water heater having uninsulated elements (543.3.1). (i) Where metal conduit (including the accessory box) or earthed cable sheath or similar is used as a protective conductor, there is presence of an earth tail between t h e accessory box and the socket-outlet terminal (543.2.7). (j) Additional requirement is provided by a 3 0 m A RCD or a risk assessment is provided for specific non-domestic (k) Socket-outlets with socket-outlets (411.3.3). integral universal serial bus (USB) charging provision, or other electronic devices such as powerline or wireless local area networking functionality, comply with BS 1363-2:2016 or BS 1363-2:2016+AI:2018. Junction boxes, joint box and terminations (a) All cable joints and terminations are installed so that they are accessible for future inspection (except for soldered, encapsulated, etc. joints or marked maintenance-free accessory. Some connecting devices must b e contained in an enclosure meeting maintenance free (526.3). t h e manufacturer's requirements to b e classed as (b) Enclosures of terminals provide suitable protection against mechanical damage (526.7). Fused connection unit (a) The rating and fuse are correct (533.1). (b) The fused connection unit complies with BS 1363-4 (Table 537.4, 559.5.1 vii). Cooker control unit (a) The cooker control unit is sited to o n e side and is l o w enough for accessibility and to prevent flexes trailing across radiant plates (522.2.1). (b) The cable t o the cooker is fixed to prevent strain on connections 50 G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology (522.8.5). 2 Conduit systems General (a) Conduit systems are securely fixed, box lids in place and are adequately protected against mechanical damage (522.8). (b) Draw points are accessible (522.8.6). (c) The recommended quantity of cables for easy draw is not exceeded during installation, to avoid causing insulation damage. Adequate boxes are suitably spaced. This item should b e inspected during the erection stage, as t h e care and workmanship of the installer can b e verified (522.8.1 and see Appendix E of t h e IET On-Site Guide’). (d) Solid elbows and tees are used only as appropriate (522.8.1). (e) Unused entries are blanked off where necessary (416.2 and 522). (f) Conduit system components comply with a relevant British Standard, depending o n performance requirements (g) Conduit (511.1). systems are provided with drainage holes and gaskets as necessary (522.3.2). (h) The radius of bends is such that cables are n o t damaged (522.8.3). (i) Conduit systems installed in protected escape routes are classed as non-flame propagating according to BS EN 6 1 3 8 6 (422.2.1). Rigid m e t a l c o n d u i t (a) Rigid metal conduit complies with BS EN 61386-21 (521.6). (b) Rigid metal conduit is connected to the MET (411.4.2, 411.5.1). (c) Line, neutral and any additional protective conductors are contained in the same conduit (521.5.1). (d) Conduit is suitable for wet, damp or corrosive situations (522.3, 522.5). (e) Conduit is fixed appropriately (522.8 and see Appendix G of Guidance Note 1). (f) Unpainted ends and scratches, etc. are protected by painting (134.1.1, 522.5). (g) Ends of conduit are reamed and bushed, where relevant (134.1.1, 522.8). Rigid n o n - m e t a l l i c c o n d u i t (a) Rigid non-metallic conduit complies with BS EN 61386 series (521.6). BS 4607, BS EN 60423 o r the (b) Ambient and working temperatures are within permitted limits (522.1, 522.2). (c) Provision is m a d e t o allow for expansion and contraction (522.15.1). (d) Boxes and fixings are suitable for the mass of luminaire suspended at the expected temperature (559.5.2). (e) Conduit is of the 'non-flame propagating' type (521.6). Flexible m e t a l c o n d u i t (a) Flexible metal conduit complies with the BS EN 61386 series (521.6). (b) A separate protective conductor is provided (543.2.3). (c) Fixed metal conduit is adequately supported and terminated (d) Line, neutral conductors and any additional protective (522.8). are contained in the same conduit (521.5.1). Trunking General (a) Trunking complies with B S 4 6 7 8 or BS EN 50085-1 (521.6). (b) Trunking is securely fixed and adequately protected against mechanical damage (522.8). (c) Trunking is selected, erected and routed to avoid ingress of water and solid objects (522.3). Guidance Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology 51 2 (d) Proximity to non-electrical cause damage (528.3). services, i.e. sources of heat, smoke, etc. cannot (e) Internal fire sealing is provided where necessary (requires inspection during the erection stage) (527.2.2). (f) Holes surrounding the trunking are m a d e good (527.2.1). (g) Band I circuits are partitioned voltage present (528.1). (h) Circuits are partitioned f r o m Band II circuits or insulated for the highest f r o m Band I circuits or wired in mineral-insulated metal-sheathed cables (528.1). (i) Cables are supported for vertical runs (522.8.5). ( j ) Trunking systems used in protected escape routes are classed as non-flame propagating according to BS EN 5 0 0 8 5 (422.2.1). Metal trunking (a) Line, neutral and any additional protective conductors are contained in the same trunking (521.5.1). (b) Metal trunking is protected against d a m p or corrosion (522.3, 522.5). (c) Metal trunking is earthed (411.4.2,411.5.1). (d) Joints are mechanically sound and of adequate continuity (543.2.5). Rigid non-metallic trunking (a) Ambient and working temperatures are within permitted limits (522.1, 522.2). (b) Provision is m a d e to allow for expansion and contraction (522.15.1). (c) Trunking is of the non-flame propagating type (521.6). (d) Cables are secured where necessary to prevent premature collapse in the event of afire (521.10.202). Busbartrunking and powertrack systems (a) Busbar trunking system complies with BS EN 60439-2 or BS EN 61439-6 or another appropriate standard; the powertrack system complies with B S E N 61534 series or another appropriate standard (521.4). (b) Systems are securely fixed and adequately protected against mechanical damage (522.8). (c) Joints are mechanically sound and of adequate continuity (543.2.5). Insulated cables Non-flexible cables (a) Non-flexible cables are of the correct t y p e and comply with Construction Products Regulation design requirements (521). the relevant (b) The current rating is correct (523 a n d Appendix 4). (c) Non-flexible cables are protected against mechanical damage and abrasion (522.8). (d) Non-flexible cables are suitable for high or low ambient temperature, as necessary (522.1). (e) Non-sheathed cables are protected by enclosure in conduit, duct or trunking (except for protective conductors of 4 mm 2 and larger) (521.10 a n d 543.1). (f) Sheathed cables concealed in a wall at a depth of less than 5 0 m m f r o m the surface and n o t forming part of a SELVor PELV circuit: (1) are routed in prescribed zones, with additional protection provided by an RCD having a rated residual operating current, l£ n , not exceeding 3 0 m A ; or (si) are provided with mechanical protection complying with (522.6.204). (g) Cables concealed in a partition containing metallic structural parts: (i) are provided with exceeding 3 0 m A ; 52 Guidance Note 3: inspection & Testing © The Institution of Engineering and Technology additional protection by an RCD having a lAn not 2 (ii) are provided with adequate mechanical protection to suit both the installation of t h e cable and its normal use; or (Hi) comply with the requirements set out in Regulation 522.6.203 (522.6.202). (h) Cables exposed to direct sunlight are of a suitable t y p e or are suitably shielded (522.11). (i) Non-flexible cables are not run in lift or hoist shaft unless they are part of the lift installation a n d of the permitted type (528.3.5). ( j ) Cables in protected escape routes should b e of t h e permitted types with regard to fire and smoke performance (422.2.1). (k) Cables buried in the ground are correctly selected and installed for use (522.8.10). (l) Cables installed overhead are correctly selected and installed for such use (522.8.4). (m) The internal radius of every bend in a wiring system should be such that it is not so tight that the cable and/or its conductors suffer damage and such that terminations are not in any way stressed (522.8.3 and Appendix G of Guidance Note 1). (n) Non-flexible cables are correctly supported and secured where necessary to prevent premature collapse in t h e event of a fire (521.10.202, 522.8.4, 522.8.5). (o) Non-flexible cables are n o t exposed to water, etc. unless they are suitable for such exposure (522.3). (p) Metal sheaths and armour are earthed (411.3.1.1). (q) Conductors are identified at terminations (514.3). (r) Joints and connections are electrically and mechanically sound and adequately insulated (526.1, 526.2). (s) All wires are securely contained in terminals, etc. without strain (522.8.5, 526). (t) Terminals are enclosed (526). (u) Glands are correctly selected and fitted with shrouds and supplementary earth tags as necessary (526.1). (v) Joints and connections are mechanically sound and accessible for inspection, testing and maintenance purposes, except as permitted otherwise (526.1, 526.3). Flexible cables (a) Flexible cables are of the correct type and comply with the relevant design requirements of t h e Construction Products Regulation (521.9.1). (b) Current rating is correct (523 and Appendix 4). (c) Cables are protected where exposed t o mechanical damage (522.6, 522.8). (d) Cables are suitably sheathed where exposed to contact with water (522.3) or corrosive substances (522.5). (e) Cables are protected where used for final connections to fixed apparatus, etc. (526.8). (f) Cables are selected for resistance to damage by external heat sources (522.2). (g) There is segregation of Band I and Band II circuits (528; see also BS 6701 and B S E N 50174 series). (h) There is segregation of fire alarm and emergency lighting circuits (528; see also BS 5839, BS 5266). (i) Cores are correctly identified (514.3). (j) Connections have durable electrical continuity, adequate mechanical strength and are made using appropriate means (526.1, 526.2). (k) Where used as fixed wiring, the relevant requirements are m e t and cables are secured where necessary to prevent premature collapse in the event of a fire (521.9.1, 521.10.202). (l) Final connections to current-using equipment are properly secured and arranged to prevent strain o n connections (526.6). (m) Mass is supported by cable so as not to impair safety of the installation (559.5.2). Guidance Note 3: Inspection & Testing © The Institution of Engineering and Technology 53 2 Protective c o n d u c t o r s (a) Cables incorporating protective Harmonized (b) Joints in conductors comply with the relevant British or Standard (511.1). metal conduit, ducting or trunking comply with Regulations for preservation of continuity (543.3). (c) Flexible or pliable conductive conduit is supplemented by a protective conductor except where only SELV systems are enclosed by the conduit (543.2.3). (d) Protective conductors have a suitable m i n i m u m csa (543.1). (e) Protective conductors with a csa of 6 mm 2 o r less are protected by insulation or equivalent, unless they are part of a multicore cable, o r f o r m part of a conductive containment system or enclosure used as a protective conductor (543.3.201). (f) A cpc at the termination of sheathed cables is protected by sleeving (543.3.201). (g) A bare cpc is protected against mechanical damage a n d corrosion (543.3.1). (h) Insulation, sleeving and terminations are identified by t h e bi-colour combination green-and-yellow (514.4.2). (i) Joints are electrically and mechanically sound (526.1). ( j ) Separate cpcs of not less than 4 m m 2 if not protected against mechanical damage and is not an integral part of a cable, n o t formed by conduit, ducting or trunking, nor contained in an enclosure formed by a wiring system (543.1.1). (k) Main and supplementary protective bonding conductors are of the correct size (544). (l) Cables are secured where necessary to prevent premature collapse in the event of a fire (521.10.202) Enclosures General (a) There is a suitable degree of protection (IP Code in BS EN 6 0 5 2 9 ) appropriate to external influences w h e n installed, taking account of the manufacturer's instructions (416.2, 512.2, 522, Part 7). 2.6 Tests associated with initial verification The test methods described in this section are recommended to b e used as part of initial and periodic verification. This does n o t rule out the use of other test methods, provided they give valid results. Note: In medical locations of group 1 and 2, the measurement and recording of supplementary bonding conductor resistance values is required. Where medical IT systems are installed, measurement of capacitive leakage currents are required. Further information is available in IET Guidance Note 7 Special Locations. 2.6.1 Test results The test results must b e recorded o n the Schedule(s) of Test Results and compared with relevant criteria. For example, in order to verify disconnection times, the relevant criteria would b e design EFLIvalues provided by t h e designer. A model Schedule of Test Results is shown in Section 5. 54 Guidance Note 3: Inspection & Testing © The Institution of Engineering and Technology 2 2.6.2 Electrical Installation Certificate (EIC) Regulation 644.1 of BS 7 6 7 1 requires that u p o n completion of the verification of a new, modified or extended installation, an EIC based on the model given in Appendix 6 of BS7671 is provided to the person that ordered the work. Chapter 6 4 requires that: 644.3 (a) the EIC is accompanied 644.3 644.,: (b) the Schedule of Test Results shall include test results for the work done; by a Schedule of Inspections, Circuit Details and Test Results. These schedules shall b e based o n the models given in Appendix 6 of BS 7671; (c) the EIC is signed or otherwise authenticated each facet of design, construction by a skilled person responsible for and inspection and test and competent to verify that the requirements of B S 7 6 7 1 have been met; and 644.1. (d) any defects or omissions revealed by the inspector are required to b e made good by the installer, and, as necessary, inspected EIC is issued; it is not the responsibility and tested again, before the of the person or organization carrying out t h e inspection and testing to make good defects or omissions. Where the installation work does not extend to the installation of a n e w circuit, a MEIWC may b e used instead of the full EIC. This simplifies the documentation for small works; in addition, the required installation inspection and testing and tests are limited to the circuit being extended or modified, as detailed in Part 4 of the certificate. See Section 5 for further details and guidance o n the completion of this certificate. NOTE: The model the model forms in Appendix6 of BS7671 can be amended to suit the installation, provided that the minimum information required is included. 2.6.3 Model forms Typical forms for use when carrying out inspection and testing are included in Section 5 of this Guidance Note. 643.1 2.6.4 T h e sequence of tests Tests associated with initial verification should b e carried out in the following sequence, where relevant and practical: (a) continuity of protective conductors, including main a n d supplementary bonding (see Section 2.6.5) (Regulation 643.2.1); (b) continuity of ring final circuit conductors (see Section 2.6.6) (Regulation 643.2.1); (c) insulation resistance (see Section 2.6.7) (Regulation 643.3); (d) protection by SELV.PELVor by electrical separation (see Sections 2.6.8 and 2.6.9) (Regulations 643.4, 643.4.1, 643.4.2); (e) insulation resistance of non-conducting floors and walls (see Section 2.6.11) (Regulation 643.5); (f) polarity (Section 2.6.12) (Regulation 643.6); (g) protection by ADS (Section 2.6.15) (Regulations 643.7, 643.7.1,643.7.2, 643.7.3); (h) earth electrode resistance (Section 2.6.13) (Regulation 643.7.2); (i) EFLI (Section 2.6.15) (Regulation 643.7.3); ( j ) prospective fault current (Section 2.6.16) (Regulation 643.7.3.201); (k) additional protection (Section 2.6.18) (Regulation 643.8); (l) check of phase sequence (Section 2.6.17) (Regulation 643.9); (m) functional testing (Sections 2.6.18 a n d 2.6.19) (Regulation 643.10); a n d (n) verification of voltage drop (Section 2.6.20) (Regulation 643.11). Guidance N o t e 3: Inspection & Testing © The Institution o f Engineering and Technology 55 2 ▼ Figure 2.12 Sequence of tests for initial verification Regulation Group Test description Section in this Guidance Note 643.2 Continuity of protective conductors, including main earthing conductor, and main and supplementary protective bonding conductors 2.6.5 643.2 Continuity of ring final circuit conductors 2.6.6 643.3 Insulation resistance 2.6.7 643.4 Protection by SELV, PELV or electrical separation 2.6.8 2.8.9 643.5 Insulation resistance of non-conducting floors and walls (rarely required) 2.6.11 643.6 Polarity 2.6.12 2.6.14 643.7 Protection by automatic disconnection of supply. Test as relevant: • Earth electrode resistance' • Earth fault loop impedance • Operation of RCDs 2.6.13 2.6.15 2.6.18 Prospective fault current 2.6.16 Additional protection. A test is required to verify the operation of RCDs used for additional protection 643.9 Check of phase sequence 2.6.17 643.10 Functional testing 2.6.18 2.6.19 643. 1 1 Verification of voltage drop 2.6.20 Safety considerations 0® Regulation 643.1 requires the tests in Regulations 643.2 to 643.6 inclusive tests to be conducted (where relevant for the particular installation) in the order shown, prior to the installation being energized. It is strongly recommended to address any unsatisfactory conditions discovered during a test, before proceeding with any subsequent tests. * Where present, Regulation 643.1 requires earth electrode resistance to be measured prior to energization. These tests may involve parts of the installation being energized, depending on the test method adopted. 643.2 2.6.5 Continuity of protective conductors, including main and supplementary bonding Regulation 411.3.1.1 requires installations that provide protection against electric shock using ADS to have a cpc run to and terminated at each point in t h e wiring and at each accessory. An exception to this is m a d e for a lampholder having n o exposedconductive-parts and suspended f r o m such a point. Regulation 643.2.1 requires that a continuity check b e carried out o n all protective conductors. This includes the earthing conductor, the protective conductors of all circuits, all main protective bonding conductors and, where applicable, all supplementary bonding conductors. Regulation 643.2.1 also requires that a continuity check b e carried out o n each conductor of every ring final circuit, including the line, neutral and protective conductors. There are two widely used test methods that have evolved for checking protective conductor continuity. method Test method 1 uses the circuit cable shorted o u t and test 2 uses a supplementary length of test cable (this method being popularly known as t h e 'wandering lead' method). 56 G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology 2 Instrument: use a low-resistance ohmmeter The relevant conductors, mentioned for these tests (see Section 4.3). above, should b e tested to verify that they are electrically sound and correctly connected. Test method 1, detailed in this item, as well as checking the continuity of the protective conductor, measures (R 1 + R2) which, when added to the external impedance (Z e), enables the EFLI(Z S) to b e checked against the design (see Sections 2.6.14 and 2.6.15). (R 1 + R2) is the sum of the resistances of the line conductor, Ri, and the cpc, R2 . Test readings may b e affected by parallel paths through exposed-conductive-parts and/or extraneous-conductive-parts. Parallel earth paths and effects on test readings Inspectors should always b e aware of t h e possible existence of parallel earth return paths. These may take t h e f o r m of metallic cable management products, extraneousconductive-parts or, indeed, other metallic parts. Examples include installations incorporating steel conduit, steel trunking, mineral-insulated copper-clad cable (MICC), steel wire armoured (SWA) or other metal-sheathed cables, equipment and accessory boxes fitted to metal stud walls or to the building fabric, and luminaires fitted in grid ceilings. Such parallel paths exist in domestic, commercial and industrial installations. The effect of parallel earth return paths is that the measured value of protective conductor continuity, R2) tends towards zero. It is often impractical and, in some cases, impossible to carry out testing with some or all of the parallel paths disconnected and the inspector must b e aware of this. Test m e t h o d 1 (for circuits) Make a temporary shorting link of cable and connect the line conductor to the protective conductor at the distribution board or consumer unit. Then test between line and earth terminals at each outlet i n the circuit, as shown in Figure 2.13. The resistance of the test leads should either b e measured and deducted f r o m t h e readings obtained, or auto-nulled by the test instrument, which most m o d e r n instruments are able to do. Where the installation has all-insulated wiring (see notes o n parallel earth paths and effects o n test results above) and the cable accessories are not in contact with earth, then this test measures(Ri + R2), i.e. the resistance of the line conductor, R i plus the resistance of t h e protective conductor, R2 , for that circuit which, if added to the EFLI at the distribution board, can b e taken as t h e circuit's EFLI.lt is important to record t h e value of (R 1 + R2) obtained at the circuit's extremity, namely the furthest circuit distance f r o m t h e distribution board. Guidance N o t e 3 : Inspection & Testing © The Institution of Engineering and Technology 57 2 ▼ Figure 2.13 Connections for testing continuity of protective conductors: test method 1 OoUT* Temporary link ■; © ir *®1 ; voiw Phw Main switch off, secured by safety locking device. All fuses removed, circuit breakers off. Zero instrument across test link. Note: remember to remove temporary link after test. Many electronic or electromagnetic control devices present an open-circuit when the l o w voltage AC power is removed. Examples may include, but are n o t limited to, the following types of product: (a) contactors; (b) motion and day/night controls; (c) energy control timers; (d) lighting dimmers; (e) remote or smart technology switches; and (f) building management system controllers. Figure 2.14 shows a n alternative approach to test method 1 , that can b e used to test protective conductors downstream of a control device which is open-circuit when low voltage AC power is removed. This test approach simply measures (R n + R2) instead o f ( R 1 + R2). ▼ Figure 2.14 Alternative approach for testing continuity of protective conductors: test method 1, for circuit conductors downstream of electronic control devices Electronic control device, for example a dimmer Temporary link •© ■© >© AUTO| VO»W PhiM Main switch off, secured by safety locking device. All fuses removed, circuit breakers off. Zero instrument across test link. Note: remember to remove temporary link after test. 58 G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology 2 Expected results for test method 1 The results should f i r s t a n d f o r e m o s t indicate conductors. For insulated a n d similar a r e not m a y b e earthed, n o discontinuity wiring systems i n s t a l l e d i n conditions c o n n e c t e d to the f a b r i c of the t h e n a s s t a t e d earlier, the readings building i n the where protective a c c e s s o r y boxes or other elements m e a s u r e d will b e the that sum of t h e l i n e a n d p r o t e c t i v e c o n d u c t o r resistances ( R 1 + R2) . T h i s t e s t c a n d e t e c t p o o r c o n t i n u i t y a t j u n c t i o n s a n d c o n n e c t i o n s as, f o r a n e w i n s t a l l a t i o n w i t h n e w accessories, t h e contribution of resistance of healthy c o n n e c t i o n s to t h e m e a s u r e d resistance is negligible a n d c a n be ignored. conductors given Thus, by employing in A p p e n d i x B of this Guidance circuits c a n b e approximated, t h e resistance Note, expected data f o r copper v a l u e s for healthy a n d c o m p a r e d with the test readings obtained. a b o u t 5 5 m w i t h 2.5 mm 2 l i n e a n d 1 . 5 m m 2 As a n e x a m p l e , a radial c i r c u i t of length p r o t e c t i v e c o n d u c t o r s s h o u l d h a v e a n ( R 1 + R2) r e s i s t a n c e as f o l l o w s : Length o f circuit is 5 5 m Resistance p e r metre of the line a n d protective c a b l e is 19.51 mQ/m (at 20 °C) f r o m Table B l T h e o r e t i c a l minimum DC r e s i s t a n c e = (55 conductors x 19.51 )/l, 000 i n a 2.5 mm 2 /1.5 mm2 = 1.07 Q W h e n v e r i f y i n g a circuit, t h e i n s p e c t o r s h o u l d t a k e i n t o a c c o u n t t h a t a h i g h e r v a l u e m i g h t b e m e a s u r e d , as t h e r e will b e s o m e resistance at t h e terminations, a n d t h e r e m a y b e a c o n t a c t r e s i s t a n c e f o r c o n n e c t i o n of p r o b e s a n d clips, t h a t c a n i n c r e a s e with c o r r o s i o n on o l d e r terminals. might a l s o contribute Switches, to a higher fuses, a n d other t y p e s of protective device, reading. Test method 2 (for circuits) Instrument: u s e a l o w - r e s i s t a n c e o h m m e t e r f o r t h i s t e s t (see S e c t i o n 4.3). O n e l e a d of t h e t e s t i n s t r u m e n t is c o n n e c t e d t o t h e e a r t h t e r m i n a l a t t h e d i s t r i b u t i o n b o a r d v i a a length of test c a b l e or ' w a n d e r i n g lead'. make contact with the protective f o r example, a t luminaires, 2.15. T h e resistance conductor switches, of the wandering d e d u c t e d f r o m t h e r e a d i n g s obtained, The other test lead at various p o i n t s o n the circuit f u s e d connection is used under units, etc. a s shown l e a d a n d t h e test l e a d s a r e either to test, in Figure measured a n d or a u t o - n u l l e d by the test instrument, which m o s t m o d e r n i n s t r u m e n t s a r e a b l e t o do. This test m e a s u r e s the resistance of the cpc, R 2 , w h i c h should b e recorded o n the Schedule of Test Results (see notes on parallel earth paths and effects o n test readings above). G u i d a n c e Note 3: I n s p e c t i o n & Testing © The Institution of Engineering and Technology 59 2 ▼ Figure 2 . 1 5 Connections for testing continuity of protective conductors: test m e t h o d 2 wander-lead Main switch off, secured by safety locking device. All fuses removed, circuit breakers off. Zero instrument through wander-lead. Expected results for test method 2 The results should f i r s t a n d f o r e m o s t indicate c o n d u c t o r s . For insulated w i r i n g systems n o discontinuity in the protective i n s t a l l e d in c o n d i t i o n s w h e r e a c c e s s o r y boxes a n d s i m i l a r a r e not c o n n e c t e d t o t h e f a b r i c o f t h e b u i l d i n g o r o t h e r e l e m e n t s t h a t m a y b e e a r t h e d , the measurement w i l l equate to the protective conductor resistance, R 2 . T h i s test c a n d e t e c t p o o r c o n t i n u i t y at j u n c t i o n s a n d c o n n e c t i o n s as, f o r a n e w installation w i t h n e w accessories, t h e c o n t r i b u t i o n o f r e s i s t a n c e o f h e a l t h y c o n n e c t i o n s i s negligible a n d c a n b e ignored. c o n d u c t o r s given Thus, by employing the resistance in A p p e n d i x B of this G u i d a n c e Note, data f o r c o p p e r e x p e c t e d values for healthy cable a n d connections c a n b e checked. As a n e x a m p l e , a radial circuit of length a b o u t 5 5 m with a 2 . 5 mm 2 c o p p e r p r o t e c t i v e c o n d u c t o r s h o u l d h a v e a n R2 r e s i s t a n c e a s f o l l o w s : Length of c i r c u i t i s 5 5 m Resistance of a 2.5 mm 2 conductor is 7.41 m Q / m (at 20 °C) f r o m Table B l T h e o r e t i c a l m i n i m u m D C r e s i s t a n c e = (55 x 7.41)71,000 W h e n v e r i f y i n g this circuit, the inspector i n t h e o r d e r of, say, 0.4 Q to 0.5 Q . If t h e circuit protective conductor s h o u l d b e looking is broken and connected = 0.41 Q f o r a reading h a s several outlets, somewhere m e a n i n g that the i n screw terminals a t each accessory, then a slightly higher value may be measured, a s there will be some resistance at the terminations. Testing bonding conductors and earthing conductors To c o n f i r m the continuity of t h e s e protective conductors, test method 2 is u s e d . In m e d i c a l l o c a t i o n s o f G r o u p 1 a n d 2 it is n e c e s s a r y t o m e a s u r e a n d r e c o r d the v a l u e s of t h e s u p p l e m e n t a r y b o n d i n g c o n d u c t o r s . A c c o u n t s h o u l d b e t a k e n of t h e p o s s i b i l i t y of test readings being a f f e c t e d by parallel paths, as m e n t i o n e d earlier in this section. For t h i s r e a s o n , it m a y b e n e c e s s a r y t o carry o u t t h e test w i t h the p r o t e c t i v e c o n d u c t o r d i s c o n n e c t e d a t o n e end, w h e r e p r a c t i c a b l e . 60 G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology 2 This method can also be used to confirm a bonding connection between extraneousconductive-parts where it is not possible to see a bonding connection, for example, where bonding d a m p s have been ’built in'. The test would b e d o n e by connecting the leads of the test instrument between any t w o points, such as metallic pipes, and looking for a suitably l o w reading taking into account the length of the protective bonding conductor(s). Keep in mind, however, that 15 m of single-core 6.0 m m 2 or 2 2 5 m of single-core 10.0 m m conductor has a resistance of approximately 0.05 Q . With such low resistances being measured, t h e resolution of the test instrument may not permit an accurate reading to b e obtained (see Section 4.3) and therefore where t h e expected resistance is less than 0.1 Q including contact resistances, a value n o t exceeding 0.1 Q should b e used as a guideline acceptable reading. It should b e noted that this is not the R2 resistance measured f r o m the MET to the bonding clamp or adjacent pipework. To verify that there is a low resistance connection to the actual extraneous-conductivepart itself, t h e measured resistance to the terminal of a bonding clamp can be compared with t h e measured resistance to the extraneous-conductive-part itself some distance f r o m the clamp. An example of this method is shown in Figure 2.16. Where metallic enclosures have b e e n used as t h e protective conductors, for example, conduit, trunking, SWA, etc., the following procedure should b e employed: (a) inspect t h e enclosure along its length for soundness of construction; and (b) perform the standard continuity test using the appropriate test m e t h o d described above. Instrument’, use a low-resistance ohmmeter for this test (see Section 4.3). ▼ Figure 2 . 1 6 Example o f testing t h e effectiveness of a b o n d i n g clamp Main switch off, secured by safety locking device. All fuses removed, circuit breakers off. Zero instrument through wander-lead. ©■©©©©©© ©©©©© _N® N®] n@|' N®r n@; First, test at the main protective bonding conductor termination <@ '© <© p© I’© ' © ; ' © ’ © ’ © wander-lead Then, test at exposed-conductive-part approximately 0.5 m to 1 m from the bonding clamp. The measurements should be roughly the same if there is a good connection between clamp and extraneousconductive-part. □.□So Guidance Note 3: Inspection & Testing © The Institution of Engineeringand Technology 61 2 Expected test results The results should first and foremost indicate no discontinuity in the protective conductors. For lengths of conductor, use Appendix B of this Guidance Note for resistance data. For joints across bonds by earth clamps and similar, the readings should approach 0.05 Q , taking into account t h e resolution of the instrument, its accuracy at low values and contact resistance. 2.6.6 Continuity of ring final circuit conductors A three-step test is required to verify t h e continuity of t h e line, neutral and protective conductors a n d the correct wiring of every ring final circuit. The test results show if t h e ring has b e e n interconnected to create an apparently continuous ring circuit, which is i n fact broken or connected as a ’figure of eight' configuration. Instrument', use a low-resistance ohmmeter for this test (see Section 4.3). Step 1 The line, neutral and protective conductors are visually identified at the distribution board or consumer unit and t h e end-to-end resistance of each is measured separately (see Figure 2.17). ▼ Figure 2.17 Connections for ring final circuit continuity testing: step 1 b. measure rn a. measure r-i c. measure r2 |e These resistances are referred t o as n, rn and r 2, respectively. A reading that indicates a n o p e n circuit, or resistance higher than the continuity measurement range, shows there is likely to b e a damaged conductor, or an issue with the integrity of connections or terminations, along t h e ring conductors under test. The resistance values obtained should b e of t h e same order if the conductors are of the same length, csa and material. If t h e protective conductor has a reduced csa, the resistance r 2 of the protective conductor loop will b e proportionally higher than that of the line or neutral loop. Because the resistance of a cable is inversely proportional to t h e area, w e can calculate h o w m u c h w e have t o multiply t h e measured value of r i by to obtain the expected value of r2 using the following formula: i r __ csa cpc 2- — ~ csa 62 G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology line x _ csa line x r 2 csacpc 2 For example, for 2.5 m m 2 /1.5 m m 2 cable: r 2=T3 x r 2= 1 -6 7 x r 2 If the resistance readings are not as expected, this could mean the following: (a) readings lower than the expected resistance would suggest that the ring is incorrectly configured, possibly wired in a 'figure of eight’ connection; this may be further confirmed by the step 2 test below; or (b) readings higher t h a n the expected resistance would suggest an issue with the integrity of one or more conductor terminations. The 'expected resistance' is that found from the tabulated DC resistance for the conductor csa per metre, multiplied by the installed length and corrected for ambient temperature. A small allowance should be made for instrument errors. Table B i gives values of DC resistance for conductors. Step 2 The open ends of the line and neutral conductors are then connected together so that the outgoing line conductor is connected to the returning neutral conductor, and vice versa (see Figure 2.18). ▼ Figure 2.18 Connections for ring final circuit continuity testing: step 2 neutral fl I connector blocks The resistance between line and neutral conductors is measured at each socket-outlet. The readings at each of the socket-outlets connected to the ring should be substantially the same and the value will be approximately one-quarter of the resistance of the line plus the neutral loop resistances, i.e. (ri + rn)/4 (see mathematical explanation in Figure 2.19). Any socket-outlets wired as spurs will indicate a higher resistance value, due to the resistance of the spur conductors. Note: Where single-core cables are used, care should be taken to verify that the line and neutral conductors of opposite ends of the ring circuit are connected together. An error in this respect will b e apparent from the readings taken at the socket-outlets, progressively increasing in value as readings are taken towards the midpoint of the ring, then decreasing again towards the other end of the ring. Where such behaviour in readings is between particular points part way round the ring, this may indicate an interconnection within the ring. Guidance Note 3: Inspection & Testing © The Institution of Engineeringand Technology 63 ▼ Figure 2.19 Mathematical explanation for step 2 (live conductors having the same csa) Figures 2.19a to e explain t h e expected results for a correctly wired ring circuit. a Origin Testpoint Afor mathmatical explanation Open loop resistance = 0.6 O Figure a above is an example of a correctly wired ring, with the open loop resistances of t h e line and neutral conductors f r o m step 1 , each being 0.6 O . A test point about a third distance round t h e ring is used to illustrate t h e maths, as explained below. b Origin 0.2 0 t Test point A 0.4Q Figures b and c show the resistances of each leg of the ring as a test is applied at this point as per step 2 (line-neutral). c Test Ni 0.2(1 E° i n t A T? 0 2(1 / N z 0.4(1 L 2 0.4(1 □.3Qq G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology 2 The equivalent connects are then represented in Figure d. 0.2 fl F Test point A cross-connections at consumer unit n2 0.4 fl F The equivalent circuit diagram and resultant resistance are shown in Figure e . 0.2 0 0.4 0 0.6 0 0.4 0 0.2 0 0.6 0 In summary, the open loop resistances are 0.6 0 for both line and neutral, giving an C i + rn) value of (0.6 + 0.6), or 1 . 2 0 . From Figure e above, it can b e seen that a correctly connected ring will give a step 2 reading of a quarter of the (rj + rn) value, or: Rste P 2 tes t = £ 4 £ . i n t h i s case = 0 . 3 fl Step 3 The open ends of the line conductor and cpc are then cross-connected (see Figure 2.20). ▼ Figure 2.20 Connections for ring final circuit continuity testing: step 3 connector blocks The resistance between line and cpc is measured at each socket-outlet. obtained at each of the socket-outlets The readings wired in the form of a ring will depend o n whether the cpc is the same csa and material as t h e line conductors: Guidance Note 3: Inspection & Testing © The Institution of Engineering and Technology 65 2 (a) Where the cpc is the same copper-equivalent csa as the line conductors, the readings will b e substantially the same and t h e value will b e approximately one-quarter of the resistance of the line plus cpc loop resistances, i.e. (r] + rn)/4 (the explanation for this being similar to that for step 2). (b) Where the cpc has a different csa f r o m the line conductors, for example where flat twin-and-earth cable is used, the resistance will increase as t h e tests move around t h e ring f r o m t h e origin of t h e circuit, to a maximum of approximately C i + r 2 )/4 at the mid-point of the ring, and decrease as the test point moves back towards the origin of the circuit. The maximum a n d minimum values expected during the test are shown in Table 2.8 (see IET Electrical Installation Design Guide for a comprehensive mathematical explanation). A higher resistance value will b e recorded at any socket-outlets or other accessories wired as spurs. The highest value recorded represents the maximum (R] + R£) of the circuit and is recorded o n the Schedule of Test Results. The value can b e used to determine the EFLI (Z s) of the circuit to verify t h e provisions for automatic disconnection of supply (see Section 2.6.14). 411.3.2.5 4193 The inspector is again reminded to take note of t h e effects of possible parallel return paths o n these continuity tests, as described in Section 2.6.5 o f this Guidance Note. In addition, where supplementary protective equipotential bonding is used in accordance with Regulations 411.3.2.4 and 419.3, this may also affect the readings for step 3. Examples of circuits which may b e affected in this way include distribution circuits and final circuits supplying central heating systems, electric showers, or water heaters. ▼ T a b l e 2.8 Variation in reading during tests around t h e ring in Step 3 where line and cpc have different csa a General case Lowest reading (notes 3 and 4) csa of line conductor and cpc 2.5 m m 2 live conductors, 1.5 m m 2 cpc (note 1 ) 4.0 mm 2 live conductors, 1.5 mm 2 cpc (note 1) 2.5 m m 2 live conductors, 1.0 mm 2 cpc (note 2) G u i d a n c e Note Percentage difference between lowest and highest reading 6 7 o o f highest reading O.S4X 20 7 o o f highest reading 0.80 x'(r i + r 4 0.82 x Other combinations 66 Highest reading (notes 4, 5 and 6) 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology ri+r z 18 7 o o f highest reading - (£1Z£2 I 2 Ri+rJ x 100 % of highest reading 2 b By length of 3 0 A or 3 2 A ring final circuits u p to the maximum lengths shown i n Table7.1(i) of the lETOn-Site Guide, with automatic disconnection provided by RCD 4.0 mm 2 live conductor, 1.5 mm 2 cpc 2.5 mm 2 live conductors, 1.5 mm 2 cpc Total ring length (m) Minimum reading (Notes 3, 4 and 6) Maximum reading (Notes 4, 5 and 6) Minimum reading (Notes 1, 4 and 6) Maximum reading (Notes 4, 5 and 6) 10 0.05 0.05 0.03 0.04 20 0.09 0.10 0.07 0.08 30 0.14 0.15 0.10 0.13 40 0.18 0.20 0.13 0.17 50 0.23 0.24 0.17 0.21 60 0.28 0.29 0.20 0.25 70 0.32 0.34 0.23 0.29 80 0.37 0.39 0.27 0.33 90 0.41 0.44 0.30 0.38 100 0.46 0.49 0.33 0.42 106 0.49 0.52 0.35 0.44 110 0.37 0.46 120 0.40 0.50 130 0.43 0.54 0.47 0.58 150 0.50 0.63 160 0.53 0.67 170 0.57 0.71 171 0.57 0.71 140 Not oossiblo fnoto 81 Notes: 1 2 3 4 5 6 7 8 UK cable type 6242Y to BS 6 0 0 4 or type 6242B to BS 721 1 :2012+AI:2020. Flat twin and earth cables manufactured between approximately 1969 and 1981. The lowest reading should occur at the origin of the circuit. Ignoring measurement error. The highest reading should occur at the midpoint of the ring, although there may not b e a socket-outlet or other accessory installed at that point, at which a measurement can b e made. Ignoring spurs from the ring. See IET Electrical Installation Design Cuide for an explanation of the data provided in this table. Exceeds maximum length of circuit due to excessive voltage drop. 643.3 2.6.7 Insulation resistance Insulation resistance testing is a fundamental construction test for inspectors. Often, o n larger sites, cables will b e insulation resistance tested during various stages of installation, to prove the integrity of installed cables. It is always preferred to re-test cables and equipment for insulation resistance as part of initial verification, as well as during construction. BS 7671:2018+A2:2022 circuits following connection of equipment permits t h e test voltage applied t o to b e reduced to 2 5 0 V DC, provided that cables were tested at 5 0 0 V DC prior to connection. G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology 67 2 643.3 BS 7 6 7 1 requires that insulation resistance is measured between all of the live conductors and between the live conductors and the protective conductor, with the protective conductor connected t o t h e earthing arrangement. During t h e test between live conductors and the protective conductor, the live conductors may b e connected together. Taking cables as an example, historically, it was acceptable to test a cable between the various cores, and test to earth (which was actually only the cpc, such as a single-core conductor, o r the armouring or sheath of the cable); sometimes, these cables were terminated without further testing. This is n o longer acceptable: it is n o w essential to test to t h e protective conductor (such as armouring) with this connected - via a fly-lead if necessary - to the installation earthing arrangement. This is shown in Figure 2.23. It is a good idea to test all cables, including those tested during the construction stage, using this method. The purpose of the insulation resistance test is t o verify that the insulation of conductors is not damaged and that live conductors or protective conductors are not short-circuited. As a reminder, prior to carrying out t h e test, t h e inspector should check that: (a) t h e protective conductor of t h e i t e m (switchgear or cable, etc.) is connected to t h e MET, which must b e connected to the means of earthing. (b) pilot or indicator lamps, and capacitors, are disconnected f r o m circuits, to avoid an inaccurate test value being obtained (see Note below). (c) voltage-sensitive electronic equipment, such as dimmer switches, touch switches, delay timers, power controllers, electronic starters for fluorescent lamps, emergency lighting, RCDs and similar equipment is disconnected, so that it is not subjected to the test voltage. The functional earthing leads of residual current circuit-breakers (with overcurrent protection) (RCBOs) should also be disconnected, to prevent a low insulation resistance reading or damage to an RCBO. (d) the incoming neutral has been disconnected/isolated, where necessary, so that there is n o connection to Earth. Notes: 1 Great care should b e taken w h e n removing neutral conductors or neutral links o n installations: the m o m e n t the neutral is removed, it may become live, if there is a 'borrowed neutral' o n t h e installation. Insulated tools should b e used for this task. 2 (b) and (c) are necessary because, as testing occurs between all conductors, anything connected and in circuit will b e subjected to t h e test voltage. Instrument: use an insulation resistance tester (see Section 4.4). Table 64 Insulation resistance tests should be carried out using the appropriate DC test voltage specified in Table 6 4 of BS 7671. The installation will b e d e e m e d to conform with t h e Regulations in this respect if the main switchboard and each distribution circuit tested separately, with all its final circuits connected b u t with current-using equipment disconnected, has an insulation resistance not less than that specified in Table 64, reproduced here as Table 2.9. 68 G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology 2 ▼ T a b l e 2 . 9 M i n i m u m values of insulation resistance Test voltage DC (V) Minimum insulation resistance (MQ) SELVand PELV 250 0.5 Up to a n d including 500 V,with t h e exception of SELVand PELV, but including FELV 500 1.0 Above 5 0 0 V 1000 1.0 Circuit nominal voltage Simple installations that contain no distribution circuits should preferably b e tested as a whole (see example in Figure 2.21). The tests should b e carried out with the main switch off, all fuses in place, switches and circuit-breakers closed (i.e., in their O N positions), lamps removed, and fluorescent and other discharge luminaires and other equipment disconnected. Where the removal of lamps and/or the disconnection of current-using equipment is impracticable, the local switches controlling such lamps and/or equipment should b e open. An insulation resistance test of line and neutral (L&N) connected together to Earth (E) will ensure that all t h e circuit conductors are tested. Where there are special lighting controls, such as contactor switching, all the circuit wiring, including such switch-lines, must b e included in the testing. Complex installations, or other installations where the overall installation presents a l o w value, may n e e d to b e subdivided into their component resistance tests. parts to perform insulation Although an insulation resistance value as low as 1 M Q would comply with the requirements of the Regulations, a new installation should not yield a test result this low. In n e w installations, a value below 20 M Q should b e investigated. Example (i): insulation resistance test of a whole consumer unit ▼ Figure 2.21 Example of a n insulation resistance test of a whole consumer unit □ Test w i t h 2-way switches in all combinations. Main switch off, secured by safety locking device. All fuses inserted, circuit breakers on. Loadsdisconnected. General lighting service (GLS)lamps removed. Switches "on". >5 5 Emo Means o f earthing and main bonding connected. Guidance N o t e 3: Inspection & Testing © The Institution of Engineering and Technology 69 2 Figure 2.21 shows an example of testing a whole consumer unit (i.e., an installation) in one test (only the L-N test is shown). The tests required are a test between the live conductors (L-N) and tests between t h e live conductors and earth (L-Eand N-E). For circuits containing two-way switches or two-way and intermediate switches, the switches must b e operated one at a time and the circuits subjected to additional insulation resistance test in these configurations. For circuits and/or equipment that is vulnerable t o the test voltage, the line and neutral conductors can b e linked/connected together and a test made between t h e linked conductors and protective Earth (as in L&N-E). It is essential that the incoming earth connection is connected to the MET of the installation (and that this is connected to t h e means of earthing) for these tests. Example (ii): insulation resistance test of a final circuit Figure 2.22 shows a n example of testing a single final circuit at a consumer unit (only the L-N test is shown). The tests required are a test between the live conductors (L-N) and tests between t h e live conductors and earth (L-Eand N-E). For circuits containing two-way switches o r two-way and intermediate switches, t h e switches must be operated one at a t i m e and the circuits subjected to additional insulation resistance test in these configurations. For circuits and/or equipment vulnerable to the test voltage, the line and neutral conductors can b e linked/connected together and a test made between t h e linked conductors and protective Earth (as in L&N - E). It is essential that t h e incoming earth connection is connected to the MET of the installation (and that this is connected to the means of earthing) for these tests. ▼ Figure 2 . 2 2 Example of insulation resistance test of a final circuit ?© =© -© Test w i t h 2-way and intermediate switches i n all combinations. SHI, L M a i n switch off, secured by safety locking device. All fuses inserted, circuit breakers on. Loads disconnected. General lighting service (GLS) lamps removed. Switches "on". >EIEIEImq |0 Means of earthing and main bonding connected. Notes: 1 T h e test should b e initially carried o u t o n t h e complete installation, b u t could b e carried out on completion of wiring at 500 V DC, before the installation of accessories, then retested at 2 5 0 V DC on completion to verify cables have not been damaged during the work. 2 Bonding a n d earthing connections are i n place. 70 G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology 2 Circuits with equipment that might influence the result of, or be damaged during, an insulation resistance test 643.3.3 Some electronic equipment may be susceptible to damage by insulation resistance tests, for example where electronic components that are not intended to withstand voltages of 5 0 0 V DC. Other equipment may influence equipment may have: (a) electronic the measurement being made. components o r transformers connected between For example, line and neutral, which present a relatively low resistance; (b) electronic control devices that use multipole relays or contactors disconnecting all live conductors (including neutral), which return to the o p e n state w h e n power is removed, such as when the circuit is made dead prior to test; and/or (c) certain protective surge protection devices, such as RCCBs, RCBOs and AFDDs, as well as devices and similar electronic components that present a low resistance during an insulation resistance test. Regulation 643.3.3 of BS7671 requires that circuits with this type of equipment have an insulation resistance test in two stages: (i) When the circuit cables are first installed, an insulation carried out between protective conductor, line conductors, with and between t h e protective resistance test is line conductors a n d the conductor connected to the earthing arrangement. Individual sections of a circuit may b e joined via temporary connectors in place of vulnerable equipment, to test multiple cable segments together in this way. (ii) Following connection of equipment that might b e damaged by, o r influence, the test, a test at 2 5 0 V D C is to b e applied between live conductors and t h e protective conductor connected to t h e earthina arrangement. insulation resistance shall have a value of at least 1 M Q . The Example of the test prior to connection for insulation resistance of a three-phase 4-core power cable The cable is tested as per Table 2.10. ▼ T a b l e 2 . 1 0 Insulation resistance test o n 4-core p o w e r cable Test 1 L I to L2 Test 2 L I to L3 Test 3 L2 to L3 Test 4 L I + L 2 + L3 (connected together) to N Test5 LI+L2+L3+N (connected together) to E The lowest value of these tests is recorded as 'between live conductors' The lowest value of these tests is recorded as 'between live conductors a n d earth1 Notes: 1 It is essential for test 5 that t h e protective conductor of t h e cable is connected to t h e installation's earthing arrangement. 2 Tests 4 a n d 5 can b e done individually, for test 4, each of LI, L 2 and L3 first to N a n d for test 4, each o f L I , L2, L3 a n d N to E. Guidance N o t e 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology 71 2 For experienced inspectors and testers, Table 2.11 shows h o w it is possible to reduce t h e number of steps for insulation resistance to four. However, should any test yield a reading lower than that referred to in Table 2.9, it will b e necessary to follow the sequence stated in Table 2.10 to identify which conductors are affected. ▼ Table 2.11 Four-step insulation resistance test o n 4-core p o w e r cable Test 1 L I to L2 L I to L2 Test 2 LI+L2toL3 L I and L2 linked together to L3 Test 3 L I + L2 + L 3 t o N All line conductors linked together to neutral Test 4 L I + L2 + L3 + N to E All live conductors linked together to Earth ▼ Figure 2.23 Insulation testing of a 4-core p o w e r cable prior to termination (showing the neutral to earth test) SWA cable Connection for test purposes AUTO M Voitef Phase Connected to MET The insulation resistance readings obtained should b e not less than the minimum values referred to in Table 2.8. Example of an insulation resistance test on a circuit with equipment that might be damaged during test 643.3.3 Figure 2.24 illustrates the test carried out following connection of equipment that might be susceptible to damage during a n insulation resistance test. Prior to connection of the equipment, all cables of the circuit should b e tested at 5 0 0 V DC, as described previously. Following connection of the sensitive equipment, provided that wiring has been previously tested at 5 0 0 V DC: (a) insulation resistance tests on a circuit are carried out at 2 5 0 V DC; (b) the test voltage is recorded o n t h e schedule of test results; and (c) the test is carried out between live conductors and cpc, with live conductors connected together. In simple installations, such as dwellings, in which m o s t circuits contain sensitive equipment, o r equipment that might affect the test, provided all cables in the installation have been tested in accordance with Table 6 4 of BS 7671 (Table 2.8) prior to connection, this test could b e carried o u t for t h e whole installation. 72 G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology 2 ▼ Figure 2.24 Insulation resistance test of a complete circuit with sensitive equipment following connection of cables .* > * ♦ « * *> * * ♦ * * lili 'O SMART-touch LED dimmers t h a t might be damaged during insulation resistance test Main switch off, secured by safety locking device. General lighting service (GLS) Lamps Removed. Switches "on". When originally installed, cables of circuit tested prior to connection in accordance with Table 64 of BS 7671. 643.3 2.6.8 Confirming testing a >E3E3E3mq 2 Votts/ Means o f earthing and main bonding connected. SELVor PELV circuits by insulation resistance In order to establish which insulation resistance tests are required for verifying a SELV or PELV system, t h e requirements of Section 414 of BS7671 must first b e understood. There are situations where the provision of insulation of SELVor PELV circuits for basic protection is generally not required by BS7671, i.e. forthe following voltages: 414.4.5 (a) up to 12 V AC or 3 0 V DC in wet areas; and (b) up to 2 5 V AC or 60 V D C in dry areas. Par However, for locations containing a bath or shower, or i n swimming pools, saunas and some other special locations, basic protection by insulation is required for SELVand PELV at all voltages. It is often, therefore, easier to carry out insulation resistance tests o n these circuits as a matter of course. Where SELVor PELV is used as a protective measure, a n d insulation resistance testing is required, Tables 2.12 and 2.13 set out the requirements. Instrument: use an insulation resistance tester for these tests (see Section 4.4). Guidance Note 3: Inspection & Testing © The Institution of Engineering and Technology 73 2 643.3.2 ▼ T a b l e 2 . 1 2 SELVinsulation resistance tests Test type Description Basic insulation Between live conductors a n d all other Test voltage DC(V) Minimum acceptable resistance (MQ) 250 0.5 250 0.5 circuits, including other SELVand PELVand l o w voltage (LV) circuits Live to Earth Note: 643.4.2 Between all SELV live parts a n d Earth In situations w h e r e t h e SELV conductors are separated by insulation only covering conductors of b o t h voltage bands, such as within a multicore cable with LV circuits, t h e n t h e test voltage shall b e increased to 5 0 0 V D C a n d t h e insulation resistance shall b e n o t less t h a n 1 M Q . ▼ Table 2.13 PELVinsulation resistance tests Test type Description Basic insulation Between live conductors a n d all other circuits, including other SELVand PELVand LV circuits Note: Test voltage DC (V) Minimum acceptable resistance (MQ) 250 0.5 In situations w h e r e t h e PELV conductors are separated by insulation only covering conductors o f b o t h voltage bands, such as within a multicore cable w i t h LV circuits, t h e n t h e test voltage shall b e increased t o 5 0 0 V DC a n d t h e insulation resistance shall b e n o t less t h a n 1 M Q . 643.4.3 2.6.9 Testing of electrically separated circuits The source of supply should b e inspected to confirm compliance with the Regulations. In addition, should any doubt exist, the voltage should b e measured to verify that it does not exceed 5 0 0 V. Insulation tests are then made as detailed in Table 2.14. Instrument: use an insulation resistance tester for these tests (see Section 4.4). ▼ Table 2 . 1 4 Tests m a d e t o verify electrical separation 74 G u i d a n c e Note Test voltage DC(V) Minimum acceptable resistance (MQ) Between t h e electrically separated live conductors a n d t h e transformer secondary live conductors 500 1.0 Basic insulation of the separated conductors Between t h e electrically separated live conductors a n d their corresponding exposed-conductive-parts 500 1.0 Basic insulation of any exposed- conductiveparts associated with separated conductors Between any exposed-conductive-parts associated with t h e electrically separated circuits and any protective conductor, other exposed-conductiveparts or Earth 500 1.0 Test type Description Basic separation 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology Additional inspections and tests for separated circuit supplying m o r e than one item of current-using equipment: 418.3.4 (a ) Apply a continuity test between all exposed-conductive-parts of the separated circuit to ensure that they are b o n d e d together. Carry o u t a 5 0 0 V DC insulation resistance test between the non-earthed protective bonding conductor and: (i) the protective conductors and/or exposed-conductive-parts of other circuits;and (ii) extraneous-conductive-parts. The insulation resistance should b e not less than 1.0 M Q . Instruments: low-resistance ohmmeter use a and an insulation resistance tester for these tests. See Section 4. (b) All socket-outlets m u s t b e inspected t o ensure that the protective conductor contact is connected to t h e non-earthed protective bonding system. (c) All flexible cables other than those supplying Class II equipment must b e inspected to ensure that they contain a protective conductor for use as an unearthed 418.3.7 protective bonding conductor. (d ) Operation of the protective device must b e verified by measurement of the fault loop impedances (i.e. between live conductors) to t h e various items of connected equipment. These values should then b e compared with the maximum Z s value required by Regulation 411.4.5, with reference to the t y p e and rating of the protective device for the separated circuit. For 2 3 0 V systems, Tables 41.2 and 41.3 of Chapter 41 of BS 7671 may b e used for the maximum Z s values for fuses and circuit-breakers, respectively. Although these tables pertain to t h e line/protective conductor loop path, and the measured values are between live conductors, they give a reasonable approximation t o the values required to achieve the required disconnection 2.6.10 Testing of functional 411J extra-low time of Table 41.1. voltage (FELV) circuits A FELV system is an extra-low voltage system meeting the requirements of Regulation Group 411.7 (Functional extra-low voltage (FELV)). The system does not m e e t all the requirements of Section 414 of BS 7671 relating to SELVor PELV.and its use is permitted only where SELVor PELVare not necessary. Regulation 643.3.2 requires that FELV circuits shall meet t h e test requirements for LV circuits (such as 'mains voltage' circuits). This includes t h e testing of: $45 (a) continuity of protective conductors (see Section 2.6.5); (b) insulation resistance (see Section 2.6.7); the test voltage being 5 0 0 V DC and t h e minimum 643.6 insulation resistance being 1 M Q and c ( ) polarity (see Section 2.6.12). It should also b e checked by inspection that: 41L7.2 (a ) the exposed-conductive-parts of t h e FELV system are connected to the protective conductor of the primary circuit of the source, provided that the primary circuit is subject to protection by ADS in accordance with Regulations b the 411.3 to 6; 411.7 ( ) source of t h e FELV system is one that meets t h e requirements of Regulation 411.7.4; and (c) plugs, socket-outlets, connecting luminaire supporting couplers (LSCs), devices for luminaires (DCLs) and cable couplers in a FELV system are required to have a protective conductor contact (connected to the protective conductor) and not b e dimensionally compatible with those used for any other systems in use at the same premises. Guidance Note 3: I n s p e c t i o n & Testing © The Institution of Engineering and Technology 75 2 134.5 A D S f o r protection against electric shock is not r e q u i r e d i n a FELV system, but may b e r e q u i r e d f o r o t h e r r e a s o n s , s u c h a s p r o t e c t i o n against t h e r m a l e f f e c t s . 418.1.2 2.6.11 Proving and testing o f non-conducting location 643.5 resistance/impedance o f floors and walls) (insulation I n t h e rare c i r c u m s t a n c e s w h e r e f a u l t p r o t e c t i o n i s p r o v i d e d by a n o n - c o n d u c t i n g location (which should be remembered general application), the following as a measure of protection not recognized should be verified, prior to carrying out insulation testing: ( a ) e x p o s e d - c o n d u c t i v e - p a r t s should b e inspected to c o n f i r m that under c i r c u m s t a n c e s n o - o n e c a n c o m e into s i m u l t a n e o u s c o n t a c t w i t h : (i) (ii) for ordinary two e x p o s e d - c o n d u c t i v e - p a r t s ; o r a n exposed-conductive-part a n d a n y extraneous-conductive-part if t h e s e p a r t s are liable to b e at different potentials t h r o u g h failure of t h e basic insulation (b) of a live p a r t ; i n a non-conducting location, t h e r e m u s t b e n o protective conductors; a n d (c) a n y socket-outlets i n s t a l l e d in the l o c a t i o n m u s t not incorporate a n earthing contact. Note: In B S 7671:2018+A2:2022, Appendix 1 3 provides guidance on escape routes a n d fire protection. There is n o longer guidance in BS7671 for measurement of insulation resistance/impedance of floors a n d walls to earth o r the protective conductor system. Following t h e s e checks, t h e insulation resistance b e t w e e n t h e insulating floors a n d 643.3 w a l l s to t h e installation MET (via a l o c a l e a r t h terminal of the general installation) s h o u l d b e m e a s u r e d . It i s r e q u i r e d t h a t a t l e a s t t h r e e m e a s u r e m e n t s a r e made. One m e a s u r e m e n t m u s t b e m a d e a p p r o x i m a t e l y 1 m f r o m a n y accessible e x t r a n e o u s conductive-part, f o r e x a m p l e , metal pipe, i n the l o c a t i o n . The other measurements s h o u l d b e m a d e a t d i s t a n c e s f u r t h e r a w a y . M e t h o d s of m e a s u r i n g t h e i n s u l a t i o n resistance/impedance of f l o o r s a n d w a l l s a r e d e s c r i b e d below. Testmethod The insulation resistance S e c t i o n 4.4). T h e t e s t is m a d e b e t w e e n t e s t e l e c t r o d e 1 o r t e s t e l e c t r o d e 2 ( s e e Figures 2 . 2 5 a n d 2.26) test may b e m a d e u s i n g a n i n s u l a t i o n resistance a n d the m a i n protective conductor tester (see of t h e installation. Measuring insulation resistance of floors and walls A magneto-ohmmeter o r battery-powered insulation a n o - l o a d v o l t a g e o f a p p r o x i m a t e l y 5 0 0 V (or i n s t a l l a t i o n exceeds The r e s i s t a n c e tester providing 1 , 0 0 0 V if t h e rated voltage of t h e 5 0 0 V) is u s e d a s a D C source. r e s i s t a n c e is m e a s u r e d between t h e test electrode a n d t h e m a i n protective c o n d u c t o r of t h e installation. The test e l e c t r o d e s may b e either of the f o l l o w i n g types. o f t e s t e l e c t r o d e 1 i s t h e reference method. It i s r e c o m m e n d e d t h a t t h e test i s m a d e b e f o r e (varnishes, p a i n t s a n d similar p r o d u c t s ) . 76 G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology I n c a s e of dispute, the application the use of the s u r f a c e treatment 2 Test electrode 1 The test electrode shown in Figure 2.25 comprises a metallic tripod, of which the parts resting o n the floor f o r m the points of a n equilateral triangle. Each supporting part is provided with a flexible base, ensuring, w h e n loaded, close contact with the surface being tested over an area of approximately 9 0 0 m m 2 and having a combined resistance of less than 5,000 Q between the terminal and the conductive rubber pads. Before measurements are made, the surface being tested is cleaned with a cleaning liquid. While measurements of t h e floors and walls are being made, a force of approximately 7 5 0 N (75 kg in weight) for floors or 2 5 0 N for walls is applied t o the tripod. ▼ Figure 2 . 2 5 Test electrode 1 039 021 10 180 15 5 mm — ♦ aluminium plate view from above 23 033 profile view section of a contact stud in a conductive rubber Dimensions in millimetres terminal contact stud in conductive rubber view from below Test electrode 2 The test electrode shown in Figure 2.26 comprises a square metallic plate with sides that measure 2 5 0 m m and a square of dampened, water-absorbent paper, o r cloth, f r o m which surplus water has been removed, with sides that measure approximately 270 mm. The paper or cloth, as applicable, is placed between the metal plate and the surface being tested. During measurement, a force of approximately 7 5 0 N (75 k g in weight) for floors or 2 5 0 N for walls is applied to the plate. Guidance Note 3 : Inspection & Testing © The Institution of Engineering and Technology 77 2 ▼ Figure 2.26 Test electrode 2 750 N wooden plate L metal plate damp cloth floor covering subfloor PE Expected results The floors and walls are considered to b e non-conducting where t h e measured resistances are at least 5 0 kQ (where the system voltage to Earth does n o t exceed 500 V). 645.5 A further test is specified in BS 7671 for extraneous-conductive-parts that are within the location, b u t to which insulation has been applied during construction. I n these cases, a 'flash' insulation tester is required, which, after t h e standard 5 0 0 V insulation test, applies a 2 kV AC root mean square (rms) test and measures the leakage current (which should not exceed 1 mA). 643.6 2.6.12 Polarity testing The polarity of all circuits must b e verified before connection t o the supply, with either an ohmmeter or the continuity range of an insulation and continuity tester. A typical test o n a lighting circuit is shown in Figure 2.27. Alternatively, polarity can b e verified by visually checking core colours at terminations, thus verifying t h e installer's connections. Whatever m e t h o d is used, polarity checks are required at all points o n a circuit to ensure that conductors have not been crossed at intermediate connection points such as junction boxes. Instrument', use a low-resistance ohmmeter for these tests (see Section 4.3). A test for polarity is necessary to ensure that all fuses and single-pole control and protective devices are connected in t h e line conductor. The centre contact of screw-type lampholders must b e connected to the line conductor (except EI4 and E27 t o BS EN 60238), so this needs to be verified, as does the correct connection non-reversible plugs and socket-outlets. It is important of all to remove all other lamps o n t h e circuit, as these may provide a conductive path between line and neutral which would t h e n permit an incorrectly connected lampholder to indicate continuity. Note: 78 The continuity test (see Section 2.6.5) and ring final circuit continuity test (see Section 2.6.6) help to confirm polarity. Guidance Note 3: Inspection & Testing © The Institution of Engineering and Technology 2 F i g u r e 2 . 2 7 P o l a r i t y test o n a l i g h t i n g c i r c u i t S // I ‘i / / / / I T/ [O] Temporary shorting link . / Polarity test is carried out at single pole switching devices, and screw type lampholders (except E14and E27 t o BSEN60328). AUTO | REMEMBER TO REMOVE THE TEMPORARY SHORTING LINK WHEN TESTING IS COMPLETE. 2.6.13 Earth electrode resistance testing T h r e e m e t h o d s of measuring t h e resistance of a n earth electrode are described i n this s e c t i o n . Test m e t h o d E l u s e s a d e d i c a t e d e a r t h e l e c t r o d e t e s t e r (fall o f p o t e n t i a l , t h r e e - o r f o u r - t e r m i n a l type); (stakeless o r p r o b e type); test m e t h o d E2 uses a dedicated earth electrode tester a n d test m e t h o d E 3 u s e s a n EFLI tester. Test m e t h o d E l : measurement using a dedicated earth electrode tester (fall of potential, three- or four-terminal type) For safety reasons, it i s essential t h e supply. Caution: If this i s the only e a r t h electrode, electrode/MET. installation t o ensure that the i n s t a l l a t i o n i s securely isolated f r o m It i s a l s o n e c e s s a r y to d i s c o n n e c t t h e e a r t h i n g c o n d u c t o r f r o m the e a r t h unprotected this m a y leave the against e a r t h faults, so complete isolation of the installation must b e m a d e . This d i s c o n n e c t i o n w i l l e n s u r e t h a t t h e test c u r r e n t p a s s e s only through installation t h e e a r t h e l e c t r o d e a n d not m u s t remain isolated and t h e e a r t h e l e c t r o d e connection Ideally, the test should f r o m the supply t h r o u g h any parallel paths. until all testing The completed reinstated. be carried out when the ground conditions are least favourable, such as when the soil i s frozen or very dry. Refer to Annex C of I E C 60364-6 The t e s t requires h a s been t h e use of two t e m p o r a r y test spikes (electrodes), for further guidance. a n d is c a r r i e d o u t i n t h e f o l l o w i n g manner. Guidance © T h e Institution Note 3: I n s p e c t i o n & Testing of Engineering a n d Technology 79 2 C o n n e c t i o n to t h e earth e l e c t r o d e is made using terminals C l a n d P I of a four-terminal e a r t h tester. To e x c l u d e the r e s i s t a n c e of t h e test l e a d s f r o m t h e resistance reading, individual leads s h o u l d b e t a k e n f r o m t h e s e terminals a n d c o n n e c t e d separately to t h e electrode. be linked Where together t h e test lead resistance at the test instrument i s insignificant, a n d connection t h e two terminals m a d e with a single may test lead, w i t h t h e s a m e b e i n g t r u e if u s i n g a t h r e e - t e r m i n a l tester. C o n n e c t i o n t o t h e t e m p o r a r y spikes is m a d e as s h o w n i n F i g u r e 2.28. ▼ 2 . 2 8 Typical earth electrode test using a three- o r four-terminal Figure tester Temporary test VoKW Pha»e \ Test spike (current, note 3) ' ' Test spike (voltage, note 2) Electrode under test (note 1 ) 3 m 3m 15 - 2 5 m 15 - 2 5 m Notes: 1 2 3 4 Connect to terminals Cl and P I of four-terminal tester, or terminal X of a three-terminal tester. Connect to terminal P2 of a four-terminal tester, o r terminal P of a three-terminal tester. Connect to terminal C 2 of a four-terminal tester, or C of a three-terminal tester. Voltage test spike is moved in t h e directions shown. The d i s t a n c e b e t w e e n t h e test spikes is i m p o r t a n t . If t h e y a r e t o o c l o s e together, their r e s i s t a n c e areas w i l l o v e r l a p . I n general, r e l i a b l e r e s u l t s m a y b e e x p e c t e d i f t h e d i s t a n c e between t h e e l e c t r o d e under maximum dimension test a n d the current of t h e e l e c t r o d e system, spike, C2, i s at least ten times f o r example, the 3 0 m for a 3 m long r o d electrode. Three readings (a) a r e taken: firstly, w i t h t h e p o t e n t i a l spike, under test a n d t h e current with T 2 moved T2, inserted m i d w a y b e t w e e n t h e electrode spike, T l ; (b) secondly, to a position 1 0 7o of t h e o v e r a l l electrode-to-current (c) last, w i t h T 2 m o v e d t o a p o s i t i o n 1 0 7o o f t h e overall d i s t a n c e t o w a r d s t h e s p i k e d i s t a n c e b a c k t o w a r d s t h e e l e c t r o d e u n d e r test; a n d c u r r e n t spike, f r o m its initial position between t h e e l e c t r o d e u n d e r test a n d T I . By c o m p a r i n g t h e t h r e e r e a d i n g s , a p e r c e n t a g e d e v i a t i o n c a n b e d e t e r m i n e d . T h i s i s calculated by taking the average of the three readings, finding the maximum deviation of the readings from this average in ohms, and expressing this a s a percentage of the average. 80 G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology 2 The accuracy of t h e measurement using this technique is typically 1.2 times t h e percentage deviation of t h e readings. It is difficultto achieve an accuracy of measurement better than 2 °/o,and inadvisable to accept readings that differ by m o r e than 5 7o. In this event, to improve the accuracy of the measurement, t h e test must b e repeated with a larger separation between the electrode under test and the current spike. The test instrument output may b e AC o r reversed DC to overcome electrolytic effects. Because these instruments employ phase-sensitive detectors, the errors associated with stray currents are eliminated. The instrument should b e capable of checking that the resistance of the temporary spikes used fortesting iswithinthe accuracy limits stated in t h e instrument specification. This may b e achieved by an indicator provided on the instrument, or t h e instrument should have a sufficiently high upper range to enable a discrete test to b e performed o n the spikes. Where the resistance of the temporary spikes is t o o high, measures to reduce the resistance will b e necessary, such as driving the spikes deeper into the ground or watering with brine t o improve t h e contact resistance. Umno c i r c u m s t a n c e s should the latter technique b e used to temporarily e a r t h electrode under test. ON COMPLETION IS reduce the resistance OF THE TEST, ENSURE THAT THE EARTHING RECONNECTED, BEFORE THE INSTALLATION IS of t h e CONDUCTOR ENERGIZED (OR RE-ENERGIZED). Test method E2: Measurement using a dedicated stakeless or clamp based earth electrode tester 643.7.2 A number of types of earth electrode resistance tester are available that utilize clamps 542.1 and can carry o u t measurements without the earth electrode under test having t o b e disconnected from the installation. The use of two such types is described here. I n s t r u m e n t using o n e test c o i l The instrument described here uses a m e t h o d of measurement similar to the fall o f potential m e t h o d (test method E l , described earlier), in that it uses two temporary test spikes (electrodes), as shown in Figure 2.29. These are placed in the ground, away f r o m t h e earth electrode under test, in similar fashion to that described for t h e fall in potential method. Guidance N o t e 3 : Inspection & Testing © The Institution of Engineeringand Technology 81 2 ▼ Figure 2.29 Instrument using one test coil To main earthing terminal of installation Current clamp containing test coil AUTO fi |o vottu Phase Electrode under test (voltage) 15 - 2 5 m Temporary test Test spike (current) | , 15 - 2 5 m The clamp containing the test coil is placed around the earth electrode o r around the conductor under test, connected to that electrode. This eliminates the effects of parallel resistances, so that only the resistance earth electrode under test is measured. The resulting level of accuracy is similar to that given by the fall of potential method. Instrument using two test coils The instrument described here relies for its operation o n there effectively being a number of earth electrodes within t h e installation, and not just the electrode under test. The electrodes other than the one under test might not b e actual earth electrodes; they might b e extraneous-conductive-parts buried in the ground o r in concrete buried in the ground, such as metallic services pipes or buried structural metalwork or, in TN systems, the means of earthing of the supply if this is connected during t h e test. The instrument uses two coils placed a small distance apart around the earthing conductor of t h e installation, as shown i n Figure 2.30, by means of clamps forming part of t h e instrument. In practice, t h e coils may b e combined into a single clamp. O n e coil induces a known voltage in a loop circuit containing t h e earth electrode under test, the general mass of Earth and other connections with earth within the installation. The second coil measures the test current. 82 Guidance N o t e 3: Inspection & Testing © The Institution of Engineeringand Technology 2 ▼ Figure 2.30 Instrument using two test coils Installation main earthing terminal @ @ @ ® ® ® ; ' @® ® ® ® ® ® ® Constant voltage 10 \ Induced current measurement ,clamp Electrode under test (having resistance to Earth RE ) The instrument carries out a calculation using the formula below. This produces a resistance reading intended to represent the resistance of the earth electrode under test. Rreading = + J.+ _L+ _L+>>-+ J. Rj Rj Rn where: reading is the resistance reading given by the test instrument Re is the actual resistance of the earth electrode under test Rb R 2 etc. are the resistances of the other 'earth electrodes' The accuracy of the test reading ( R rea ding) depends on t h e existence of multiple parallel paths for t h e returning test current to t h e instrument, such that t h e effective parallel resistance of these paths is low enough to b e neglected. For example, if there were four other 'earth electrodes', effectively connected i n parallel, each having a resistance of, say, 4 0 Q, their combined resistance would b e 10 Q . If the resistance of the earth electrode under test was 100 Q, the total resistance, Rrea ding. measured by t h e test instrument would be 100 Q +10 Q=110 Q . Consequently, the measured value ( Rrea ding) would b e 1 1 o 7o of the actual value (RE), an error of 10 °/o. However, if there was only one earth electrode other than the o n e under test, the error in the measurement could b e significantly greater, as t h e effective path would t h e n b e through t w o electrodes effectively connected in series. Using the same values as in the previous example, this would m e a n that the resistance, Rrea din g , measured by the test instrument would be 100 Q + 4 0 Q =140 Q . Consequently, Rrea ding would then b e 140 7 o o f the actual value (R E), an error of + 4 0 7o. Guidance Note 3: Inspection & Testing © The Institution of Engineeringand Technology 83 2 Usually, a n e a r t h e l e c t r o d e test is c a r r i e d o u t to e n s u r e t h a t the r e s i s t a n c e R e i s less t h a n a s p e c i f i e d v a l u e . Since Reading > R e , using earth electrode method E 2 may b e m o r e appropriate i n installations w h e r e t h e c o m b i n e d resistance of o t h e r e a r t h e l e c t r o d e s , o r the e f f e c t i v e e a r t h e l e c t r o d e f o r m e d by e x t r a n e o u s - c o n d u c t i v e - p a r t s , a n d the electrode under test, i s l e s s t h a n the limit i s u s e f u l a t p r o p e r t i e s w h e r e g r o u n d is not r e q u i r e d f o r R e . The test method available t o i n s e r t m e a s u r e m e n t e a r t h electrodes T 1 a n d T2 for test m e t h o d E l , for example, d u e to extensive p a v e d o r t a r m a c s u r f a c e s , a n d the use of test method E3 is not d e s i r a b l e due to safety concerns. Testmethod E3: Measurement using an earth fault loop impedance (EFLI)tester An e a r t h e l e c t r o d e may b e tested using a n EFLI tester. However, the results m a y not b e a s accurate a s using a dedicated it is recognized that e a r t h e l e c t r o d e tester. F O R SAFETY REASONS, T H E INSTALLATION M U S T B E ISOLATED FROM T H E SUPPLY B E F O R E DISCONNECTING T H E EARTHING CONDUCTOR. T h e EFLItester i s c o n n e c t e d b e t w e e n the line c o n d u c t o r a t t h e source of the installation a n d the e a r t h e l e c t r o d e via t h e e a r t h i n g c o n d u c t o r , a n d a test p e r f o r m e d . T h e i m p e d a n c e r e a d i n g t a k e n i s t r e a t e d a s t h e electrode resistance. ON COMPLETION OF THE TEST, ENSURE THAT THE EARTHING CONDUCTOR IS RECONNECTED BEFORE THE SUPPLY IS ENERGIZED (OR RE-ENERGIZED). Results of earth electrode testing For TN-S systems s u p p l i e d by t r a n s f o r m e r o r generator a d i s t r i b u t i o n n e t w o r k operator, o r a distribution having its own earth e l e c t r o d e a c c o r d i n g to BS7430, electrode r e s i s t a n c e v a l u e s m a y n o t h a v e b e e n s p e c i f i e d , a s t h e r e is a s e p a r a t e m e t a l l i c e a r t h conductor a n d electrodes often simply provide a local reference earth. For installations that c o n t a i n generators, including static c o n v e r t e r s (inverters) o p e r a t e i n d e p e n d e n t l y , o r a s a s w i t c h e d a l t e r n a t i v e to t h e p u b l i c supply, e l e c t r o d e s h o u l d c o m p l y w i t h the r e c o m m e n d a t i o n s of B S 7430, Practice for Electrical Energy Storage Systems that t h e earth o r the IET Code of a s appropriate. For T T s y s t e m s , i n t h e a b s e n c e o f t h e d e s i g n e r ' s s p e c i f i c a t i o n , B S 7 6 7 1 m a x i m u m values where Regulation 4T1.5.3 R C D s a r e used for automatic disconnection of supply that by are addressed i n 411.5.3. R e g u l a t i o n 411.5.3 requires: (a) t h e disconnection time shall R e g u l a t i o n 4 1 1 . 3 . 2 . 3 o r 411.3.2.4; be required Regulation 411.3.2.2, and (b) R a x lAn < 50 V where: Ra is the sum of the resistances of the e a r t h electrode a n d the protective c o n d u c t o r ( s ) c o n n e c t i n g it to the e x p o s e d - c o n d u c t i v e - p a r t s ( i n Q ) . iAn is t h e rated r e s i d u a l o p e r a t i n g current For a nominal voltage, of the R C D (in a m p s ) . U o , of 2 3 0 V , Table 2.15 gives m a x i m u m values n o n - d e l a y e d RCDs, w h i c h m a y b e s u b s t i t u t e d f o r R A i n e q u a t i o n (b) a b o v e . 84 G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology of Z s f o r 2 ▼ Table 2.1 5 Maximum values of EFLI (Z s) for non-delayed RCDs to BS EN 61 008-1 and BS EN 61009-1 for U o of 2 3 0 V Maximum value of EFLI, Zs (Q) RCD rated residual operating current, l/\n (mA) Where a time-delayed RCD is used t o provide fault protection, t h e maximum value of EFLI, including t h e earth electrode resistance, must b e such that the requirements of 411.3 and 411.5 are met. This is likely to require a lower figure than given above. The table indicates that the use of a suitably rated RCD will theoretically allow m u c h higher values of R A, and therefore of Z s, than could b e expected by using the circuit overcurrent devices for fault protection. Note: 643.7 It is advised, however, in Note 2 of Table 41.5, that earth electrode resistance values above 2 0 0 Q may not b e stable, as soil conditions change due to factors such as soil drying and freezing. 2.6.14 Protection by automatic disconnection of supply (ADS) The effectiveness of measures for fault protection by ADS can b e verified for installations within a TN system by: (a) measurement of EFLI (as described in 2.6.15); (b) confirmation by short-time visual inspection that overcurrent devices have suitable or instantaneous tripping setting for circuit-breakers, or current rating (l n) and t y p e for fuses; and (c) where RCDs are employed to meet disconnection times for ADS, testing to confirm that the disconnection times of Chapter 41 of BS 7671 can b e m e t by verifying EFLI, and testing operation of RCDs (see Sections 2.6.15 and 2.6.18). For installations within a TT system, effectiveness can be verified by: (a) measurement of the resistance of the exposed-conductive-parts of the equipment (b) confirmation short-time by visual inspection that earthing arrangement of the for the circuit in question; overcurrent devices have suitable or instantaneous tripping setting for circuit-breakers, or current rating (l n) and type for fuses; and (c) where RCDs are employed, testing to confirm that the disconnection times of Chapter 41 of BS 7671 can b e met by verifying EFLI, and testing operation of RCDs (see Sections 2.6.15 and 2.6.18). 643. 643.7.3 Where RCDs are required for additional protection, operation of RCDs (see Section 2.6.18). this is verified by testing the 2.6.15 Earth fault loop impedance (EFLI) verification Where limitation of EFLIis part of a protective measure, it is fundamental that t h e initial verification process includes verification of EFLIs. Guidance Note 3: Inspection & Testing © The Institution of Engineering and Technology 85 2 The earth fault current loop comprises the following elements, starting at the point of fault o n t h e L-Efault loop: (a) the cpc; (b) the MET and earthing conductor; (c) for TN systems, t h e metallic return path or, in t h e case of TT and IT systems, t h e earth return path; (d) t h e path through the earthed neutral point of the transformer; (e) the transformer winding (or the equivalent in another source of energy); and (f) the line conductor f r o m the ’source’ to t h e point of fault. There are two methods used for verifying total EFLIfor a circuit: 1 measurement of total EFLI(Zs) using an EFLItester, where it is safe to d o so; or 2 measurement of (R] + R 2) during continuity testing of a circuit (see Sections 2.6.5 and 2.6.6) and addition to the measured EFLI external to that circuit (Z e). The latter is preferred w h e n determining Z s for final circuits and distribution circuits. Measurement o f total E F L I ( Z Measurement using a n E F L I t e s t e r of Z s is made o n a live installation and, for safety and practical reasons, neither the connection with Earth nor bonding conductors are disconnected. Where measurements are made close to a transformer, an instrument with suitable resolution is required. Instrument: Note: use an EFLItester for this test (see Section 4.5). An EFLItester may not produce an accurate reading in installations with grid-connected or island-mode (grid-forming) inverters (see Section 2.6.24). M e a s u r e m e n t o f (R! + R2) d u r i n g continuity t o t h e EFLI e x t e r n a l t o t h a t c i r c u i t (Z e) testing of a c i r c u i t a n d addition This procedure is described in Section 2.6.5 and, for ring circuits, Section 2.6.6. The (Ri -I- R 2) value recorded for a particular circuit is added to the EFLI at the origin of that circuit. F o r a consumer unit at t h e origin of an installation, this is as follows: Zs = Ze + (Ri + R2) where: Zs Ze (R 1 + R2 ) is the total EFLI in Q is the external EFLI'external' to the installation is the measured resistance of t h e line conductor and cpc, measured during the continuity test method 1 or step 3 of the ring circuit continuity test. For consumer units or distribution boards not at the origin, confusion can arise over the term 'external EFLI'(Z e) and some prefer to write or note t h e EFLI at the distribution board as Zdb- As this value is not external to the installation, the formula is modified to: Zs = Zdb + (Ri + R2) 86 G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology 2 Circuit-breakers a n d residual current devices (RCDs) The test (measuring) current of EFLI testers may trip some types of 6 A Type B circuit-breakers and any RCD protecting t h e circuit. This will prevent a measurement being taken and may result in a n unwanted disconnection of supply to the circuit under test. Instrument manufacturers can supply l o o p testers that are less liable to trip RCDs by either limiting t h e test current (to less than 15 mA) or by DC biasing (this technique saturates the core of the RCD prior to applying the test). M e a s u r e m e n t o f external EFLI (Z e) 542 4 2 The externa l EFLI, Z e , is measured using an EFLItester at the origin of the installation. The impedance measurement is made between t h e line conductor of the supply and the means of earthing with t h e main switch open or with all t h e circuits isolated. The means of earthing must b e disconnected f r o m t h e installation MET for t h e duration of t h e test, to remove parallel paths. Care should b e taken to avoid any shock hazard to the testing personnel and other persons on the site, both whilst establishing contact and whilst performing t h e test. It is strongly recommended to check for diverted neutral currents where there is a TN-C or TN-C-S earthing arrangement, or where PME conditions apply (see Appendix E). ENSURE THAT THE EARTH CONNECTION THE INSTALLATION H A S BEEN RECONNECTED BEFORE IS ENERGIZED (OR RE-ENERGIZED). See Figure 2.31 for test method connections. Instrument: use a n EFLItester for this test (see Section 4.5). ▼ Figure 2 .31 Example of a test for Ze at the origin of a small installation | pate I I [oonia i&h i<wh| 0101 ■O gBfflBBfla Main switch off, secured by safety locking device. Test between i n c o m i n g l i n e conductor a n d t h e m e a n s o f earthing, which s h o u l d be disconnected from t h e rest 100 A of t h e installation, a n d f r o m extraneous-conductiveparts, s o t h e r e a r e n o parallel p a t h s . As previously mentioned, the measured Ze can be used to add to circuit (Rj + R2) values. Guidance N o t e 3 : Inspection & Testing © The Institution of Engineering and Technology 87 2 Determining external EFLI(Ze) by enquiry The external EFLI,Ze, can b e determined by enquiry with the electricity distributor. However, if this is relied upon, a test must b e made to verify that t h e D N O earthing is effective. A test lamp may b e used to check that current is able t o pass between line and the means of earthing. Alternatively, an EFLItester can b e used to verify that the value of Ze is consistent with that quoted by the distributor o r measured previously. Verification of EFLItest results 643 J K i s important to recognize that BS 7671 requires the inspector not only to test the installation, but also to compare the results with relevant design criteria (or with criteria within BS7671). This may seem obvious, b u t it is not u n c o m m o n for some inspectors to pass test information back to their office without making the necessary comparisons, possibly assuming that t h e office or someone else will check t h e results. The office might then assume that t h e inspector has checked t h e results against criteria, whereas in fact, no-one has. It is important to remember that the person w h o signed the certificate is responsible. Employees should follow their employer's respect of methods for determination of prospective fault current. procedures in Values of Zs should b e compared with o n e of the following: (a) for standard thermoplastic (polyvinylchloride Appendix A of this Guidance Note. Table 4 1 2 Table 4L4 (b ) EFLI figures provided PVC) circuits, the values i n by the designer. See also Appendix A, which provides information o n how to correct measured results for ambient temperature, as this m a y not have been done by the designer (the inspector will need to clarify this point). (c) tabulated values in BS 7671, corrected for temperature. See Appendix A, which provides information o n how to correct measured results for ambient temperature. (d) using a factor of 0.8 (see Appendix A2). Appendix A provides a formula for making temperature adjustments, together with a worked example. 643.7.3.201 2.6.16 Prospective fault current (l pf ) Regulation 643.7.3.201 introduces the requirements of Regulation 434.1 into t h e testing section, with the designer required to determine t h e prospective fault current under both short-circuit and earth fault conditions a t every relevant point o f t h e installation. This may b e done by calculation, b e ascertained by enquiry or b e measured directly using an instrument (inspection). The expression 'every relevant point’ means every point where a protective device is required to operate under fault conditions, and includes the origin of the installation. Appendix 14 provides s o m e further guidance on these requirements. The inspector must have knowledge of the design in this respect as, for example, if t h e switchgear at the origin of a n installation is suitably rated for prospective fault current, a n d switchgear of similar short-circuit rating is used downstream of that point, then n o further checks will b e necessary. This is because the magnitude of the prospective fault current decreases with increasing distance downstream of the origin, assuming there is not another source of supply, such as a generator, connected to t h e installation at a point other than the main supply terminals of the installation. Any fault current contribution f r o m a generator must b e included if the generator can operate in parallel with the supply. If a generator or other source can supply the installation in place of 88 G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology 2 t h e normal supply, then generally fault currents will b e significantly lower and t h e protection may take longer to clear a fault, making it possible that t h e l 2 t contribution could cause thermal damage t o some cables or equipment. Regulation 434.5.1 requires that, except where back-up protection is provided by another device in accordance with the second paragraph of that regulation, the breaking capacity rating of each protective device shall be not less than the prospective fault current at its point of installation. The t e r m 'prospective fault current' includes t h e prospective short-circuit current and the prospective earth fault current. The maximum prospective fault current at the point of installation of a protective device is the greater of these t w o prospective fault currents at that point, which should b e determined and compared with the breaking capacity of the device. W i t h t h e p o w e r on, the m a x i m u m v a l u e of t h e prospective short-circuit current can b e obtained by direct connection of t h e instrument between live conductors at the protective device at t h e origin or other relevant location within t h e installation. Both two-lead and three-lead instruments capable of determining prospective fault current are available; it is important that any instrument used is set to the correct range and connected i n accordance with the manufacturer’s instructions for its use. Failure to do so could b e dangerous, could result in damage to t h e instrument and might result in misleading readings being obtained. Instrument: use the prospective fault current range of a suitable EFLItester for this test (see Section 4.5, final paragraph). With some instruments, the voltage between line conductors cannot b e measured directly. Where this is t h e case, it can b e assumed that for three-phase supplies, the maximum balanced prospective short-circuit level will be, as a rule of thumb, approximately twice the single-phase value. This figure errs o n the side of safety. Where a n instrument is rated for the higher voltage, a more accurate prospective fault current measurement, for a three-phase installation, can b e obtained by measuring the line-to-line fault current and dividing the measured result by 0.87. Prospective earth fault current may b e obtained with the same instrument. Again, care must b e taken to ensure that t h e instrument is set correctly and connected as per the manufacturer's instructions for use. Appendix 14 of BS 7671 provides a reminder measurements of the hazards involved directly from live parts. Guidance in HSE publication in taking HSR25 should b e followed. It is recommended t h a t alternative m e a n s a r e u s e d t o d e t e r m i n e prospective fault current w h e r e possible. Where a measurement of prospective fault current is necessary, it should always b e made downstream of a protective device rated for t h e anticipated prospective fault current. Fused test leads alone are not considered suitable for this purpose, and, in t h e absence of a suitable protective device, a temporary one should b e fitted. Note: A prospective fault current tester may not produce an accurate reading in installations with grid-connected or island-mode (grid-forming) inverters (see Section 2.6.24). Guidance N o t e 3: Inspection & Testing © The Institution of Engineering and Technology 89 2 The values obtained should b e compared with t h e breaking capacity of t h e appropriate protective device. The breaking capacity of t h e protective device should b e greater than the highest value of prospective fault current obtained using the instrument. Whichever is the greater of the prospective short-circuit current and the prospective earth fault current obtained should be recorded o n the EIC,EICRand the Schedule of Test Results, as appropriate. If t h e measured value of prospective fault current appears to exceed t h e fault current rating for t h e equipment the current-limiting or protective device, further consideration m u s t b e given to effect of any upstream protective devices and the ability for the source of supply to deliver the indicated prospective fault current. The maximum value of prospective fault current for an installation will be with t h e installation unloaded and t h e conductors at ambient temperature. F o r a three-phase system, the prospective three-phase short-circuit current will always b e larger than the single-phase line-to-neutral or earth fault currents. Note on the accuracy of EFLIand prospective fault current testers (see also Sections 2.6.24 and 4.5) EFLI testers become less accurate at low value impedance readings, such as w h e n measuring close to a transformer noted that the standard instrument or other low impedance used for determining source. It should b e prospective fault current is effectively an EFLI instrument. While earth fault loop testers should have a resolution of at least 0.01 Q, this should not b e confused with accuracy. A displayed test result of less than about 0.1 Q, or about 1.0 Q,when o n the lower current range (such as 15 mA), could b e prone to significant errors. Such errors can significantly affect the calculation o f prospective fault current. Should more accurate measurements b e needed o n large installations with very low impedance supplies, specialist high-current four-wire EFLI testers are available. Note: An EFLI and prospective in installations (Section with current tester grid-connected fault or may not produce island-mode a n accurate reading (grid -forming) inverters 2.6.24). Rated short-circuit breaking capacities of protective devices The rated short-circuit capacities of fuses, circuit-breakers to BS EN 6 0 8 9 8 and B S 3 8 7 1 (now withdrawn) and RCBOsto B S E N 61009 are shown in Table 2.16. Note that B S 3 8 7 1 identified the short-circuit capacity of circuit-breakers with an 'M1 rating. 90 G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology 2 ▼ T a b l e 2 . 1 6 Rated short-circuit capacities of protective devices Device type Semi-enclosed fuse to BS 3 0 3 6 with category of duty Device designation Rated short-circuit capacity (kA) S1A 1 S2A 2 S4A 4 General-purpose fuse to BS 88-2 System E (bolted) type 80 kA at 400 V System G (clip in) type 50 kA at 230 V o r 8 0 kA a t 400 V Domestic fuse to BS 88-3 ____________________________________________________ Circuit-breakers to ■cn les 1.5 (1-5) 3.0 (3-0) 6 (6-0) 10 (7-5) 15 (7.5) 20 (10.0) 25 (12.5) 1 B S E N 6 0 8 9 8 and RCBOsto B S E N 61009* BS 1361 fuses (BS 1361 has been withdrawn, but these fuses will still be found in existing installations) Domestic fuse to BS 1361 Circuit-breakers to BS 3871 (replaced by BS EN 60898) Two short-circuit capacity ratings are defined in BS EN 6 0 8 9 8 and BS EN 61009: l c n : the rated short-circuit capacity (marked o n t h e device); and l c s : the service short-circuit capacity. Guidance N o t e 3: Inspection & Testing © The Institution of Engineering and Technology 91 2 The difference between the two short-circuit ratings described above is the condition of the circuit-breaker after manufacturer's testing. I c n is the maximum fault current that the device can interrupt safely, although its characteristics may have been altered and i t may n o longer b e usable. Ics is the maximum loss of performance. fault current that the The l c n value (for example, 6,000) device can interrupt safely without is marked o n the device in a rectangle. For t h e majority of applications, t h e prospective fault current at t h e terminals of t h e circuit-breaker should not exceed this value. For domestic installations, t h e prospective fault current is unlikely to exceed 6 kA, up to which value l c n will equal l cs - (For domestic installations, the D N O may specify a higher fault current value - perhaps up t o 16 kA - but this level is rapidly reduced through the impedance of t h e supply cables.) For switchgear, the relevant fault current (short-circuit) rating of t h e switchgear (or assembly) should b e equal t o or exceed the maximum prospective fault current at the point of connection to the system. For non-domestic installations o n the public supply network, this information will have to b e obtained f r o m t h e local DNO. The terminology to define the short-circuit rating of an assembly is given in the BS EN 61439 series of standards as follows: (a) rated short-time withstand current l cw ; (b) rated peak withstand current Ipij and (c) rated conditional short-circuit current l cc . Further details are provided in Guidance Note 2. Fault currents up to 16 kA Except in London and some other major city centres, the maximum fault current for 2 3 0 V single-phase supplies up to 1 0 0 A is unlikely to exceed 16 kA. Appendix 14 of BS7671 advises that it is often not necessary to measure o r calculate the prospective fault current at the origin of individual dwellings or similar premises i n which the distributor has declared the prospective fault current to b e 16 kA: In dwellings (household) or similar premises, where a consumer unit to BS EN 61439-3 is used and the maximum prospective fault current declared by the distributor is 16 kA, it is n o t necessary t o measure or calculate prospective fault current at the origin of the supply. The term 'distribution board for operation by ordinary persons' used in BS EN 61439-3 applies to a wider range of products than a domestic consumer unit. The 16 kA conditional rating applies only to consumer units as defined in B S 7 6 7 1 as follows: Consumer unit (may also b e k n o w n as a consumer control unit or electricity control unit). A particular type of distribution board intended for operation by ordinary persons, comprising a type-tested co-ordinated assembly for t h e control and distribution of electrical energy, incorporating manual means of double-pole isolation on the incoming circuits) and an assembly of one or more protective devices, signalling and other devices proven during the type-test of t h e assembly as suitable for such use. 92 G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology 2 536.4.201 The short-circuit capacity of OCPDs individually having a short-circuit capacity rated less than 16 kA, but incorporated within consumer units, may b e taken to b e 16 kA where: (a) the installation has a supply provided in accordance with the ESQCR, with a nominal voltage of up to 2 5 0 V A C ; (b) the service cutout is a fuse rated 100 A or less complying with either BS 1361 (Type II) o r BS 88-3; (c) t h e consumer unit complies with either: (i) BS EN 61439-3 (including t h e 16 kA conditional short-circuit test described in Annex ZB of t h e standard), incorporating only components and protective devices specified by t h e manufacturer; or (ii) (for initial verification of additions a n d alterations to existing installations with older consumer units) either: • BS 5486-13:1979 with label 'CM16'; • BS 5486-13:1989; or • BS EN 60439-3 (including the 16 kA conditional short-circuit test described in Annex ZA of the standard), incorporating only components and protective (see Regulations devices specified by the manufacturer 432.1 and 530.3.4 of BS 7671:2008). Recording the prospective fault current Both t h e E l C a n d the EICR contain a section headed 'Nature of Supply Parameters', which requires the prospective fault current at the origin to b e recorded. The value to b e recorded is the greater of either the short-circuit current (between o r the earth fault current (between line conductors) live conductors) and the MET). If it is considered necessary to record values at other relevant points, this can b e done o n the Schedule of Test Results. Where the protective devices used at t h e origin have the necessary rated breaking capacity, a n d devices with similar breaking capacity are used throughout t h e installation, it can b e assumed that the Regulations are satisfied in this respect for all distribution boards (provided there is n o t another source of supply, such as a generator, connected to the installation at a point other than the main supply terminals of t h e installation)(see also Section 2.6.24). 2.6.17 643.9 Phase sequence testing Regulation 643.9 requires verification that the phase sequence is maintained for multiphase circuits within an installation. In practice, this will b e achieved by checking polarity a n d connections throughout the installation. While the regulation requires phase sequence to b e maintained throughout the installation, this should not b e confused with phase rotation. Phase rotation is a description of which way a correctly-wired three-phase induction motor will run. If t h e timing of t h e sine waves o n LI, L 2 and L3 are such that LI precedes L2, which precedes L3, then t h e motor will run clockwise. If t h e timing of t h e sine waves is changed by swapping any two wires, as shown in Figure 2.32, then the motor will run anticlockwise. To ensure correct operation of three-phase loads, for example three-phase laundry equipment, it is recommended test phase rotation at t h e point closest to the load, before the load is energized. to Phase sequence continuity may b e confirmed, with the installation/circuits isolated, using testing as for continuity of conductors. This may b e carried out using the same method as Rj + R2 testing. Guidance © T h e Institution Note 3: Inspection & Testing of Engineering a n d Technology 93 2 ▼ Figure 2.32 All possibilities of swapping any two wires Original 1-2-3 phase rotation (wires 1 and 2 swapped) phase rotation = 2-1-3 End result 2 1 3 ----------------------------------------------------- 3 (wires 2 and 3 swapped) phase rotation = 1-3-2 1 ----------------------------------------------------- 1 2 3 2 (wires 1 and 3 swapped) phase rotation = 3-2-1 3 2 2 3 Optionally, a n d o c c a s i o n a l l y , t h e i n s p e c t o r may a p h a s e rotation tester, w i s h to c h e c k p h a s e s e q u e n c e b y u s i n g of e i t h e r : (a) a rotating (b) a n indicator l a m p type. disc t y p e ; o r I n s t r u m e n t s c o n t a i n i n g b o t h of t h e a b o v e f o r m s o f i n d i c a t i o n a r e a l s o a v a i l a b l e . V a r i o u s types of i n d i c a t i o n exist, display equivalent (LCD) leads are connected to i n c l u d i n g a rotating a n d other the disc, m e a n s of indication. i n s t a l l a t i o n and, a n e l e c t r o n i c liquid Generally, crystal coloured o r labelled if t h e p h a s e sequence/rotation i s correct, t h e i n d i c a t i o n c o n f i r m s this. In the c a s e of a rotating d i s c type instrument, S o m e approved offer d o not Both over standard three-wire a t t a c h t h e wires indicator l a m p type, (formerly types d i r e c t i o n of of phase rotation R/B/Y) t h e m . These testers, as they t h e i n s t a l l a t i o n , n e e d i n g o n l y two either the Guidance Note 3: Inspection & Testing © The Institution of Engineering and Technology L1/L2/L3 (formerly R/Y/B) lamp or the l a m p will be illuminated. sequence i n d i c a t o r c a n a l s o b e u s e d to a t t h e s u p p l y t e r m i n a l s to l a b e l l i n g / i d e n t i f i c a t i o n of p l a i n c o n d u c t o r s . 94 to p h a s e rotation be probed with the hand-held probes. the L1/L3/L2 o r anticlockwise. t e s t e r s h a v e a p h a s e r o t a t i o n f a c i l i t y b u i l t i n to i n safety r e q u i r e t h e i n s p e c t o r to p h a s e s to With voltage a n increase the d i s c will rotate either clockwise motors verify p h a s e s e q u e n c e / a n d to confirm the correct 2 ▼ Figure 2.33 Examples of phase sequence indication from phase rotation instruments Indication type Indication for clockwise phase rotation sequence Indication for anticlockwise p h a s e rotation sequence Alphanumeric For example multifunction tester, phase sequence meter Graphical symbols For example multifunction tester, phase sequence meter Illuminated L E D For example approved two-pole voltage tester 2.6.18 Operation and functional testing of RCDs The operating times of RCDs are required to b e tested i n t h e following circumstances: 643.7.1 (a) where they are relied o n for disconnection for compliance with Chapter 41 of BS7671; and 643.8 (b) where they are installed as additional protection, BS 7671. as specified in Chapter 41 of Where RCDs are installed with circuit-breakers and the circuit has the characteristics to satisfy Chapter 41 of BS 7671 without the RCD,then testing of the RCDisnot essential unless it is specified for additional protection. Operation of R C D s 411.4.5 Before using a test instrument, the RCDtest button should b e pressed. This provides 4H.5.3 basic information that the RCD is functioning, and will help avoid danger that may occur during test if the RCD did not respond. BS EN 61557-6 requires the test current for a tripping test to b e applied at the zero-crossing point of the AC wave. Therefore, for each of the tests, readings should b e taken with the test waveform starting on both positive and negative half-cycles usually identified '0°' and '180°’ o n test instruments, and the longer operating t i m e recorded for t h e l x l An Type AC test. Prior to these R C D tests, it i s essential, for safety reasons, that the EFLI i s tested to check the r e q u i r e m e n t s h a v e been met. Guidance Note 3: Inspection & Testing © The Institution of Engineeringand Technology 95 2 Instrument: u s e a n RCD tester f o r t h e s e tests, (see Section 4.7). W h e r e t h e RCD tester is capable of testing RCDs w i t h different residual current operating characteristics (Type AC, Type A, Type F o r Type B), it s h o u l d b e configured f o r t h e correct setting f o r t h e test b e i n g u n d e r t a k e n as indicated i n Table 2.17. RCDs are m a r k e d w i t h s y m b o l s t o indicate their residual current operating characteristic as s h o w n i n Figure 2 . 3 4 . ▼ Table 2.17 Tests for RCDs a Recommended RCD Types tests Instrument RCD Type setting (note 1) Applied residual current Maximum expected tripping time (ms) RCDs to harmonized standards (note 2) RCDs to BS 4293 or BS 7288:1990 (note 3) Non-delay Non-delay S-delay Time-delay All Type AC toxlAn RCD should not trip RCD should not trip All Type AC IxlAn (note 4) 300 200 500 {(0.5 to 1.0) x time deiay}+200 b Examples of optional RCD tests for fault-finding and similar purposes (see notes 5 and 6) RCD Type All RCDs with residual current rating 3 0 mA or less Instrument RCD Type setting (note 1) Applied residual current Type AC Type AC All RCDs with residual current rating exceeding 3 0 mA Type A, F o r B RCDs to a harmonized standard (note 2) Type A (carry out Type AC tests first) Type B RCDs to a harmonized standard (note 2) Type B (carry out Type AC and Type A tests first) Maximum expected tripping time (ms) Non-delay S-delay or time-delay 5 x I a h o r 2 5 0 mA (note 7) 40 150 5xlAn 40 150 V2x( /2xlAn) pulsed DC RCD should not trip l x 0 / 2 x l A n ) pulsed DC 300 500 5 x ( 2 x lz\ n ) pulsed DC 40 150 2 x l / \ n smooth DC 300 500 Notes: 1 Where applicable, Instruments without an 'RCD Type' setting can only b e used to carry out Type AC tests. 2 Harmonized standards for the purposes of Table 2.17a are considered to be BS EN 61008, BS EN 61009, BS EN 60947-2 and BS 7288:2016. (BS 7288:2016 is the UK implementation of HD 6 2 6 4 0 Residual current devices with or without overcurrent protection for socket-outlets for household and similar uses'). 3 RCDs to BS 4293 and editions of BS 7 2 8 8 earlier than BS 7288:2016 should b e tested as Type AC only. Tests for other Types are not applicable for RCDs to these standards. 96 G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology 2 4 This test is required by Regulation 643.7 of BS 7671 (where the RCD is used for automatic disconnection of supply) or Regulation 643.8 of BS 7671 (where the RCD is used for additional protection). RCD to BS 4293 or BS 7288:1990 should meet the operating times of the appropriate product standard, where these are shorter than those specified in BS 7671 :201 8+A2:2022, because a longer operating time than that in the relevant product standard may indicate that the RCD is n o longer operating correctly. The longest tripping time for each of the two tests (0° and 180°) is recorded in column 2 8 of the Schedule of Test Results (see example in Figure 5.6). 5 Optional tests are intended for fault-finding and similar purposes only. The performance requirements of the optional tests are to be met by product manufacturers and are not BS 7671 requirements. Not all test instruments can perform all of the tests listed here (see note 1). 6 Since RCDs are only rated for a finite number of operations, carrying out frequent optional tests can shorten the product's life. For example, in carrying out all of the above tests, including optional tests, for a 30 mA Type B RCD, would require the RCD to 7 trip 12 times. For RCDs to harmonized standards (see note 2), with residual operating current l An 30 mA, the manufacturer may select a current for the Type AC 40 m s tripping test of 2 5 0 mA instead of 5 x l An . Where this is declared by t h e manufacturer, failing to trip within 4 0 m s at 5 x l An . does not necessarily mean the RCD is faulty. For this reason, and to prevent shortening the usable life of RCDs (see note 5), BS 7671:2018+A2:2022 does not require testing of RCDs at 5 x l An . V Figure 2 . 3 4 Markings o n RCDs for residual current operating characteristic RCD Type isymbol symbol reference in IEC 60417 T y p e A C to B S EN 61008, or 6148 T y p e A to B S E N 61008, B S E N 61009, B S E N 60947-2 or 6149 B S EN 61009, B S EN 60947-2 B S 7288:2016 B S 7288:2016 6149+6160 T y p e F to BS E N 62423 OR or B S E N 60947-2 6399 — — — 6149+6160+6297 T y p e B to B S EN 62423 or B S 6398 EN 60947-2 OR 6150 S t y p e (time d e l a y ) in addition 6395 to one of the a b o v e markings Note: RCDs to BS 4293, and BS 7288:1 990, have no marking for residual current operating characteristic. They would be considered equivalent to Type AC RCDs if assessing their continued use with respect to additions to an existing installation downstream of the device. The designer should also consider that there have been other improvements in product standards for RCDs in relation to device characteristics, isolation, short-circuit rating, reliability, and electromagnetic compatibility. Guidance N o t e 3 : Inspection & Testing © T h e Institution of Engineering and Technology 97 2 RCD test method 1: residual current test applied between line and protective conductor RCDtest method 1 is preferred where RCDs are used for fault protection, as it provides further validation that the RCD is operating within a specific t i m e for a simulated fault to t h e relevant protective conductor. The test is m a d e o n the load side of the RCD between t h e line conductor of t h e protected circuit and the associated cpc. The load should b e disconnected during the test to avoid spurious results. These tests can result in a potentially dangerous voltage o n exposed-conductive-parts and extraneous-conductive-parts when t h e EFLI approaches t h e maximum acceptable limits. Precautions m u s t therefore b e taken to prevent contact of persons o r livestock with such parts. It may not b e possible to use this test method conclusively in s o m e situations, for example where: (a) there is an upstream RCD for which there is n o selectivity, such as a test on an RCD in a caravan supplied f r o m a caravan site or repair workshop socket-outlet, where B S 7 6 7 1 requires that the socket-outlet and caravan both have additional protection by an RCD rated 3 0 m A or less. In these cases, either RCD may trip first, and it is n o t guaranteed that t h e disconnection t i m e measurement will b e that of t h e RCD under test. (b) protective conductor currents f r o m equipment that cannot b e disconnected f r o m the circuit under test, or f r o m other parts of the installation energized, affect the conditions time measurement that are of the applied test so that the disconnection is affected. (c) an RCD in an IT system is being tested, and there is n o current return path via a cpc. RCDtest method 2: upstream/downstream test Where RCDtest m e t h o d 1 cannot b e used conclusively, or it is not considered practicable or safe to conduct a n EFLI test prior to testing the RCD, RCD test m e t h o d 2 can b e considered. This method is outlined in Clause 6.3 of PD IEC/TR 6 2 3 5 0 Guidance for the correct use of residual current-operated protective devices (RCDs) for household and similar use, which states that the test method resistance or disconnected avoids risks associated with high protective conductors, a n d avoids instrument errors due to protective conductor currents. The test is m a d e between a live conductor o n the supply side (upstream) of t h e RCD and another live conductor o n the load side (downstream) of the RCD, for example: (a) single-phase RCDs, o r three-phase RCDs with a monitored neutral, between upstream neutral and downstream (b) three-phase (i) (ii) (iii) (iv) (v) (vi) Note: 98 line; or RCDs without neutral, between upstream LI and downstream L2; upstream LI and downstream L3; upstream L 2 and downstream LI; either: upstream L 2 and downstream L3; upstream L3 and downstream L I ; or upstream L3 and downstream L2. The instrument, test leads, and probes, must be rated for the line-to-line voltage of the three-phase system at appropriate overvoltage category (see Section 1.1). G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology 2 Examples of testing an RCCBand RCBOare shown in Figures 2.35 and 2.36 respectively. These examples are included to illustrate the principles only. The person carrying out the test should take all practicable steps to avoid the risk of contact with live parts, such as the example shown in Figure 2.37. The test should only b e performed with covers removed, in equipment where all line conductor terminals meet IP2X/IPXXB. Before attempting this test method, check with the test equipment manufacturer's instructions that the method is supported by the instrument. Some test instruments require only two test leads to be connected during the test, but some require three test leads. ▼ Figure 2 . 3 5 Example of upstream/downstream test o n a single-phase RCD a. 2-lead test (where supported by test equipment) Other circuits switched off where possible Supply ©'I © © Test is made between line conductor at the load side of the RCD, and the neutral conductor at the supply side. Check with test instrument manufacturer that the instrument is suitable for the upstream/downstream test. b. © © © ms I&. 30mA 3-lead test ©©©©©©© Other circuits switched off where possible Supply ©’ E3 ©I© ©I© Test is made between line conductor at the load side of the RCD, and the neutral conductor at the supply side. Check with test instrument manufacturer that the instrument is suitable for the upstream/downstream test. © © ms EF W! ■« - OFF l&n 30mA TEST Guidance Note 3: Inspection & Testing © The Institution of Engineering and Technology 99 2 ▼ Figure 2.36 Example of upstream/downstream test on an RCBO a. 2-lead test (where supported by test equipment) I Supply 1 Other circuits switched off where possible oet Test is made between line conductor at the load side of the RCBO, and the neutral conductor at the supply side. C. J ms Check with test instrument manufacturer that the instrument is suitable for the upstream/downstream test. b. 30mA 3-lead test I \l 1 II Supply 1 Other circuits switched off where possible © EERIE \ \ Test is made between line conductor at the load side of the ROBO, and the neutral conductor at the supply side. Check with test instrument manufacturer that the instrument is suitable for the upstream/downstream test. LJms Un 30mA M In some cases, it is possible to conduct the upstream/downstream test without having to remove equipment covers, as an upstream neutral can b e connected via an appropriate socket-outlet combination. Examples are shown in Figures 2.37 and 2.38, which illustrate arrangements to test a 3 0 m A RCD within a caravan, w h e n the caravan is supplied f r o m a 3 0 m A RCD-protected socket-outlet at t h e caravan site pitch, or in a workshop environment. 100 G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology 2 ▼ Figure 2 . 3 7 Example of upstream/downstream test for an RCD or RCBO in a caravan (2-lead test) caravan inlet -pitch outlet caravan connecting lead pgSBs downstream line connection from socket-outlet in caravan, via shrouded test Y-splitter \ Upstream neutral connection from trailing socket-outlet, via shrouded y test plug / wander-lead Plug BS EN 60309-2 plug to BS 13632 trailing socket outlet converter 2Q3ms 30mA Check with test instrument manufacturer that the instrument is suitable for the upstream/downstream test Figure 2 . 3 8 Example of upstream/downstream test for an RCD or RCBO in a caravan (3-lead test) Y-splitter pitch outlet caravan inlet caravan connecting lead |?BBB|B|B! downstream line connection from socket-outlet i n caravan, via shrouded test wander-lead plug Upstream neutral — connection from trailing socket-outlet, via shrouded test plug / BS EN 60309-2 plug to BS 13632 trailing socket outlet converter 30.3 ms 30mA Check with test instrument manufacturer that the instrument is suitable for the upstream/downstream test Guidance N o t e 3: Inspection & Testing © The Institution of Engineering and Technology 101 2 Results of RCD tests 643.7 The maximum disconnection t i m e for a residual test current of l An should not exceed 643.8 t h e relevant non-time- delayed values shown in Table 2.17. The maximum disconnection t i m e for a residual test current of | An for the AC test is recorded in the Schedule of Test Results. Integral test device 643.10 An integral test device is incorporated i n each RCD. This device enables t h e functioning of t h e mechanical parts of the RCD to b e verified by pressing t h e button marked T or 'Test 1. Operation of the integral test device does not provide a means of checking: (a) the continuity of the earthing conductor o r the associated cpcs; (b) any earth electrode or other means of earthing; (c) any other part of the associated installation earthing; or (d) the sensitivity of t h e device. 514.12.2 The RCDtest button will only operate the RCD if it is energized. B S 7 6 7 1 recommends that the test button is pressed at least every 6 months. 2.6.19 Other functional 643.10 testing Other equipment, including switchgear, controls and interlocks, should also b e functionally tested - that is, operated to confirm that they work and are properly installed, mounted a n d adjusted. The settings o n all adjustable relays and controls, etc. should b e checked to see that they align with the designer’s proposed requirements. RCD test buttons should b e operated t o see that the RCD trips. AFDDs have b e e n introduced in t h e 18th Edition of the IET Wiring Regulations (532.6). There are two general types: those with a test button and those with an automatic test facility. Functional testing can only b e carried out by pressing the test button; there is n o means of functionally testing the t y p e without a test button. Circuit-breakers should n o t b e used as lighting switches o n a regular basis (as in some warehouses), unless they are approved by t h e manufacturers for such use. 2.6.20 Verification of voltage drop Verification of voltage drop is not normally required during initial verification. It is usually sufficient to check that voltage drop calculations have been undertaken and that the design voltage drops are within the limits required in BS7671. Where it may b e necessary to verify that voltage drop does not exceed t h e limits stated Sect 525 In the relevant product standards of installed equipment, B S 7 6 7 1 provides guidance to d o so. Where no such limits are stated, voltage drop should be such that it does not impair t h e proper a n d safe functioning of installed equipment. Voltage drop problems are quite rare, but the inspector should b e aware that long runs of circuit conductors and/or high currents can sometimes cause voltage drop problems. 102 G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology 2 Accurate measurement of voltage drop within an installation is not practical, as this would m e a n measuring the instantaneous voltage at both the origin and at t h e point of interest simultaneously, together with the instantaneous load current. An indication of voltage drop can b e obtained to ensure that it is not excessive for t h e proper functioning of the equipment by simple voltage measurement at the equipment terminals with t h e installation fully loaded. Voltage drop may b e determined by measurement of the combined live conductor resistance and by calculation using this value and the full load current of t h e equipment, with compensation for conductor temperature difference for measured and operating conductor values. This will determine voltage drop within the circuit, which can then b e used to verify compliance. Table 4Ab Appendix 4 of BS 7 6 7 1 gives maximum values of voltage drop for lighting and for other uses, depending u p o n whether an installation is supplied directly from a public LV distribution network o r f r o m a private LV supply. The voltage drop for general purposes in Appendix 4 exceed the requirements of s o m e product standards. For example, BSEN 61851-1:2011 for electric vehicle charging equipment requires charging points t o operate within a utilization voltage range of Uo ± 10 7o, which therefore requires a maximum voltage drop of 4 7o in a consumer's installation supplied in accordance with t h e ESQCR. It should b e remembered that voltage drop may exceed t h e values stated in Appendix 4 in situations such as motor starting periods and where equipment has a high inrush current, where such events remain within the limits specified in the relevant product standard or reasonable recommendation by a manufacturer. 2.6.21 Verification of protection o f low voltage (LV) installations against temporary overvoltages due to faults in the high voltage (HV) or LV system Sect 442 The protection referred to in this section of the Guidance Note is the subject of Section 4 4 2 of BS7671. F o r m o r e information, see Guidance Note 1. 442.2.1 Temporary overvoltages due to a n HV system fault 442.2.2 Regulations 442.2.1 and 442.2.2 give t h e requirements concerning the magnitude and duration of temporary overvoltages occurring due to a fault in t h e HV system (typically, 11 kV) supplying t h e substation f r o m which t h e LV installation is supplied. 442.2.3 Regulation 442.2.3 points o u t that t h e requirements of Regulations 442.2.1 and 442.2.2 are deemed to be met if the LV installation is supplied f r o m a system for distribution of electricity t o the public. This assumes that the public electricity supply distribution network is appropriately designed and constructed, as is the case in Great Britain. Where this is the case, there is n o need for the inspector to check compliance with Regulations 442.2.1 and 442.2.2. 442.2.1 Where the LV installation is supplied from a privately owned substation, the design 442.2.2 responsibility for complying with Regulations 442.2.1 and 442.2.2 rests with the designer(s) of t h e substation and the associated LV distribution network up to the incoming terminals of the LV installation. The inspector will need to b e in possession of sufficient information provided by this party (or parties) about the intended means of compliance, to enable him or her to verify, so far as is reasonably practicable, that these means have been properly put into effect. Matters to b e checked by the inspector include: Guidance N o t e 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology 103 2 (a) that the HV and LV earthing arrangements of the substation have b e e n correctly installed and that their resistances to Earth meet the designer's requirements; (b) that t h e HV earthing and LV arrangements are interconnected or, where appropriate, separated, according to t h e designer's requirements; (c) that any global earthing system or additional connections with Earth in the LV network that are relied o n for safety are in existence and properly installed, and that the resistance of connections with requirements; and Earth meets the designer's (d) that t h e rated currents and settings of protective devices are as intended by the designer. Temporary overvoltages due t o an LV system fault 442.3 Regulations 442.3, 442.4 and 442.5 require consideration to b e given to t h e stress voltages that would occur in an installation in t h e event of loss of the neutral conductor In a TN or TT system, a n earth fault in an IT system with distributed neutral, or a short-circuit between a line conductor and a neutral conductor. In practice, there is usually little that an installation d o to meet the requirements designer and constructor can of these regulations beyond selecting and installing equipment with appropriate insulation voltage ratings, such as 600/1,000 V cables for an installation of nominal voltage of 2 3 0 / 4 0 0 V. The inspector should check that this has been done. 2.6.22 Verification of protection against overvoltages origin or due t o switching Section GN1 Table 4 4 : of atmospheric The protection referred to in this section of t h e Guidance Note is the subject of Section 443 of BS 7671. Formore information, see Guidance Note 1. Irrespective of whether the electrical designer has chosen to specify SPDs, t h e inspector should check that all electrical equipment of the installation has been so selected and installed that, according to its product standards, it provides at least the applicable value of rated impulse voltage referred to in Table 443.2 of BS 7671. The values of rated impulse withstand voltage in that table are given according to the Category (I, II, III or IV) into which the equipment falls and to t h e nominal voltage of the installation. Table 4 4 3 . 2 of BS 7671 gives examples of equipment falling into each of the categories. Section 534 Where protection against overvoltages by the use of SPDs has been specified by the designer, the inspector should check that these have been selected and installed in accordance with t h e designer's requirements or otherwise in accordance with Section 5 3 4 of BS7671. The inspector needs t o verify that SPDs have n o t become expired or defective by ensuring that indicator lights are correctly illuminated or that the coloured flag or flags o n the devices indicate that they are serviceable. Remote status indicating facilities such as connection to an audible alarm may also have been provided and this should also b e checked for correct operation. 104 G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology 2 2.6.23 Verification of measures against electromagnetic disturbances Sect 444 GN1 I n s p e c t o r s should f a m i l i a r i z e themselves with the section o n avoidance a n d reduction o f e l e c t r o m a g n e t i c d i s t u r b a n c e s i n B S 7 6 7 1 ( S e c t i o n 4 4 4 o f B S 7671). For m o r e i n f o r m a t i o n , s e e G u i d a n c e N o t e 1. It s h o u l d b e noted t h a t compliance E l e c t r o m a g n e t i c Compatibility with E M C requirements Regulations 2016 in B S 7671 is something that a n d in the i s not usually v e r i f i e d by t a k i n g site m e a s u r e m e n t s . For m o s t installations, E M C i s d e m o n s t r a t e d by a c o m b i n a t i o n o f t h e i n s t a l l a t i o n design a p p r o a c h ( i n c l u d i n g , w h e r e a p p l i c a b l e , d e t a i l s of E M C mitigation measures), i n f o r m a t i o n that would p r o d u c t conformity, need to b e retained a n d good i n s t a l l a t i o n p r a c t i c e s . The f o r the 'design f i l e ' (which needs to be r e t a i n e d by t h e ' r e s p o n s i b l e p e r s o n ’ , w h i c h , u n d e r t h e 2 0 1 6 r e g u l a t i o n s i s t h e installer) might include: (a) f o r a s m a l l o r s i m p l e i n s t a l l a t i o n consisting the EMC Regulations solely of equipment complying with 2016: (i) product manuals and (ii) notes on what was done installation instructions, with evidence of the regulatory (UKCA o r UKNI) marking of products; a n d (b) f o r a large o r complex where instructions installation, could not be followed (if relevant); o r where t h e above d o e s not a p p l y : (i) m a n u f a c t u r e r / i m p o r t e r d e c l a r a t i o n s of conformity, o r statements (ii) cable and product manufacturer's installation instructions and specifications; and (iii) design of EMC s t a n d a r d s c o m p l i a n c e , etc; • drawings design ► a n d r e p o r t s demonstrating: conformity to relevant installation standards, which might include: B S 7671; ► B S E N 50310; ► B S E N 50174 ► B S IEC 6 1 0 0 0 - 5 - 2 ; a n d ► o t h e r s (for series; s y s t e m s such a s emergency lighting, fire alarms a n d s o o n t h a t m a y h a v e a d d i t i o n a l E M C r e q u i r e m e n t s a s p a r t of t h e i r system standards); • • evidence that manufacturer instructions measures w h e r e t h e y c o u l d not be; have been followed, or mitigation product selection relevant for the E M environment (see P D IEC/TR 61000-2► for larger installations/multi-use ► a s t a t e m e n t o f mitigations outside 5): premises, E M e n v i r o n m e n t zoning; a n d a n d r e s i d u a l risk f o r e q u i p m e n t i n s t a l l e d the target E M environment. S e c t i o n 4 4 4 s p e c i f i e s a d d i t i o n a l m i t i g a t i n g m e t h o d s f o r E M C a p p l i e d t o t h e design installation of cables and equipment. Many of these mitigating methods concern and the routing of cables and their distance from other cables, a s well as providing equipotential bonding. Thus, v e r i f i c a t i o n of E M C a n d c o m p l i a n c e with S e c t i o n 4 4 4 is as follows: (a) c h e c k i n g t h e E M C d e s i g n h a s b e e n f o l l o w e d w i t h r e s p e c t to c a b l e routing, s e p a r a t i o n distances, (b) inspection of cable use of suitable sheath and containment screen n e c e s s a r y , c o n t i n u i t y c h e c k i n g of t h e s e items; a n d enclosures, terminations and, etc.; if considered and (c) c a r r y i n g o u t c o n t i n u i t y c h e c k s o f a n y a d d i t i o n a l m i t i g a t i n g b o n d i n g n e t w o r k p r o v i d e d (for e x a m p l e , a l o c a l m e s h network). Guidance N o t e 3: I n s p e c t i o n & Testing © The Institution of Engineering and Technology 105 2 BS IEC 61000-5-2 contains guidance o n good installation practices for inspection items, to achieve EMC. BS EN 50310 contains requirements for electrical tests to b e carried out for bonding networks in buildings containing ICT systems. While there are n o specific requirements in BS 7671 for either installers or inspectors to carry out electric field or magnetic field strength measurements, designs for certain installations may require such measurements to b e made, based o n assessments carried out at t h e design stage. chapter 82 2.6.24 Prosumer's electrical installations (PEIs) A PEI is one in which electrical energy is both produced and consumed. The simplest t y p e of PEI is an installation with a solar PV system. This section outlines particular considerations installation. Further information, for initial testing with this t y p e of including guidance on initial verification, can be found in the IET Code of Practice for Electrical Energy Storage Systems and the IET Code of Practice for Grid-Connected Note: Solar Photovoltaic Systems. In PEIs, the term power conversion equipment (PCE) is used to describe both inverters and AC-DC converters, as a single device, such as a combined inverter charger for a battery storage system, may perform both functions. M u l t i p l e s u p p l i e s a n d safe i s o l a t i o n PEIsusually have m o r e than one source of supply. Isolation of the electrical installation for safe working o n certain parts of the installation will involve m o r e than one point of isolation. These should b e appropriately labelled in accordance with Regulation 514.15.1. It is essential to follow a rigorous approach to the identification of the correct points of isolation for t h e part of the system that is being worked on, along with the use of means of securing the points of isolation in t h e OFF position. Supply characteristics may change between installation operating modes PEIshave operating modes as shown in Table 2.18. When t h e installation is operating in island mode, the supply characteristics are likely to b e different, as the installation is supplied by local generation (in t h e f o r m of power converters such as inverters) rather than the public distribution network. As a consequence of moving from connected mode to island mode, for example: (a) The earthing arrangement may change, for example f r o m TN-C-S to TN-S, or f r o m TT to TN-S. A consumer's earth electrode may b e required. (b) The prospective fault current is likely to b e far less, and the effective greater, than in connected modes of operation. EFLI In smaller installations, there may be insufficient fault current to operate overcurrent protective RCDs or protection built into electronic converters must b e used for protection devices, a n d against electric shock. Manufacturer’s instructions should b e consulted to check whether external protective devices are required. 106 G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology 2 ▼ Table 2. 18 Operating modes for PEIs Mode Definition in Part 2 of BS 7671 ______ _ _ Connected mode Operating mode which needs connection to the public network (direct feeding mode and reverse feeding mode). Direct feeding mode Operating mode in which the public network supplies the (PEI) (see note 1). Reverse feeding mode Operating mode in which the PEI supplies the public network (see note 2). Island mode Operating mode in which the PEIis disconnected from the public distribution network, but remains energized (see note 3). Notes: 1 Local storage units can supply current-using equipment or be charged by local power supplies and/or the public distribution network. 2 Local storage units can supply current-using equipment and/or the public distribution network or be charged by local power supplies. 3 An island mode can be either the result of an automatic process or the result of a deliberate action. 643,73.1 Note 1 EFLI a n d p r o s p e c t i v e f a u l t c u r r e n t m e a s u r e m e n t i n PEIs 826.7 Grid-connected inverters operating in parallel with the public supply track the rise and fall of the supply voltage. Consequently, measurement when a prospective fault current o r EFLI is taken in a PEI in connected modes of operation, the contribution of the inverter may b e masked by this behaviour. In island mode, inverters can appear to b e a constant current source, up to t h e value of their in-built current limit. When a prospective fault current or EFLI measurement is taken in a PEI in island mode, especially using a 'no trip' or 'low current' setting usually used to avoid tripping RCDs, the prospective fault current reading may b e much higher than t h e actual value, and the EFLI lower. The IET Code of Practice for Electrical Energy Storage Systems advises: (a) external earth fault loop impedance and prospective fault current measurements are carried out at the origin, with all PCE isolated. (b) earth fault loop impedance and prospective fault current measurements for the remainder of the installation are not taken unless all the inverters in the system are isolated. In order to provide verification for automatic disconnection of supply, t h e following tests can b e used: (i) for connected mode: the verification of earth fault loop impedance (Zdb and Z$) is based o n the external earth fault loop impedance, Ze, plus measured (R1+R2) values. Prospective fault current should b e the measured prospective fault current plus the sum of t h e current limit of all connected m o d e inverters. (ii) for island mode: (Zdb and Zs) manufacturer's if applicable, verification of earth fault loop impedance is determined using measured (R1+R2) values, plus the information regarding the value of Z e to b e assumed for the EESSor the relevant PCE within it. Prospective fault current should b e t h e sum of the current limit of all connected-mode inverters. Note: The prospective fault current measurement at the origin is not necessary if it can be determined by other means (see Section 2.6.16). Guidance Note 3: Inspection & Testing © The Institution of Engineering and Technology 107 2 Functional testing and system documentation Functional testing of the relevant management a n d control devices c a n b e complex. Particularly f o r dwellings, the level of documentation b e extensive, a n d it i s important maintenance of the installation in future. Code of Practice for Electrical for Grid-Connected 108 G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology Solar a n d commissioning to check that suitable information Further information Energy Storage Photovoltaic Systems. records will is provided for safe c a n b e found in the IET Systems a n d the IET Code of Practice Periodic inspection and testing 3.1 651.1 3 Purpose of periodic inspection and testing The purpose of periodic inspection and testing is to provide an engineering view o n whether or n o t an installation is in a satisfactory condition where it can continue to b e used safely. A detailed visual examination of the installation is required, together with appropriate tests. The tests are mainly to confirm that the disconnection times stated in Chapter 41 of BS 7 6 7 1 are met. The periodic inspection and testing is carried out, so far as is reasonably practicable, for: (a) the safety of persons and livestock against the effects of electric shock and bums; (b) protection against damage to property by fire and heat arising f r o m a n installation defect; (c) confirmation that t h e installation is not damaged or deteriorated so as to impair safety; and (d) the identification of installation defects and departures f r o m the requirements of B S 7 6 7 1 that may give rise to danger. For an installation under effective supervision in normal use, periodic inspection and testing may b e replaced by a n adequate regime of continuous monitoring and maintenance of the installation and all its constituent equipment by skilled persons competent in such work. It is important in such a regime that maintenance records, with references to inspection and testing, are recorded and stored. Such records should b e available for scrutiny and n e e d not b e in the standard EICRformat. 3.2 Necessity for periodic inspection and testing Periodic inspection and testing is necessary because all electrical installations deteriorate, due to a number of factors, such as damage, wear, tear, corrosion, excessive electrical loading, ageing and environmental influences. Consequently: (a) legislation requires that electrical installations are maintained in a safe condition, and this lends itself to periodic inspection and testing (see also Tables3.1 and 3.2); (b) licensing authorities, public bodies, insurance companies, mortgage lenders and others may require periodic inspection and testing of electrical installations, as is, for example, the case for HMOs (see Tables 3.1 a n d 3.2); and Guidance N o t e 3: Inspection & Testing © The Institution of Engineeringand Technology 109 3 (c) additionally, periodic inspection and testing should b e considered in t h e following circumstances: (i) to assess compliance (ii) with BS 7671; o n a change of occupancy of the premises (especially for rented domestic accommodation); (iii) (iv) (v) (vi) o n a change of use of t h e premises; after additions or alterations to the original installation; where there is a significant change (increase) in the electrical loading of t h e installation; and where there is reason to believe that damage may have been caused to t h e installation, as might b e the case, for example, after flooding. Reference to legislation and other documents requirements is made below. It is vital that these are ascertained before undertaking periodic inspection a n d testing. 3.3 Electricity at Work Regulations (EAWR) 3.3.1 The need for appropriate inspection and testing Regulation 4(2) of t h e EAWR requires that: As may b e necessary to prevent danger, all systems shall b e maintained prevent, so far as is reasonably practicable, such danger. so as to HSR25, which provides guidance o n these regulations, advises that this regulation is concerned with t h e need for maintenance to ensure the safety of the system, rather than with the activity of carrying out t h e maintenance in a safe manner, which is required by Regulation 4(3). The obligation to maintain a system arises if danger would otherwise result. There is n o specific requirement to carry out a maintenance activity as such; what is required is that the system is kept in a safe condition. The frequency and nature of the maintenance must be such as to prevent danger so far as is reasonably practicable. There have been many debates as to what 'reasonably practicable' means. In the event of an accident, i t would b e for a court to decide the issues. In essence, however, the reduction of risk to as low as is reasonably practicable means weighing that risk against the sacrifice needed t o further reduce it. The decision should b e weighted in favour of health and safety, because the presumption implement is that t h e duty holder should t h e risk reduction measure. To avoid having to make this sacrifice, the duty holder must b e able to show that it would b e grossly disproportionate to the benefits of risk reduction that would b e achieved. Thus the process is not one of balancing t h e costs and benefits of measures, b u t rather, of adopting measures except where they are ruled o u t because they involve grossly disproportionate sacrifices. Ultimately, under t h e EAWRit is the duty holder who is responsible for t h e safety of an electrical installation at work. This leads to the question as to w h o the duty holder is. In Section 4 of the Health a n d Safety at Work etc. Act 1974 (HSWA), reference is m a d e to a person "who has, t o any extent, control of premises". This may b e an identified person with that specific responsibility within an organization, such as a landlord, or perhaps a manager or supervisor. Regular inspection of equipment, including the electrical installation, is a n essential part of any preventative maintenance programme. This regular inspection may b e carried out as necessary without dismantling (or with partial dismantling, as required) a n d supplemented 110 G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology by appropriate testing. 3 T h e r e i s n o s p e c i f i c requirement requires dismantling, of c a b l e s or components, However, while should a r e j u s t i f i e d . Dismantling, t h a t it is impractical b e b a l a n c e d against the p o s s i b l e consequences w o u l d ensue f r o m inspection, a m a t t e r of a little inspection 3.3.2 to dismantle a n item risks c o u l d b e i n t r o d u c e d f r o m u n s a t i s f a c t o r y reassembly, f a i l i n g to i n s p e c t i n s i d e switchgear a floor, t h e decision the risks a s s o c i a t e d w i t h a n d particularly d i s c o n n e c t i o n i n t r o d u c e s a risk of u n s a t i s f a c t o r y reassembly. it is e a s y t o decide or that o n e v e r y i n s p e c t i o n . Where testing the i n s p e c t o r s h o u l d c o n s i d e r whether d i s m a n t l i n g a n d reassembling equipment, to test t h e installation of not d o i n g so, f o r example, f o r signs of overheating. f o r instance, Where Where in irreparable d a m a g e i n l i f t i n g f l o o r t i l e s to inspect not to i n s p e c t w o u l d b e justified. extra w o r k o r inconvenience, of this c a b l e s under the decision is simply f o r e x a m p l e , i n c a r r y i n g o u t a visual of c a b l e s in a d o m e s t i c d w e l l i n g l o f t void, it c o u l d b e d i f f i c u l t to justify. Safety in inspection and testing Safety issues i n general are outlined testing, the inspector risk assessments, i n S e c t i o n 1. When carryingout periodic inspection is advised to include the following a n d test a n d inspection procedures considerations and when developing for a particular installation: (a) safety information in existing information a n d p r e v i o u s records for the installation; (b) a n y e x i s t i n g risk a s s e s s m e n t s o r s a f e t y f i l e s held by t h e p e r s o n ordering the work (for (Design example, the h e a l t h a n d safety a n d Management) Regulations file 2015 r e q u i r e d by the Construction (CDM)); (c) information f r o m p r e - i n s p e c t i o n surveys; a n d (d) the age of the installation, a n d probable p e r i o d since the last inspection a n d test. I n s p e c t i o n a n d testing and those c a r r y i n g out discover should u n e x p e c t e d i s s u e s t h a t require the inspections 3.3.3 of e x i s t i n g i n s t a l l a t i o n s m a y involve i n s p e c t i o n a n d testing unknowns, r e m a i n a l e r t t o the f a c t that they may d y n a m i c risk a s s e s s m e n t s to b e c o n d u c t e d a s a n d tests progress. Diverted neutral currents Installations i n w h i c h P M E conditions by o p e n - c i r c u i t protective a p p l y c a n c a r r y diverted e a r t h a n d neutral neutral (PEN) c o n d u c t o r faults. currents caused Diverted neutral c u r r e n t s m a y also b e e x p e r i e n c e d i n i n s t a l l a t i o n s w h i c h s h a r e e x t r a n e o u s - c o n d u c t i v e p a r t s , such as c o n d u c t i v e gas or w a t e r s e r v i c e pipes, i n s t a l l a t i o n s in w h i c h P M E conditions o r s t r u c t u r a l steelwork, with apply. As a safety p r e c a u t i o n f o r t h o s e c a r r y i n g out inspection a n d testing, these types of installations a n d testing commences, to determine should to i f diverted neutral b e checked currents before inspection a r e present. A p p e n d i x E d e s c r i b e s a s a f e t y check p r o c e d u r e to i d e n t i f y d i v e r t e d n e u t r a l currents. 3.4 341.1 Design W h e n c a r r y i n g o u t the design of a n installation, a n d p a r t i c u l a r l y when e q u i p m e n t , the designer s h o u l d t a k e into account b e r e a s o n a b l y expected, i n c l u d i n g t h e f r e q u e n c y of routine between subsequent inspections (supplemented, the quality s p e c i f y i n g the of t h e m a i n t e n a n c e t o checks and t h e p e r i o d a s n e c e s s a r y , by testing). Guidance Note 3: Inspection & Testing © The Institution of Engineering and Technology 111 3 Information on the requirements for routine checks and inspections should b e provided in accordance with Section 6 of t h e HSWA 1974 and as required by t h e CDM Regulations. Dutyholders and users of premises should seek this information as the basis on which to make their own assessments. The HSE advises in HSR25 that practical experience of an installation's use may indicate the need for an adjustment to the frequency of checks and inspections. This is a matter of judgement for the dutyholder. BS 7 6 7 1 requires t h e designer of a n electrical installation to recommend t h e interval to t h e first periodic inspection and insert the date of that recommendation o n t h e E1C. However, as stated in Regulation 341 .1, wider consideration should b e given to the expected maintainability of a n installation, and t h e client, and perhaps t h e installer, should also b e involved, with t h e designer taking t h e advice of other relevant persons into account. After the first, and further periodic inspections a n d tests, the inspector, in conjunction with t h e client, taking into account the test results and the observations found, will then advise on t h e period until the next inspection. Whatever inspection and testing periods are decided u p o n must b e justifiable, as they may b e requested to b e justified in t h e case of an accident or similar. It would not b e unreasonable for the inspector to write supporting reasons for the period onto the inspection and test report. 3.5 Routine checks Electrical installations should n o t b e left without any attention for t h e periods of years that are normally allowed between formal inspections. In domestic premises, it is presumed that the occupier will soon notice any breakages or excessive wear and arrange for precautions t o b e taken and repairs to b e carried out. Commercial and industrial installations come under the EAWR. For these installations, formal arrangements are required for maintenance and interim routine checks (as well as for periodic inspections); there should also b e the facility to receive wear-and-tear reports f r o m users of the premises. The frequency and t y p e of these routine checks will depend entirely u p o n the nature of the premises and should b e set by the electrical dutyholder. Routine checks should include t h e items listed in Table 3.1. Table 3.2 ( i n Section 3.7) provides guidance o n the frequency for initial interval between inspections, which m a y need to b e increased as an installation ages. 112 G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology 3 ▼ Table 3.1 Routine checks Activity Check Defects reports All reported defects have b e e n rectified Inspection Look for: (a) (b) (c) (d) (e) breakages wear/deterioration signs of overheating missing parts (covers, screws) loose fixings Confirm: (a) (b) (c) Operation switchgear accessible (not obstructed) doors of enclosures secure adequate labelling in place Operate: (a) (b) (c) switchgear (where reasonable) e q u i p m e n t - switch o n and off including RCDs (using test button) Note that routine checks need not b e carried out by an electrically skilled person, but should b e undertaken by somebody who is able to safely use t h e installation and recognize defects. There is a general ongoing requirement to manage health and safety at work, and electrical safety is just one area of this. To ensure that regular routine checks are m a d e o n the electrical installation, it may b e advantageous in larger premises to combine these with other regular checks, such as emergency lighting a n d fire alarm inspections, general fire safety inspections, emergency exit route inspections, and so on, o n security patrols. A system to record obvious defects should b e implemented and a simple f o r m is all that is needed. 3.6 Required information It is essential that t h e inspector knows and agrees with the client the extent of t h e installation to b e inspected and any criteria regarding t h e limit of t h e inspection. This should b e recorded. 514.9 Enquiries should b e m a d e to t h e person responsible for the electrical installation with regard to t h e provision of diagrams, design criteria, type of electricity supply (and any alternative supply) and earthing arrangements. Where they exist, diagrams, charts or tables should b e m a d e available to indicate t h e type and composition of circuits and t h e identification of protective devices for shock protection, isolation and switching, with a description of the method used for fault protection. Unfortunately, most such records are not kept up-to-date w i t h modifications made to the installation, and an inspector will initially need to verify the accuracy of any such information provided. Where there are n o records, in all but t h e simplest domestic installation, a n inspector may first need to spend t i m e tracing installation systems and circuits and producing basic drawings and schedules, before starting any inspection and testing work. Guidance N o t e 3 : Inspection & Testing © The Institution of Engineering and Technology 113 3 3.7 Frequency of periodic inspections 644.4 The t i m e intervals between t h e recommended dates of periodic inspections and 653.4 testing require careful consideration. The date for t h e first periodic inspection and test is required to b e considered and recommended by the installation designer, based o n their design philosophy and maintenance advice f r o m other parties (Regulation 341.1). The period for each subsequent periodic inspection is required to b e considered and recommended by the inspector as part of carrying out a periodic inspection a n d test. Regulations 644.4 and 653.4 requires the reason for selecting the interval between the current inspection and the next periodic inspection to b e recorded on the EIC, MEIWC o r EICR as relevant. 652.1 In advising the person ordering t h e work about t h e t i m e interval for t h e period for t h e next recommended periodic inspection and test, t h e inspector is required to take into consideration t h e individual characteristics of t h e type of installation and equipment, its condition, use and operation, any damage and deterioration, any known maintenance and t h e external influences to which it is subjected. The results and recommendations of any previous periodic inspection reports should also b e considered. The suggested initial frequencies for inspection and testing given in Table 3.2 are recommendations and not legal requirements. The period between subsequent inspections may b e reduced, o r occasionally increased. It is the responsibility of the person responsible for the electrical installation to determine when the next periodic inspection is undertaken. In making this decision, they should take appropriate advice f r o m specialists, where necessary, t o assessthe conditions affecting t h e installation that might lead to defects, potential damage and/or deterioration that would affect safety. Such advice m a y include routine checks, manufacturers' o r engineers' advice and guidance, and periodic inspection and testing reports, with this information assisting the person responsible for t h e electrical installation in determining t h e maintenance plan for t h e installation. Over time, and with practical maintenance experience, it may b e possible to extend periodic inspection and testing intervals if t h e results of routine checks, inspections or tests show that few faults are found and that t h e installation is not subject to excessive deterioration. However, if faults are common, it may b e necessary t o reduce intervals or take other action to improve maintenance and reduce risk. Routine checks and periodic inspection and testing by an inspector are only a part of the requirement for maintenance; t h e person responsible for the electrical installation has a continuing ongoing responsibility for the safety of an installation. Note: Persons responsible for electrical installations are reminded of the requirements of Regulation 4(2) of the EAWR. Undertaking routine inspection and testing of their installationswill assist in meeting this duty. The inspector, being a skilled person, should apply sound engineering judgement and experience w h e n deciding u p o n t h e intervals between inspecting and testing an installation based u p o n t h e criteria in Regulation 6 5 2 of BS 7671. It must also b e noted that in the event of an accident or dangerous occurrence, t h e inspector may b e required to justify their decision. In t h e case of domestic and commercial premises, a change i n occupancy of the premises may necessitate additional inspection and testing. 114 Guidance N o t e 3: Inspection & Testing © The Institution of Engineeringand Technology 3 651.1 The formal periodic inspection and testing should b e carried out in accordance with Regulation 642, supplemented by tests as detailed in Regulation 643. This requires an inspection comprising a detailed examination of the installation, carried o u t without dismantling, or with partial dismantling as required, together with the appropriate tests of Regulation 643 as required to comply with Regulation 651.2. 652.2 Where there is an effective management system in place for inspection and preventative maintenance of the installation (for example, where there are competent permanent on-site maintenance staff), periodic inspection and testing can b e replaced by an adequate regime of continuous monitoring and maintenance of the installation and its constituent equipment. However, appropriate records must b e maintained o n site to show that a n inspection and preventative maintenance plan is in place and is being adhered to. Although periodic inspection a n d testing is primarily aimed at keeping an electrical installation in a safe state, it can also have other financial benefits, such as identifying possible upcoming equipment failures that could interrupt production, providing advice o n energy saving, a n d reducing running costs. It must also b e noted that while this Guidance Note is concerned with periodic inspection and testing for t h e maintenance of safety of general electrical installations, there are other specialist parts of an electrical installation, such as plant controls, fire alarms and emergency lighting, that also require separate periodic inspection and testing by specialists for t h e maintenance of safety. ▼ Table 3.2 Recommended initial frequencies of inspection of electrical installations Notes Routine check (see Section 3.5) Maximum initial period between inspections and testing (Note 8) Domestic accommodation: general — Change of occupancy/10 years Domestic accommodation: rented houses a n d flats 1 year 5 years 1,2, 10, 12 Residential accommodation (HMOs): halls of residence, nurses' accommodation, etc. 1 year 5 years 1 , 2 , 10, 11 Commercial 1 year 5 years 1 , 2 , 3, 4 6 months 5 years 1,2, 6 Industrial 1 year 3 years 1,2 Offices 1 year 5 years 1,2 Shops 1 year 5 years 1,2 Laboratories 1 year 5 years 1,2 Type of installation General installation Educational establishments Medical locations (see Appendix 11 t o the IET Guide to Electrical Installations Medical Locations) in Hospitals a n d medical clinics: Goup 0 1 year 5 years 1,2 Hospitals a n d medical clinics: Group 1 a n d Group 2 6 months 1 year 9 Guidance Note 3 : Inspection & Testing ® The Institution of Engineering and Technology 115 3 Routine check (see Section 3.5) Maximum initial period between inspections and testing (Note 8) Notes Cinemas 1 year 1 -3 years 2, 6 Church installations 1 year 5 years 2 Leisure complexes (excluding swimming pools) 1 year 3 years 1,2, 6 Places of public entertainment 1 year 3 years 1,2, 6 Restaurants, hotels a n d short-term lets 1 year 5 years 1,2, 6 Theatres 1 year 3 years 2, 6 Public houses 1 year 5 years 1,2, 6 Village halls/community centres 1 year 5 years 1 ,2 Type of installation Buildings open to the public Special and specific installations Agricultural and horticultural Caravans Caravan parks Highway power supplies Marinas Mobile a n d transportable units according to Section 717 of BS 7671 (a) Pre-delivery (b) On-site/in-use (see above for medical locations) 1 year 3 years 1,2 1 year 3 years 7, 12 6 months 1 year 1 , 2 , 6 , 12 as convenient 6 - 8 years 4 months 1 year 1,2 13 Prior to delivery, or 1 year if in storage Prior to delivery, or 1 year if i n storage On connection at site, then dependent o n On connection use at site, then dependent use on Fish farms 4 months 1 year 1,2 Swimming pools 4 months 1 year 1,2,6 Emergency lighting daily/monthly 3 years 2, 3, 4 Fire alarms daily/weekly 1 year 2, 4, 5 Launderettes monthly 1 year 1,2, 6 Petrol filling stations 1 year 1 year 1,2, 6 3 months 3 months 1,2 Construction site installations Notes: 1 2 3 4 5 6 7 116 Particular care m u s t b e taken t o comply w i t h t h e Electricity Safety, Quality a n d Continuity Regulations (ESQCR) (as amended). Regulation 4 of t h e E A W R a n d HSR25. See BS 5266-1 : 2 0 1 6 Emergency lighting. Code o f practice for the emergency lighting of premises a n d t h e IET Electrician's Guide to Emergency Lighting. Other intervals are r e c o m m e n d e d f o r t e s t i n g operation of batteries and generators. See BS 5839-1 : 2017 Fire detection and fire alarm systems for buildings. Code o f practice for design, installation, commissioning and maintenance of systems in non-domestic premises and the IET Electrician's Guide to Fire Detection and Fire Alarm Systems. Local Authority conditions of licence. There is specific legislation listed i n BS 7 6 7 1 relating to cinemas a n d theatres. It is r e c o m m e n d e d that a caravan is inspected a n d tested every three years, w i t h this period reduced t o every year if it is used frequently (see Regulation 721.514.1 and Fig 721 (Instructions for electricity supply)). Guidance Note 3: Inspection & Testing © The Institution of Engineering and Technology 3 8 The person carrying out subsequent inspections may recommend that the interval between future inspections be increased or decreased as a result of the findings of their inspection. 9 Medical locations shall have their isolating transformer equipment inspected and tested for functionality, as well as alarms, etc. Every third year the output leakage current of the IT isolating equipment shall be measured. Measurements to verify that the resistance of the supplementary equipotential bonding is within the limits stipulated by Regulation 710.415.2.2 should be carried out annually. In addition, in Group 2 Medical locations complete functional tests of the insulation monitoring devices (IMDs) associated with the medical IT system including insulation failure, transformer high temperature, overload, discontinuity and the audible/visual alarms linked to them should be conducted annually. 10 The Landlord and Tenant Act 1985 requires that properties under the Act have their services maintained. Periodic inspection and testing is the lET's recognized method of demonstrating this. 1H The Management of Houses in Multiple Occupation (England) Regulations and the Management of Houses in Multiple Occupation (Wales) Regulations. 12 The Electrical Safety Standards in the Private Rented Sector (England) Regulations 2020 requires landlords in the private rented sector in England to have a rental property inspected and tested every five years and supply a copy of the report to the tenant within 28 days. Any remedial works or further investigation must be completed within 2 8 days, and confirmation provided in writing to the tenant, and local authority if required, within 28 days of completion of this work. There are similar requirements in all devolved nations, and guidance is available on the relevant Government website. 13 Mobile and transportable units should be inspected and tested at least every 12 months. Mobile and transportable units that are connected to an independent source of electricity at site should be inspected and tested on connection. In use, mobile and transportable units should be at periods suitable for the environment in which it is being used, for example every three months in a construction site environment, up to a maximum of 12 months between inspection and testing. Any landlord (of an H M O or other occupancy) may b e considered to have duties under the EAWRdue to their responsibilities under Section 3 of t h e HSWA 1974 (relating, for example, to the c o m m o n areas of a set of flats). In Scotland, the private rented sector has legal requirements to maintain the electrical installation. Landlords are required by law to ensure that the electrical installation in a rented property is safe w h e n tenants m o v e in and is maintained in a safe condition throughout its duration and that an H M O has a periodic inspection carried o u t o n the property every five years. (The definition of a H M O is difficult, but it hinges o n whether the persons living i n the house are related - as in a large family residence - or completely separate, as in a block of flats.) 3.8 Requirements for periodic inspection and testing 3.8.1 Process: prior to carrying out inspection and testing Prior to carryingout t h e inspection, the inspector will need to meet with the client o r the client's representative to agree the scope a n d nature of t h e work required and the programme and to highlight likely items that require isolation. Consultation with t h e client or t h e client's representative prior to t h e periodic inspection and testing work being carried out is essential t o determine the access and any disruption to the normal work in the premises. The inspector will also n e e d to ascertain, and b e appraised of, particular health and safety requirements (as dangerous processes may b e being carried out), security and access and fire safety requirements, a n d to determine the degree of electrical disconnection that will b e acceptable. To assist with the planning of the detailed inspection and testing, any existing drawings, schedules and documentation of t h e installation should b e available; some initial Guidance Note 3: Inspection & Testing © The Institution of Engineering and Technology 117 3 validation of these will b e necessary. In addition, the extent of previous maintenance a n d routine tests, along with documentation including t h e original design a n d E I C , a n d certificates for any other electrical works that have b e e n carried out in the premises, if available, should b e provided to the inspector. For safety, it is necessary to carry out a visual inspection of t h e installation before testing or opening enclosures, removing covers, etc. So far as is reasonably practicable, t h e visual inspection must verify that the safety of persons, livestock and property is not endangered. 3.8.2 General procedure Note: The following advice is not applicable to domestic or simple installations, as the extent and method of inspection and testing is rudimentary in such installations compared with more complex installations. Although there are various approaches to carrying out inspection and testing, one suggested method is to first obtain an overview of the installation, ideally f r o m diagrams a n d charts, as well as from a simple 'walk-round' survey prior to starting the full inspection. This will enable the inspector to b e able to plan the inspection and to identify items that require isolation, etc. M o s t importantly, this initial survey will enable the inspector to set sample sizes, (see Section 3.8.3). 651.1 Where diagrams, charts or tables are not available, a degree of exploratory work may b e necessary so that inspection and testing can be carried out safely and effectively; this may include a survey to identify switchgear, controlgear and the circuits they control. Indeed, for m o r e involved installations without design information, such as, diagrams or charts, t h e client should b e advised that such diagrams require producing in order to plan and conduct the inspection and testing. Alternatively, where the inspector considers that it is safe to proceed, the inspection can commence, but may b e limited to visual inspection. The production of diagrams and charts can be called for on the EICR. 651.2 Note should b e m a d e of any k n o w n changes in environmental conditions or building structure, and of any additions or alterations. The inspector may need to consider whether such changes have affected t h e suitability of wiring systems and other equipment f o r t h e i r present load, location, and m e t h o d of installation. During t h e inspection, opportunity should b e taken to identify dangers that might arise during t h e testing. Any location and equipment for which safety precautions may b e necessary should b e noted and the appropriate steps taken. A thorough inspection should b e made of all electrical equipment that is not concealed, and should include the accessible internal condition of a sample of the equipment. The external condition should b e noted and, if damage is identified or if the degree of protection has been impaired, this should b e recorded o n t h e Schedule of Inspections appended to the Report. The inspection should include a check o n t h e condition of electrical equipment and material, taking into account any available manufacturer's information, with regard to the following: (a) safety; (b) age; (c) damage and defects; (d) corrosion and external influence®; 118 Guidance Note 3: Inspection & Testing © The Institution of Engineering and Technology 3 (e) overloading (f) (signs of); wear a n d tear a n d environment; (g) change i n u s e o f t h e l o c a t i o n i n w h i c h it i s i n s t a l l e d ; a n d (h) suitability f o r continued use. T h e a s s e s s m e n t o f c o n d i t i o n s h o u l d t a k e a c c o u n t o f k n o w n changes influencing a n d a f f e c t i n g e l e c t r i c a l safety, f o r example, plumbing i n conditions o r s t r u c t u r a l changes. W h e r e parts of a n electrical installation are excluded f r o m t h e s c o p e of a periodic inspection a n d test, they should b e identified in the 'Extent a n d limitations' section of t h e Report. Periodic inspection a n d testing should b e u n d e r t a k e n i n such a w a y as to minimize d i s t u r b a n c e of t h e i n s t a l l a t i o n a n d i n c o n v e n i e n c e t o the user. Where it i s n e c e s s a r y t o d i s c o n n e c t p a r t o r t h e w h o l e of a n i n s t a l l a t i o n i n o r d e r to c a r r y o u t a test, disconnection should b e made at a time the a g r e e d with the user a n d f o r the minimum p e r i o d n e e d e d to carryout the test. Where m o r e than o n e test necessitates a disconnection, where possible, these tests should 643.3.2 b e made during one disconnection period. A c a r e f u l c h e c k s h o u l d b e m a d e of t h e t y p e of e q u i p m e n t o n site s o t h a t t h e n e c e s s a r y p r e c a u t i o n s c a n b e taken, w h e r e c o n d i t i o n s r e q u i r e , t o d i s c o n n e c t o r s h o r t - o u t electronic a n d other equipment t h a t might b e damaged by testing. Special c a r e must b e taken w h e r e control a n d protective devices contain electronic c o m p o n e n t s . 3.8.3 Setting inspection and testing samples T h e i n s p e c t o r m u s t b e f a m i l i a r w i t h s e t t i n g b o t h i n s p e c t i o n a n d t e s t i n g s a m p l e sizes, a s c a r r y i n g o u t 100 7o inspection a n d unachievable o r testing i n a n e l e c t r i c a l i n s t a l l a t i o n is unrealistic h o w e v e r m a y be a c h i e v a b l e f o r d e f i n e d p a r t s of it. Information is p r o v i d e d i n this s e c t i o n a n d i n t h e relevant s a m p l i n g table, Table 3 . 3 . As pointed o u t in S e c t i o n 3.8.3, o n e r e c o m m e n d e d p r o c e d u r e i s f o r the inspector t o carry o u t a n initial w a l k - r o u n d s u r v e y t o e s t a b l i s h initial s a m p l e sizes a t v a r i o u s p o i n t s throughout the installation. T h e detailed s a m p l e size i s a d j u s t e d upwards i f necessary, inspection depending is then s t a r t e d a n d the u p o n the results obtained. W h e r e practicable, s a m p l e s s h o u l d b e selected t h a t are representative of t h e w h o l e installation. Parts of the i n s t a l l a t i o n that, in the i n s p e c t o r ' s experience, a r e m o r e likely to be p r o b l e m a t i c , s h o u l d b e p r i o r i t i z e d . Discussions of s a m p l i n g a n d s a m p l e size selection b e r a t h e r simplistic, while in practice, a r e generally s i m p l i f i e d and tend to m a t t e r s a r e usually quite different. As discussed previously, a n initial s u r v e y of t h e p r e m i s e s m u s t b e c a r r i e d o u t ; i t i s r e a s o n a b l y likely, a s with m o s t buildings, t h a t different things will have been in i t s life. It m a y b e n e c e s s a r y to t a k e separate done to it a t v a r i o u s t i m e s s a m p l e s of the s a m e thing indifferent areas. For e x a m p l e , i n a f a c t o r y , t h e c o n d i t i o n o f a f l u o r e s c e n t l u m i n a i r e installation i n the o f f i c e a r e a i s unlikely to b e representative i n s t a l l a t i o n in t h e production of the condition of a f l u o r e s c e n t luminaire area, even if they a r e the s a m e type of luminaire. Guidance N o t e 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology 119 Inspectors will require all of their experience in setting sample locations and sizesand should consider: (a) t h e approximate age and probable condition of the electrical installation in the area being inspected; (b) any electrical installation work carried out since the last inspection and test; (c) any differences in the installation in the area (part of it may have been refurbished or taken from another area); (d) the type a n d usage of the installation o r part thereof in that area (part of it may have b e e n used for another purpose previously); (e) the ambient environmental ambient environmental conditions in t h e area and any differences in t h e conditions over the area; (f) the apparent effectiveness of ongoing maintenance, if any; (g) the period of t i m e elapsed since previous inspection/testing; (h) the size of the installation and any differences i n the ambient environmental conditions over the area; (i) consultation with the installation owner; and (j) the quality of records such as EICs, MElWCs, previous periodic reports, maintenance records, site plans/drawings inspection and data sheets relating to installed equipment. It should b e noted that the initial sample size is based only o n a visual pre-inspection and consultation of records. Further, what may at first appear to b e good, for example, the quality of maintenance, may turn o u t to b e poor during the detailed inspection and testing. In determining the sample size, it should b e noted that the minimum to get meaningful population size results is 1 0 0 according to statistical sampling theory. That means that inspection and testing as a whole, should cover at least 100 points on electrical equipment. The term electrical equipment is defined in BS 7671 as follows: El lectrica! e q u i p m e n t ( a b b r : Equipment). Any item for such purposes as generation, conversion, transmission, distribution o r utilization of electrical energy, such as machines, transformers, apparatus, measuring instruments, protective devices, wiring systems, accessories, appliances and luminaires. For very small installations such as those in some domestic premises, this principle is likely to m e a n that most electrical equipment forming part of the fixed installation is inspected a n d tested as appropriate. For example, a small domestic installation may only have four circuits each with less than ten accessories connected; t h e total number of items of electrical equipment, including the consumer unit and circuit wiring, is likely to b e well under 100, and, because it is practicable, all items are likely to b e included in the inspection and test. There should certainly b e n o sample of circuits made in such premises. In larger installations, such as those in commercial or industrial premises, it is recommended to change t h e sample to b e inspected and/or tested between periodic inspection and test visits. To facilitate this, the specific equipment sampled should b e clearly identified in t h e records. If this is not done, due t o large population sizes f r o m which samples are taken, it is possible that some parts of t h e installation would rarely, if ever, b e inspected and/or tested. 120 Guidance Note 3: Inspection & Testing © The Institution of Engineering and Technology 3 ▼ Figure 3.1 Suggested procedure for setting a n d adjusting sample sizes periodic verification required conduct pre inspection survey and establish sample size select samples for inspection and testing based on sample size information available on samples previously selected? select samples for inspection and testing based on sample size, avoiding previously selected samples where appropriate yes concentrate on circuits and equipment most likely to show defects carry out inspection and testing on samples selected intermediate/poor/ indeterminate results good results status of results no increase sample size or discuss with client whether more in-depth investigation is necessary sample size to be increased? yes final report Where the inspection or testing of a sample yields poor or unacceptable results, this would suggest that similar problems might exist elsewhere in uninspected or untested items. The inspector will t h e n need either to increase the sampling or refer back to the client; it may b e that the inspector recommends that 100 °/otesting is carried o u t in that area. The principle of this is indicated in Figure 3.1. G u i d a n c e N o t e 3: Inspection © The Institution of Engineering & Testing and Technology 121 As an example, consider the testing of final circuits at a distribution board with a sample size of 10 7o of the lighting circuits. Suppose that more than one of these circuits was found to have an unacceptably high earth fault loop impedance (EFLI), with a relatively low EFLIatthe incoming terminals to the distribution board itself, and that there were no apparent factors to suggest why the final circuit values were high. It would be remiss to complete the EICRby using just this 10 7o sample and stating that improvements were required for these circuits. It would be far more appropriate to increase the sample size or to recommend that all circuits at the distribution board were tested, based on the initial findings. If relatively small sample sizes are chosen, it is important that these are representative of the complete installation. Similarly, if a repeat periodic inspection is undertaken using a sampling system, then a different sample, again representative of the complete installation, must be chosen. Therefore, previous periodic inspection and test records should be consulted prior to commencement of a sample inspection and test. Suggested sample sizes for visual inspections are provided in Table 3.3; suggested sample sizes for testing are discussed in Section 3.10.1 of this Guidance Note and in Table 3.4. V T a b l e 3 . 3 Range of samples for inspection Item Suggested minimum sample size (notes 1, 2) Typical checks Main switchgear external inspection 100% Signs of damage, overheating or ageing Main switchgear internal sections and cable terminations Ideally 100 % but not less than 2 0 % (note 2) Signs of overheating, ageing, check tightness of terminals Main switchgear internal inspection of circuit-breaker connections a n d control sections Ideally 1 0 0 % b u t n o t less than 2 0 % Signs of overheating, ageing, check tightness of terminals Final circuit distribution boards Ideally 100 % but not less than 25 % (note 4) Signs of overheating, ageing, check tightness of terminals Final circuit accessories B e t w e e n 1 0 % to 1 0 0 % (note 3). Samples selected should cover all final circuits in small installations. Damage, signs of overheating Earthing and protective bonding conductors 100% Presence of conductors and tightness of terminations Notes: 1 Where t h e inspection o f a sample yields p o o r or unacceptable results, this w o u l d suggest that similar problems m a y exist elsewhere i n t h e uninspected items. T h e inspector will n e e d either t o increase t h e sampling or refer back t o t h e client; it m a y b e 2 3 4 5 122 that t h e inspector r e c o m m e n d s that 1 0 0 % inspection is carried o u t i n that area. 1 0 0 % where practicable. Generally, it is less appropriate to apply small sample sizing to the inspection of socket-outlets compared w i t h samples for lighting, as i t is m o r e likely that user e q u i p m e n t will b e hand-held presenting a greater risk for potential electric shock. D o not 'sample samples', resulting in a very l o w overall sampled installation. Samples m u s t b e representative. If i t is decided t o sample, for example, sub-main cables at 10 7o,then further sampling should not b e applied to t h e final circuit distribution boards o n these circuits. One easy way t o remember sampling is to reflect o n the fact that where just 1 0 % of final circuits have b e e n inspected, this actually means that 9 0 % have not b e e n inspected. Guidance Note 3: Inspection & Testing © The Institution of Engineering and Technology 3 Whenever samples are taken, and whatever sample size is utilized, the inspector must remember that t h e requirement installation being inspected of the Report is to say whether or not t h e electrical (subject t o any agreed limitations) is suitable or not for continued use. The inspector m u s t carry out sufficient inspection and testing to allow t h e m to make that judgement, i n many dwellings and smaller commercial installations, sampling would b e largely inappropriate and should never o m i t entire circuits. 3.9 Periodic inspection 3.9.1 Example checklist of items that require inspection Appx6 The following is a copy of the checklist in Appendix 6 of BS 7671, which lists items at various locations within a n installation that may require inspection. The items in this checklist are examples; t h e list is not exhaustive. ELECTRICAL INTAKE EQUIPMENT (VISUAL INSPECTION Where inadequacies in intake equipment are encountered, ONLY) it is recommended that the person ordering t h e report informs the appropriate authority. • • • Service cable Service head Earthing arrangements (where provided, for example TN-C-S and TN-S systems, b u t not TT systems) • Meter tails (on both supplier and consumer side of the meter) • Metering equipment • Isolator (where present) Note: It is important for the inspector to provide information about inadequacies with electrical intake equipment, along with any recommendation to inform the relevant authority, to the person ordering the report, in writing to cover liability. PRESENCE OF ADEQUATE ARRANGEMENTS FOR PARALLEL O R SWITCHED ALTERNATIVE SOURCES • Adequate arrangements where a generating set operates as a switched alternative to t h e public supply (551.6) • Adequate arrangements where a generating set operates in parallel with t h e public supply (551.7) AUTOMATIC • DISCONNECTION Main earthing bonding arrangements (411.3; Chap 54) 1 Presence of distributor's earthing arrangement (542.1.2.1; 542.1.2.2), or 2 presence of installation earth electrode arrangement (542.1.2.3) Adequacy of earthing conductor size (542.3; 543.1.1) 3 Adequacy of earthing conductor connections (542.3.2) 4 Accessibility of earthing conductor connections (543.3.2) 5 Adequacy of main protective bonding conductor sizes (544.1) 6 Adequacy and location of m a i n protective bonding conductor connections (543.3.2; 7 • OF SUPPLY 544.1.2) Accessibility of all protective bonding connections (543.3.2) 8 Provision of earthing/bonding labels at all appropriate locations (514.13) FELV- requirements satisfied (411.7; 411.7.1) Guidance Note 3: Inspection & Testing © The Institution of Engineeringand Technology 123 3 OTHER METHODS O F PROTECTION (where any of the methods listed below are employed details should b e provided o n separate pages) • Non-conducting location (418.1) • Earth-free local equipotential bonding (418.2) • Electrical separation (Section 413; 418.3) • Double insulation (Section 412) • Reinforced insulation (Section 412) DISTRIBUTION EQUIPMENT • Adequacy of working space/accessibility to equipment (132.12; 513.1) • Security of fixing (134.1.1) • Condition of insulation of live parts (416.1) • Adequacy/security of barriers (416.2) • Condition of enclosure(s) in terms of fire rating etc (; 421 .1.6; 421.1.201 ; 526.5) • Enclosure not damaged/deteriorated so as to impair safety (651.2) • Presence and effectiveness • Components of obstacles (417.2) are suitable according to manufacturers' assembly instructions or literature (536.4.203) • Presence of main switches), linked where required (462.1; 462.1.201; 462.2) (functional check) (643.10) • Operation o f main switches) • Manual operation of circuit-breakers, RCDs and AFDDsto prove functionality (643.10) • Confirmation that integral test button/switch causes RCD(s) to trip when operated (functional check) (643.10) • RCD(s) provided for fault protection, where specified (411.4.204; 411.5.2; 531.2) • RCD(s) provided for additional protection, where specified (411.3.3; 415.1) • Confirmation overvoltage protection (SPDs) provided where specified (534.4.1.1) • • Presence of RCD six-monthly test notice where required (514.12.2) Presence of diagrams, charts or schedules at or near equipment, where required (514.9.1) • Presence of alternative supply warning notice, where required (514.15) Labels for multiple supplies should b e provided at: 1 The origin 2 The meter position, if remote f r o m origin 3 The distribution board to which the alternative/additional sources are connected 4 All points of isolation of ALL sources of supply • Presence of next inspection recommendation label (514.12.1) • Presence of other required labelling (Section 514) • Selection of protective device(s) and base(s); correct t y p e and rating (411.3.2; 411.4,.5, .6; Sections 432, 433, 434) • Single-pole protective devices in line conductors only (132.14.1, 530.3.2; 643.6) • Protection against mechanical damage where cables enter equipment • Protection against electromagnetic effects where cables enter ferromagnetic (522.8.1; 522.8.5; 522.8.11) enclosures (521.5.1) Confirmation that ALL conductor connections, including connections to busbars, are correctly located in terminals and are tight and secure (526.1) The use of individual components in a distribution board or consumer unit assembly complying their compatibility controlgear assembly. 124 G u i d a n c e N o t e 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology with their respective product standard(s) does not indicate when installed with other components in an LV switchgear and 3 Incorporated components inside the assembly can be f r o m different manufacturers. It is essential that all incorporated components have their compatibility for the final enclosed arrangements verified by t h e original manufacturer of the assembly and are assembled i n accordance with their instructions, for example, those of the consumer unit or distribution board manufacturer. The original manufacturer is t h e organization that carried out t h e original design and t h e associated verification of the LV switchgear and controlgear assembly to the relevant part of the BS EN 61439 series. If an assembly deviates from its original manufacturer's instructions, or includes components n o t included in t h e original verification, the person introducing the deviation becomes the original manufacturer, with the corresponding obligations. The inspector may wish to note such assemblies for further investigation. Consumer unit standards have also evolved over the years to provide co-ordinated 'conditional ratings'. 1 BS 5486-13: 1979 had a 6 kA, 10 kA, o r 16 kA conditional rating as part of a British Standard. The inspector therefore needs to check t h e label or instructions for CM6, CM10 or CM16. 2 BS 5486-13: 1989 had a 16 kA conditional rating as part of a British Standard. BS 5486-13 was withdrawn and replaced by B S E N 60439-3: 1991. 3 BS EN 60439-3: 1991 had UK National deviation Annex ZA 16 kA conditional rating. B S E N 60439-3: 1991 was withdrawn and replaced by 4 BS EN 60439-3: 2012. BS EN 61439-3: 2012 has UK National deviation Annex ZB 16 kA 5 BS EN 61439-3: 2012 (incorporating conditional rating. December corrigenda September 2013 a n d 2015) is the only current version for new installations, but the older equipment may still b e in use in installations. DISTRIBUTION CIRCUITS • Identification • Cables correctly supported throughout of conductors (514.3.1) their run (521.10.202; 522.8.5) • Condition of insulation of live parts (416.1) • Non-sheathed • (521.10.1) Suitability of containment • Cables correctly terminated i n enclosures (Section 526) • Confirmation • busbars, are correctly located in terminals and are tight and secure (526.1) Examination of cables for signs of unacceptable thermal or mechanical • damage/deterioration (421 .1 ; 522.6) Adequacy of cables for current-carrying capacity with regard for the type and cables protected by enclosure in conduit, ducting or trunking systems for continued use (including flexible conduit) (Section 522) that ALL conductor connections, including connections to nature of installation (Section 523) • Adequacy of protective devices: type and rated current for fault protection (411.3) • Presence and adequacy of circuit protective conductors (411 .3.1.1; 543.1 ) • • Coordination between conductors and overload protective devices (433.1 ; 533.2.1) Cable installation methods/practices w i t h regard to the type and nature of • Where exposed to direct sunlight, cable of a suitable type (522.11.1) • Cables concealed installation and external influences (Section 522) under floors, above ceilings, in walls/partitions less than 5 0 m m f r o m a surface, and in partitions containing metal parts 1 installed in prescribed zones (see Section D. Extent and (522.6.202) limitations) or Guidance Note 3 : Inspection & Testing © The Institution of Engineering and Technology 125 3 2 incorporating earthed armour or sheath, o r run within earthed wiring system, o r otherwise protected against mechanical damage by nails, screws and t h e like (see Section D. Extent and limitations) • (522.6.204) Provision of fire barriers, sealing arrangements and protection against thermal effects (Section 527) • Band II cables segregated/separated • • Cables segregated/separated f r o m non-electrical services (528.3) Condition of circuit accessories (651.2) f r o m Band I cables (528.1) • Suitability o f circuit accessories for external influences (512.2) • Single-poleswitchingor protective devices in line conductors only (132.14.1 ;530.3.3) • Adequacy of connections, including cpcs, within accessories and to fixed and stationary equipment - identify/ record numbers and locations of items inspected (Section 526) • Presence, operation and correct location of appropriate devices for isolation and switching (Chapter 46; Section 5 3 7 ) • General condition of wiring systems (651.2) • Temperature rating of cable insulation (522.1.1; Table 52.1) FINAL CIRCUITS • Identification • Cables correctly supported throughout of conductors (514.3.1) • Condition of insulation of live parts (416.1) • Non-sheathed cables protected by enclosure in conduit, ducting or trunking (521.10.1 ) • Suitability of containment their run (521.10.202; 522.8.5) systems for continued use (including flexible conduit) (Section 522) • Adequacy of cables for current-carrying capacity with regard for the t y p e and nature of installation (Section 523) • • Adequacy of protective devices: type and rated current for fault protection (411.3) Presence and adequacy of circuit protective conductors (411.3.1.1; 543.1) • Co-ordination between conductors and overload protective devices (433.1 ; 533.2.1 ) • Wiring system(s) appropriate for the t y p e and nature of t h e installation and • Cables concealed under floors, above ceilings, in walls/partitions, external influences (Section 522) adequately protected against damage (522.6.201; 522.6.202; 522.6.203; 522.6.204) 1 installed in prescribed zones (see Section D. Extent and limitations) (522.6.202) 2 incorporating earthed armour or sheath, o r run within earthed wiring system, or otherwise protected against mechanical damage by nails, screws and t h e like (see Section D. Extent and limitations) (522.6.201; 522.6.204) • Provision of additional protection by 3 0 m A RCD 1 *for all socket-outlets of rating 3 2 A or less unless a documented risk assessment confirms an RCD is not necessary (411.3.3) 2 *for the supply of mobile equipment not exceeding 3 2 A rating for use outdoors (411.3.3) 3 *for cables concealed in walls at a depth of less than 5 0 m m (522.6.202; 4 522.6.203) *for cables concealed i n walls/partitions containing metal parts regardless of depth (522.6.203) 5 • *for final circuits supplying luminaires within dwellings (411.3.4) Suitability of equipment in terms of IP and fire ratings (416.2; 421.1; 421. 1.201; 526.5) • Enclosurenot damaged/deteriorated during installation so as to impair safety (134.1.1) • Provision of fire barriers, sealing arrangements and protection against thermal effects (Section 527) 126 Guidance Note 3: Inspection & Testing © The Institution of Engineering and Technology 3 • Band II cables segregated/separated f r o m Band I cables (528.1) • Cables segregated/separated f r o m non-electrical services (528.3) • Termination of cables at enclosures - identify/record numbers a n d locations of items inspected (Section 526) 1 Connections 2 N o basic insulation of a conductor visible outside enclosure (526.8) under no undue strain (526.6) 3 4 Connections of live conductors adequately enclosed (526.5) Adequately connected at point of entry to enclosure (glands, bushes etc.) (522.8.5) • Condition of accessories including socket-outlets, switches and joint boxes (651.2) • Suitability of accessories for external influences (512.2) • Single-poleswitchingor protective devices in line conductors only (132.14.1;530.3.3) Note: *Older installations designed prior to BS 7671:2018 may not have been provided with RCDsfor additional protection. ISOLATION • AND SWITCHING Isolators (Sections 460; 537) 1 2 Presence and condition of appropriate devices (462; 537.2.7) Acceptable location - state if local or remote f r o m equipment in question (Section 462; 537.2.7) 3 Capable o f being secured in the OFF position (462.3) 4 Correct operation verified (643.10) 5 Clearly identified by position and/or durable marking (537.2.6) 6 Warning notice posted in situation where live parts cannot b e isolated by t h e operation of a single device (514.11.1:537.1.2) • Switching off for mechanical maintenance (Section 464; 537.3.2) 1 2 Presence and condition of appropriate devices (464.1; 537.3.2) Acceptable location - state if local o r remote f r o m equipment in question (Section 462; 537.2.7) • • 3 Capable of being secured in t h e OFF position (462.3) 4 Correct operation verified (functional check) (643.10) 5 Clearly identified by position and/or durable marking (537.3.2.4) Emergency switching/stopping (465; 537.3.3) 1 Presence and condition of appropriate devices (465.1; 537.3.3) 2 Readily accessible for operation where danger might occur (537.3.3.6) 3 Correct operation verified (643.10) 4 Clearly identified by position and/or durable marking (537.3.3.6) Functional switching (463.1; 537.3.1) 1 2 Presence of appropriate devices (537.3.1.1; 537.3.1.2) Correct operation verified (537.3.1.1; 537.3.1.2; 643.10) CURRENT-USING EQUIPMENT (PERMANENTLY CONNECTED) • Suitability for t h e environment and external influences (512.2) • Security of fixing (134.1.1) • Cable entry holes in ceilings above luminaires, sized or sealed so as to restrict the spread of fire (527.2) • • Provision of undervoltage protection, where specified (Section 445) Provision of overload protection, where specified (Section 433; 552.1) • Recessed luminaires (downlighters) • 1 Correct t y p e of lamps fitted (559.3.1) 2 Installed to minimize build-up of heat (421.1.2; 559.4.1) Adequacy of working space/accessibility to equipment (132.12; 513.1) Guidance © The Institution Note 3 : Inspection & Testing of Engineering a n d Technology 127 3 PART 7 SPECIAL INSTALLATIONS OR LOCATIONS • If any special installations o r locations are present, list t h e particular inspections applied. Where Special Installations or Locations relating to a particular Section of Part 7, an additional inspection schedule ) should b e provided on separate pages. 3.10 Periodic testing 3.10.1 General 651.1 The periodic testing is supplementary to the inspection of the installation: see Section 3.8.1. The same range and level of testing as for initial testing is not necessarily required, or indeed possible, installations that have been previously tested and for which there are comprehensive records of test results may not need the same degree of testing as installations for which n o such records exist. 651.5 Periodic testing may cause danger if t h e correct procedures are not applied. Persons carrying out periodic testing must b e competent in the use of t h e instruments employed and have adequate knowledge and experience of the t y p e of installation (see Section 3.8.1). The inspector will n e e d t o set a sample size for testing. Notes o n the principle of this are included in Section 3.8.3, which should b e studied together with the guidance o n suggested tests in Table 3.4. Where a sample test indicates results significantly different f r o m those previously recorded, further investigation is necessary. In addition, if during t h e course of testing a sample, significant errors are found that suggest that the same problems might exist in untested items, the inspector should take appropriate action by either increasing the sampling or by referring back to the client regarding t h e matter; it may b e that the inspector recommends that 100 °/otesting is carried out in that area. This principle is mentioned earlier, in Figure 3.1. 3.10.2 Tests to be made 651.2 The tests considered appropriate by t h e person carrying out the inspection should b e carried out in accordance with t h e recommendations in Table 3.4 a n d considering Section 3.8.1 to 3.8.3 of this Guidance Note. See Section 2.6 of this Guidance Note for test methods, noting that alternative methods m a y b e used, provided they give reliable results. ▼ Table 3.4 Testing t o b e carried o u t w h e r e practicable o n existing installations (see Notes 1 and 2) Test Recommendations Continuity of protective conductors Accessible exposed-conductive-parts of current-using equipment accessories (notes 4 a n d 5 ) Continuity of bonding conductors 128 G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology (a) (b) _________________________ Main protective bonding conductors to extraneous- conductive-parts Supplementary bonding conductors and | 3 Test Recommendations Continuity of ring final circuit conductors Where there are records o f previous tests, this test m a y n o t b e necessary unless there m a y have been changes m a d e to t h e ring final circuit Polarity At the following (a) (b) (c) (d) (e) _______________________ positions: origin of the installation distribution boards accessible socket-outlets extremity of radial circuits lighting circuits Where there are records of previous tests, this test m a y not b e necessary unless there m a y have been changes to the circuit. EFLI At t h e following positions: (a) (b) (c) (d) origin of t h e installation distribution boards accessible socket-outlets extremity o f radial circuits Insulation resist ance If tests are to b e m a d e : Earth electrode resistance If tests are t o b e made: (a) (a) between live conductors (connected together, where applicable) and Earth at main a n d final distribution boards (note 6) test each earth electrode o r group of electrodes separately, w i t h t h e test links removed, a n d with t h e installation isolated f r o m t h e supply source Functional tests RCDs Tests as required b y Regulation 643.1, followed integral test button by operation of the Functional tests of circuit-breakers, isolators a n d switching devices a n d other functional tests where necessary Manual operation to confirm that t h e devices disconnect t h e supply, including functional test of AFDDsthat have a test button, by pressing t h e test button. Notes: 1 The person carrying out t h e testing should decide which of the above tests are appropriate by using their experience and knowledge of t h e installation being inspected and tested and by consulting any available records (see Section 3.8.3 of this Guidance Note). 2 3 4 5 6 7 Where sampling is applied, t h e percentage u s e d is at t h e discretion of t h e inspector (see Section 3.8.3 of this Guidance Note). A percentage of less t h a n 1 0 7o, or sampling i n installations w i t h a sample population of less than 1 0 0 items of electrical equipment, is inadvisable. T h e tests n e e d n o t b e carried o u t i n t h e order s h o w n i n t h e table. T h e EFLI test m a y b e used to confirm t h e continuity o f protective conductors at socket-outlets and, w h e r e it is safe to d o so, at accessible exposed-conductive-parts of current-using e q u i p m e n t a n d accessories. Generally, accessibility m a y b e considered t o b e within 3 m f r o m t h e floor or f r o m w h e r e a person can stand. Where t h e circuit includes SPDs or other electronic devices that require a connection to earth for functional purposes, these devices will require disconnecting t o avoid influencing t h e test result and t o prevent t h e m being damaged. Where an installation is fully loaded and the conductors are at their normal operating temperatures, measured loop impedance values can b e directly compared with the maximum values of EFLI set out in the tables in Chapter 41 of the Regulations. Loop impedance data for unloaded conductors at 20 °C can b e found in t h e lET's On-Site Guide. Guidance Note 3: Inspection & Testing © The Institution of Engineeringand Technology 129 3 8 Except at the origin of t h e installation, EFLI may b e determined by means other than measurement (see Section 2.6.15). 9 See Section 2.6.24 w h e r e EFLI i s t o b e determined in installations with inverter supplies, such as PEIs. 1 0 In some installations, it i s not always practicable to isolate the supply to certain parts of the installation for t h e purposes of frequent periodic inspection a n d testing, for example those supplying safety services. In these circumstances, s o m e information regarding t h e state of insulation may b e obtained using a leakage current clamp meter (sometimes called 'tong tester') - see Appendix C . 3.10.3 Additional notes on periodic testing T h i s s e c t i o n p r o v i d e s s o m e n o t e s o n t h e practicalities o f c a r r y i n g out t h e p e r i o d i c t e s t s , p a r t i c u l a r l y w i t h i n a n i n s t a l l a t i o n w h e r e o n l y p a r t i a l i s o l a t i o n is p r a c t i c a b l e . a Continuity of protective earthing and bonding conductors, and EFLItesting If a n e l e c t r i c a l i n s t a l l a t i o n i s i s o l a t e d f r o m t h e supply, it i s p e r m i s s i b l e to d i s c o n n e c t p r o t e c t i v e e a r t h i n g a n d b o n d i n g c o n d u c t o r s f r o m t h e m a i n e a r t h i n g t e r m i n a l (MET) in o r d e r to v e r i f y t h e i r c o n t i n u i t y . W h e r e it i s not p r a c t i c a b l e t o i s o l a t e a n e l e c t r i c a l i n s t a l l a t i o n f r o m t h e s u p p l y a t t h e t i m e of t h e i n s p e c t i o n a n d t e s t i n g w o r k s , t h e p r o t e c t i v e e a r t h i n g o r b o n d i n g c o n d u c t o r s s h o u l d not b e d i s c o n n e c t e d as, u n d e r f a u l t c o n d i t i o n s , t h e e x p o s e d - c o n d u c t i v e - p a r t s a n d e x t r a n e o u s - c o n d u c t i v e - p a r t s c o u l d b e r a i s e d to a d a n g e r o u s v o l t a g e relative to Earth potential. In addition, the measurement of EFLI at various parts of the installation is, for practical reasons, carried out with the protective earthing a n d bonding conductors connected. A convenient way to carry o u t t h e a b o v e p e r i o d i c tests i n a large installation c o u l d b e to u s e t h e w a n d e r i n g l e a d m e t h o d t o test c o n t i n u i t y (see S e c t i o n 2.6.5, 2), n o t i n g t h a t t h e c o n d u c t o r s were n o t d i s c o n n e c t e d f o r t h e s e tests, test m e t h o d a n d to d i r e c t l y m e a s u r e EFLI a t t h e s a m e t i m e . W i t h t h e e a r t h i n g a n d b o n d i n g c o n d u c t o r s c o n n e c t e d , t h e tests c o n f i r m c o n n e c t i o n , b u t not t h e c o n t i n u i t y of t h e c o n d u c t o r s i n v o l v e d . Motor circuits L o o p i m p e d a n c e tests o n m o t o r circuits c a n o n l y b e c a r r i e d o u t o n t h e s u p p l y s i d e of isolated m o t o r controlgear. A continuity t e s t b e t w e e n t h e circuit protective c o n d u c t o r (cpc) a n d the m o t o r i s t h e n n e c e s s a r y . b Insulation resistance I n s u l a t i o n r e s i s t a n c e tests s h o u l d b e m a d e o n electrically isolated circuits w i t h a n y e l e c t r o n i c e q u i p m e n t t h a t might b e d a m a g e d by a p p l i c a t i o n of t h e test voltage disconnected, o r o n l y a m e a s u r e m e n t t o protective earth m a d e , w i t h t h e live conductors c o n n e c t e d together. It i s a d v i s e d to d i s c o n n e c t f u n c t i o n a l e a r t h c o n n e c t i o n s to r e s i d u a l c u r r e n t d e v i c e s (RCDs) a n d r e s i d u a l c u r r e n t circuit-breakers (with protection) (RCBOs) w h e n c a r r y i n g o u t i n s u l a t i o n r e s i s t a n c e tests, overcurrent as it m a y o t h e r w i s e i n f l u e n c e t h e results. 643.3 For m o s t installations, t h e m o s t p r a c t i c a l test i s a n i n s u l a t i o n r e s i s t a n c e test b e t w e e n live c o n d u c t o r s (connected together) a n d e a r t h ; i n p r a c t i c e , t i m e d o e s not u s u a l l y a l l o w f o r a line to n e u t r a l t e s t . W h e r e e q u i p m e n t i s i n s t a l l e d t h a t m a y b e s u s c e p t i b l e to d a m a g e by a 5 0 0 V DC t e s t voltage, devices, R e g u l a t i o n 6 4 3 . 3 states t h a t t h e t e s t s h o u l d b e c o n d u c t e d w i t h a t e s t v o l t a g e of 2 5 0 V DC. 130 s u c h as e l e c t r o n i c c o n t r o l a n d m o n i t o r i n g Guidance Note 3: Inspection & T esting © The Institution of Engineering and Technology 3 Test Recommendations Continuity of ring final circuit conductors Where there are records of previous tests, this test may not b e necessary unless there m a y have been changes m a d e to the ring final circuit Polarity At the following positions: (a) (b) (c) (d) (e) origin o f t h e installation distribution boards accessible socket-outlets extremity of radial circuits lighting circuits Where there are records of previous tests, this test m a y not b e necessary unless there may have b e e n changes to t h e circuit EFLI At t h e following (a) (b) (c) (d) positions: origin of t h e installation distribution boards accessible socket-outlets extremity o f radial circuits Insulation resist ance If tests are to b e m a d e : Earth electrode resistance If tests are to b e m a d e : (a) (a) between live conductors (connected together, where applicable) and Earth at m a i n a n d final distribution boards (note 6) test each earth electrode or group of electrodes separately, with t h e test links removed, a n d w i t h t h e installation isolated f r o m the supply source Functional tests RCDs Tests as required by Regulation integral test button 643.1, followed by operation of the Functional tests of circuit- breakers, isolators a n d switching devices and other functional tests where necessary Manual operation to confirm that t h e devices disconnect t h e supply, including functional test of AFDDsthat have a test button, by pressing the test button. Notes: 1 The person carrying out the testing should decide which of the above tests are appropriate 2 3 4 5 6 7 by using their experience and knowledge of t h e installation being inspected and tested and by consulting any available records (see Section 3.8.3 of this Guidance Note). Where sampling is applied, t h e percentage used is at t h e discretion of t h e inspector (see Section 3.8.3 of this Guidance Note). A percentage of less than 10 7o, or sampling in installations w i t h a sample population of less than 1 0 0 items of electrical equipment, is inadvisable. The tests n e e d n o t b e carried o u t i n t h e order s h o w n i n t h e table. The EFLI test m a y b e used t o c o n f i r m t h e continuity of protective conductors at socket-outlets and, where i t is safe t o d o so, at accessible exposed-conductive-parts o f current-using e q u i p m e n t a n d accessories. Generally, accessibility m a y b e considered to b e within 3 m f r o m t h e floor o r f r o m w h e r e a person can stand. Where t h e circuit includes SPDs o r other electronic devices that require a connection to earth for functional purposes, these devices will require disconnecting t o avoid influencing t h e test result a n d to prevent t h e m b e i n g damaged. Where an installation is fully loaded and t h e conductors are at their normal operating temperatures, measured loop impedance values can b e directly compared with t h e maximum values of EFLI set out in t h e tables in Chapter 41 of the Regulations. Loop impedance data for unloaded conductors at 20 °C can b e found in the lET's On-Site Guide. Guidance N o t e 3: Inspection & Testing ©The Institution of Engineering and Technology 129 3 8 Except at the origin of the installation, EFLI may be determined by means other than measurement (see Section 2.6.15). 9 See Section 2.6.24 where EFLI is to be determined in installations with inverter supplies, such as PEIs. 1 0 In some installations, it is not always practicable to isolate the supply to certain parts of the installation for the purposes of frequent periodic inspection and testing, for example those supplying safety services. In these circumstances, some information regarding the state of insulation may be obtained using a leakage current clamp meter (sometimes called 'tong tester') - see Appendix C. 3.10.3 Additional notes on periodic testing This section provides s o m e notes o n t h e practicalities of carrying o u t the periodic tests, particularly within an installation where only partial isolation is practicable. a Continuity of protective earthing and bonding conductors, and EFLItesting If an electrical installation is isolated from t h e supply, it is permissible to disconnect protective earthing and bonding conductors from the main earthing terminal (MET) in order to verify their continuity. Where it is not practicable to isolate an electrical installation from t h e supply at t h e t i m e of the inspection and testing works, t h e protective earthing or bonding conductors should not b e disconnected as, under fault conditions, t h e exposed-conductive-parts and extraneous-conductive-parts could b e raised to a dangerous voltage relative to Earth potential. In addition, the measurement of EFLI at various parts of the installation is, for practical reasons, carried out with the protective earthing and bonding conductors connected. A convenient way to carry o u t t h e above periodic tests i n a large installation could b e to use the wandering lead m e t h o d to test continuity (see Section 2.6.5, test method 2), noting that t h e conductors were not disconnected for these tests, and to directly measure EFLI at t h e same time. With t h e earthing and bonding conductors connected, t h e tests confirm connection, but not t h e continuity of the conductors involved. Motor circuits Loop impedance tests o n motor circuits can only b e carried o u t o n the supply side of isolated motor controlgear. A continuity test between t h e circuit protective conductor (cpc) and the motor is t h e n necessary. b Insulation resistance Insulation resistance tests should b e m a d e o n electrically isolated circuits with any electronic equipment that might b e damaged by application of the test voltage disconnected, or only a measurementto protective earth made, with t h e live conductors connected together. It is advised to disconnect functional earth connections to residual current devices (RCDs) and residual current circuit-breakers (with overcurrent protection) (RCBOs) w h e n carrying out insulation resistance tests, as it may otherwise influence t h e results. 643.3 For most installations, t h e most practical test is an insulation resistance test between live conductors (connected together) and earth; i n practice, t i m e does not usually allow for a line to neutral test. Where equipment is installed that may be susceptible to damage by a 5 0 0 V DC test voltage, such as electronic control and monitoring devices, Regulation 643.3 states that t h e test should b e conducted with a test voltage of 2 5 0 V DC. 130 Guidance Note 3: Inspection & Testing © The Institution of Engineeringand Technology 3 Check that information/warnings are given at the distribution board of circuits o r equipment likely t o b e damaged by testing. Any diagram, chart or table should also include this warning. The results of insulation testing should b e compared with previous results, where possible. Table 2.8 of this Guidance Note (Table 6 4 of BS7671) requires a minimum insulation resistance of 1 M Q , but strictly speaking, this value applies only to initial verification. It can, however, be used as a guide for periodic testing. Such low insulation resistancereadingsmay indicate that there isa problem with an item of electrical equipment, and where possible past records should be reviewed to identify historical readings to determine if there has been a sudden, or gradual, decrease, from previous tests. Where equipment is disconnected for these tests and the equipment has exposed- conductive-parts required by t h e Regulations to b e connected to protective conductors, the insulation resistance between t h e exposed-conductive-parts and all live parts of the equipment should b e measured separately and ought to comply with the requirements of the appropriate British Standard for t h e equipment. There is a range of possible outcomes when carrying out insulation testing. Tests are typically made between all live conductors connected together and Earth at a test voltage of 5 0 0 V DC. The inspector will need to measure the values of insulation resistance for a given distribution board and then take a view based o n their engineering judgement as to whether the results obtained are acceptable. It should b e noted that distribution boards with large numbers of final circuits will generally give a lower insulation resistance value than distribution boards with fewer final circuits. c Polarity It should b e established whether there have been any additions or alterations to the installation since its last inspection. If no additions or alterations have been made, the polarity test may n o t b e necessary. d 643.10 Operation of overcurrent circuit-breakers Where protection against overcurrent is provided by circuit-breakers, the manual operating mechanism of each circuit-breaker should b e operated to verify that t h e device opens and closes satisfactorily. It is n o t normally necessary or practicable to test the operation of the automatic tripping mechanism of circuit-breakers. A test would n e e d to b e made at a current substantially exceeding t h e m i n i m u m tripping current in order to achieve operation within a reasonable time. For circuit-breakers to BS EN 6 0 8 9 8 , a test current of not less than two and a half times the rated tripping current of the device is needed for operation within o n e minute, and m u c h larger test currents would b e necessary to verify operation of the mechanism for instantaneous tripping. If there is doubt about the integrity of the automatic mechanism for circuit-breakers of t h e sealed type, designed n o t to b e maintained, it will normally b e m o r e practicable to replace the device than to make further tests. Such doubt may arisefrom visual inspection, if the device appears to have suffered damage or undue deterioration, or where there is evidence that the device may have failed t o operate satisfactorily in service. Circuit-breakers with the facility for injection testing may b e so tested and, if appropriate, their relay settings confirmed. Guidance Note 3 : Inspection & Testing © The Institution of Engineering and Technology 131 3 e Operation of devices for isolation and switching Where means are provided i n accordance with t h e requirements of t h e Regulations for isolation and switching, the devices should b e operated to verify their effectiveness and checked to ensure adequate and correct labelling. It should b e verified by inspection that easy access to such devices is maintained and that effective operation is not impaired by any material placed near the device. Access and operation areas may b e required to b e marked to ensure they are kept clear. For isolating devices in which the position of the contacts o r other means of isolation is externally visible, visual inspection of operation is sufficient and n o testing is required. The operation of every safety switching device should b e checked by operating t h e device in t h e manner normally intended, t o confirm that it performs its function correctly in accordance with t h e requirements of BS 7671. Where it is a requirement that the device interrupts all t h e supply conductors, the use of a proprietary test lamp, or two-pole voltage detector connected between each line and t h e neutral on the load side of the switching device, is essential to confirm isolation. Reliance should not b e placed o n a simple observation that the equipment controlled has ceased to operate. Where switching devices are provided with detachable or lockable handles in accordance with the Regulations, a check should b e made to verify that the handles or keys are n o t interchangeable with any others available within the premises. 643.10 Where any f o r m of interlocking is provided, such as between a main circuit-breaker and a n outgoing switch or isolation device, the integrity of t h e interlocking must b e verified; this may b e beyond the scope of the inspector and something that is referred to a manufacturer or specialist. Where switching devices are provided for isolation or for mechanical maintenance switching, the integrity of the means provided to prevent any equipment from being unintentionally or inadvertently energized or reactivated m u s t b e verified. f 643.7 Operation of RCDs Fault protection Where an RCD is provided for fault protection, t h e operating time should generally b e n o greater than those stated in Table 41.1 (Regulation 411.4.5) for final circuits and 5 s for distribution circuits, unless supplementary bonding has been applied in accordance with Regulation 419.3. Additional protection 643.8 Where an RCD with a rated residual operating current n o t exceeding 3 0 m A is used t o provide additional protection in t h e event of failure of basic protection and/or failure of t h e provision for fault protection or carelessness by users, t h e effectiveness is d e e m e d to have b e e n verified where an RCD meeting t h e requirements of Regulation 415.1.1 disconnects within 3 0 0 ms w h e n tested at a current equal to or higher than its rated residual operating current (lAn). 132 Guidance Note 3: Inspection & Testing © The Institution of Engineering and Technology I3 3.11 Electrical Installation 653 J Condition Report (EICR) A m o d e l of the EICR is provided in Appendix 6 of BS 7671, together with a m o d e l Condition Report Inspection Schedule, and Schedules of Circuit Details and Test Results. Typical completed forms are given in Section 5 of this Guidance Note. The full EICR documentation Electrical Installation comprises the following: Condition Report (EICR) and Condition Report Inspection Schedule (one or more) and Schedule On completion of Circuit Details and Schedule of periodic inspection of Test Results (one or more) and testing, the EICR and its accompanying schedules must b e given to the client or person who ordered the inspection. A very important point to remember is that any damage, deterioration, defects, dangerous conditions and non-compliance with B S 7 6 7 1 that may give rise to danger (’danger' being a risk of injury to persons or livestock) must b e recorded o n the Report. Classification codes C l to C3 indicate danger and non-compliances with BS 7671; these are explained in Table 3.5. Each separate item entered in the Section K 'Observations' section of t h e Report should b e coded C l , C 2 or C3 as appropriate, or, exceptionally, Fl (see Table 3.5). Only one classification code is to b e recorded against each observation. Where an installation defect or non-compliance with the Regulations has attracted a code of C l , C 2 or Fl, t h e overall assessment of the Report must b e 'unsatisfactory'. G u i d a n c e N o t e 3: I n s p e c t i o n & Testing © The Institution of Engineering a n d Technology 133 3 ▼ Table 3 . 5 Classification of danger a n d non-compliances (for use during periodic inspection a n d testing) Classification of danger or non-compliance Description Notes and guidance Cl Danger present. Risk of injury. Immediate remedial action required. To b e attributed to matters that cannot b e left. It is suggested that these are rectified or possibly, that isolation m a y be recommended or necessary. Examples include accessible bare live parts, badly damaged equipment with risk of access to live parts, incorrect polarity, a n d / o r arcing or burning f o u n d in switchgear. C2 Potentially dangerous: urgent remedial action required. T o b e attributed to issues that, while urgent, do not require immediate remedial action. Examples include a non-earthed installation (this requires a further fault to result i n danger), fundamentally undersized cables, EFLI values greater t h a n required by BS7671, a 'borrowed1 neutral, equipment with inappropriately selected IP (this m a y warrant C 1 if severe), insulation readings under 1 MQ, a n d connections not housed within appropriate enclosures. 134 C3 Improvement recommended. To b e attributed where C l or C2 do n o t apply. Examples include t h e absence of most warning notices, absence of t h e required diagrams a n d charts, n o or incorrect marking of conductors at terminations, a n d absence of an RCD specified for additional protection (where t h e circuit otherwise tests as normal). Fl Further investigation required without delay. To be attributed where the inspection has revealed an apparent deficiency that could not, due to the limitations or extent of the inspection, be fully identified and where further investigation m a y reveal a C I or C 2 item. An example could b e where characteristics of electricity supply (such as voltage or external EFLI) do not conform to supply industry norms. May also be used where part of an installation included i n the scope of the inspection a n d test could not b e accessed. Guidance Note 3: Inspection & Testing © The Institution of Engineering and Technology 3 3.12 Periodic inspection of installations constructed to an earlier edition of BS7671 or the lEEWiring Regulations People often ask what standard should b e applied w h e n carrying o u t t h e periodic inspection of a n installation constructed in accordance with an earlier edition of BS 7671, or an even earlier edition of t h e lEEWiring Regulations, or to an unknown standard. Each edition of the Wiring Regulations has provided for an increase in safety to the users of installations. Some installation practices and methods that were compliant with earlier editions would n o w b e considered unacceptable or dangerous, such as the use o f a public water pipe as a means of earthing. In all cases, t h e inspection should b e carried o u t against the current edition of BS7671 . It is likely that there will b e items that d o not comply with that edition, but this does n o t necessarily m e a n that t h e installation is unsafe. If the inspector considers that an item, although not warranting code C l or C2, requires improvement, it should b e given code C3 o n the EICR. If the item does not require improvement, it may b e recorded as an observation but it does not warrant a classification code. Reference is made to existing installations both in the second paragraph of the Introductions to BS 7 6 7 1 and its amendments, and in the Note by the HSEthat follows the Preface to BS 7671. Guidance Note 3: Inspection & Testing © The Institution of Engineering and Technology 135 NOTES 136 G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology Test instruments and 4 equipment 4.1 Instrument standard BS EN 61010 Safety requirements for electrical equipment for measurement, control, and laboratory use is the basic safety standard for electrical test instruments. The series of standards to which electrical test equipment for verification of measures for protection against electric shock is BS EN 61557 Electrical safety in low voltage distribution systems up to 1000 1/ a.c. and 1500 1/ d.c. Equipment for testing, measuring or monitoring of protective measures. This standard includes performance requirements and requires compliance with BS EN 61010. In Section 1.1 of this Guidance Note, reference was made to the use of test leads conforming to HSEGS38. The HSE always advise only to carry out live tests that are actually useful and informative, so as to minimize danger; the inspector should always consider whether any particular live test is necessary before undertaking it. The safety measures and procedures set o u t in GS38 should b e observed for all instruments, leads, probes and accessories. Some test instrument their instruments are used in conjunction manufacturers advise that with fused test leads a n d probes. Other manufacturers advise the use of non-fused leads and probes where t h e instrument has in-built electrical protection, but it should b e noted that such electrical protection does not extend to the probes and leads. Appendix 14 of BS7671 also recommends "the measurement that: should always b e made on t h e output terminals of a suitably rated protective device. If such a device is not present then a temporary one should b e fitted. Measurement should never b e made where overcurrent protection is not present between the point of connection and the supply transformer. Fused test leads alone do not meet this requirement." Where unsure, a risk assessment should b e carried out to establish if fused test leads should b e used. Manufacturers may provide multifunction test instruments to BS EN 61557-10 that combine more than one, or all, of the functions listed in Sections 4.3 to 4.8. Some of these instruments may have additional features such as current measurement (via clamp). G u i d a n c e N o t e 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology 137 4 4.2 Instrument accuracy The accuracy of a n e w or repaired instrument should b e established to provide a point of reference. Accuracy is usually confirmed by calibration, but a calibration certificate may not b e supplied with the instrument unless specifically requested. A certificate of conformity may b e provided indicating that the instrument's as part of the manufacturing accuracy was verified process. Such verification follows the same procedure as calibration, but individual calibration data is n o t issued. A basic measurement accuracy of 5 7 o i s usually adequate. In the case of analogue instruments, a basic accuracy of 2 7 o o f full-scale deflection will provide the required accuracy measurement over a useful proportion of the scale. It should not b e assumed that the accuracy of the reading taken in normal field use will b e as good as the basic accuracy. The ’operating accuracy’ is always worse than the basic accuracy, and additional errors derive from three sources: ( a ) instrument e r r o r s : basic instrument accuracy applies only in ideal conditions. The actual reading accuracy can also b e affected by: (i) digital instruments. Sources of error: test leads, fused leads, battery condition, ambient temperature, electrical noise, etc. (ii) analogue instruments. Sources of error: Orientation of the instrument on older instruments'. With hand-cranked units, cranking speed, can also affect performance. (b) l o s s o f calibration: manufacturer's instruments should b e periodically calibrated following recommendations and procedures traceable to National Standards. Intermediate checks can be made to ensure there are n o major errors in measurement by comparing readings with those obtained from other instruments, or by the use of a proprietary 'check box' having clearly defined characteristics. In all cases, the t y p e and frequency of recalibration or checking required should b e as specified by the instrument manufacturer. However, the user should take into account ambient environmental and usage factors, as appropriate. For example, if an instrument is left in storage at a constant temperature in a dry environment for long periods, a n d / or is used infrequently, t h e user may b e able to extend the recalibration interval. However, if an instrument is roughly handled and is regularly transported a n d stored in vehicles (and hence is subjected to fluctuations in temperature and humidity caused by changes in time of day/night and time of year), then more frequent confirmation of accuracy would b e appropriate. Instruments should also b e subjected t o regular checks before use so that errors caused by deterioration of leads, probes, connectors, etc. d o n o t result in inaccurate readings being recorded when, for example, Schedules of Test Results are compiled. Typically, in analogue instruments, this corresponds to making measurements near to the zero point on the scale, where inaccuracies and non-repeatability at all evident with this type of electromechanical very are not movement. It is essential t h a t an i n s t r u m e n t is inspected f o r damage a n d that the s a f e t y a n d the accuracy o f a n instrument is c o n f i r m e d a f t e r any incidences o f mechanical or electrical mishandling. 138 G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology 4 (c) field errors: t h e instrument reading accuracy will also b e affected by external influences as a result of working in the field environment. These influences can take many forms. Some sources of inaccuracy are described in the appropriate sections of this Guidance Note. BS EN 61557 requires a maximum operating error of n o m o r e than ± 3 0 7 o o f reading over the stated measurement range, taking into account the worst-case environmental, supply and battery conditions. To achieve satisfactory in-service performance, it is essential to b e fully informed about the test equipment, how it is to b e used, and the accuracy to b e expected. Traceability to National Standards can b e assured by using a calibration laboratory accredited by a National Accreditation Body. In the UK this is t h e United Kingdom Accreditation Service (UKAS). A list of accredited laboratories can b e found at www.ukas.com or a search for sources of calibration by instrument can b e made at https://www.ukas.eom/find-an-organisation/browse-by-category/#orgtype-273. 4.3 643.2.1 Low-resistance ohmmeters The continuity of conductors and connections to exposed-conductive-parts and extraneous-conductive parts, if any, shall be verified by a measurement of resistance on: (a) protective conductors, including protective bonding conductors; and (b) in the case of ring final circuits, live conductors. The instrument used for low-resistance tests may b e either a specialized low-resistance ohmmeter or t h e continuity range of an insulation and continuity tester. The test current may b e DC or AC. It is recommended that it b e derived f r o m a source with no-load voltage between 4 V and 24 V and a short-circuit current of not less than 200 m A . The measuring range should cover the span 0.2 Q to 2 Q , with a resolution of at least 0.01 Q for digital instruments. Instruments conforming to B S E N 61557-4 will meet the above requirements. Field effects contributing to in-service errors include probe or crock-clip contact resistance, test lead resistance, AC interference and thermocouple effects in mixed metal systems. Whilst contact resistance cannot b e eliminated with two-terminal testers, and can introduce errors, the effects of lead resistance can b e eliminated by measuring this prior to a test and subtracting t h e resistance f r o m t h e final value, or by using t h e test instrument's 'nulling' feature built in to most m o d e r n instruments. an external AC source (interference pick-up) cannot b e eliminated, Interference from although it may b e indicated by vibration of the pointer of an analogue instrument or by an unstable digital readout. Thermocouple effects can b e eliminated by reversing the test probes and averaging the resistance readings taken in each direction. G u i d a n c e N o t e 3: I n s p e c t i o n & Testing © The Institution of Engineering and Technology 139 4 4.4 Insulation resistance testers The instrument used should b e capable of developing the test voltage required across the load. The test voltage required is: Table 64 (a) 2 5 0 V DC for SELVand PELV circuits with equipment such as SPDs that may influence test results or b e damaged - but the insulation resistance is to b e at least 1 M Q (643.3.2); (b) 5 0 0 V DC for all circuits rated u p to and including 5 0 0 V, except SELVand PELV circuits; and (c) 1,000 V DC for circuits rated above 5 0 0 V and u p to 1,000 V. Instruments conforming to BSEN 61557-2 will fulfil all the above instrument requirements. When an insulation resistance test is applied to a test subject, the measurement may b e influenced by different circuit characteristics, for example: (a) capacitive charging; (b) absorption or polarization of the insulation; and (c) conduction or leakage currents. These factors can b e reduced or eliminated by extending the test time for which the test voltage is applied, and can be seen as a steady insulation reading on the instrument, after a n initial rapid increase in value. Capacitance may b e as high as 5 pF and the instrument should have an automatic discharge facility capable of safely discharging such a capacitance. Following an insulation resistance test, t h e instrument should b e left connected until t h e capacitance within the installation has b e e n fully discharged. 4.5 EFLI testers Loop impedance testing is the practice of measuring the impedance of a live circuit. Typically, t h e circuit voltage, either line-neutral (L-N), line-Earth (L-E) or line-line (L-L), is first measured to acquire the off-load voltage. A load is then applied and t h e n e w circuit voltage is measured. The voltage drop is used to calculate the impedance of the circuit. Exactly how this is done differs between manufacturers. However, all methods can b e presented with electrical conditions that pose a challenge to the measurement. Sources of error can include: (a) electrical noise and transients; (b) external load switching; (c) harmonics; (d) ROD uplift; (e) test lead contact resistance; and (f) instrument resolution and proximity to the source transformer (instrument resolution for many instruments means the instrument cannot provide adequate readings if taken too close to a supply transformer). 140 Guidance Note © T h e Institution 3: I n s p e c t i o n & Testing of Engineering a n d Technology 4 Three t y p e s of measurement a r e t y p i c a l l y available, l i s t e d i n o r d e r of preference: (a) t w o - w i r e high current test; (b) t h r e e - w i r e non-trip test; a n d (c) t w o - w i r e n o n - t r i p t e s t . Two-wire high current test: This is the test that should the circuit. a l w a y s be employed The l o a d u s e d u s u a l l y generates unless there between is a n R C D o r R C B O i n 2 A a n d 1 5 A. This is s u f f i c i e n t to c r e a t e a m e a s u r a b l e v o l t a g e d r o p a n d c o n s e q u e n t l y a s t a b l e a n d a c c u r a t e result. T h e t e s t u s u a l l y lasts f o r n o m o r e t h a n 3 - 4 m o r e t h a n 4 0 ms o n two consecutive s i n total, w i t h t h e l o a d b e i n g p r e s e n t f o r n o half-cycles. Test currents higher than 15 A risk tripping some low current miniature circuit-breakers (MCBs). Three-wire non-trip test: W h e r e t h e r e a r e RCDs o r R C B O s present, out using a non-trip not to trip the significant voltage l o o p impedance RCD, typically drop. t h e L-E f a u l t l o o p i m p e d a n c e m a y b e c a r r i e d test. The l o a d current a r o u n d 1 5 m A . However, Consequently, in this test is s m a l l enough 1 5 m A does not create a many m o r e test cycles a r e p e r f o r m e d a n d the t e s t r u n s f o r significantly longer, w i t h t h e r e s u l t s far m o r e s u s c e p t i b l e to v a r i a t i o n . Two-wire non-trip test: The third o p t i o n o n s o m e instruments of not r e q u i r i n g the third lighting i s a t w o - w i r e non-trip test lead to b e connected, test. This h a s t h e advantage a n d i s especially u s e f u l on some circuits. T h e d r a w b a c k is that it is t h e most t e c h n i c a l l y difficult susceptible to m o r e errors than the three-wire test f o r t h e i n s t r u m e n t a n d c a n b e test. It should only b e used a s a last resort. Safety To m i n i m i z e e l e c t r i c s h o c k h a z a r d f r o m t h e p o t e n t i a l o f t h e p r o t e c t i v e c o n d u c t o r d u r i n g L-E i m p e d a n c e tests, t h e test d u r a t i o n s h o u l d b e w i t h i n safe l i m i t s . For two-wire high current tests, the instrument or a time determined by the s a f e t y limits B S I E C 60479-1 i f t h e voltage Effects of current should derived on human cut off the test current f r o m the information beings and livestock. after 40 ms contained General within aspects, rise o f t h e p r o t e c t i v e c o n d u c t o r e x c e e d s 5 0 V d u r i n g the t e s t . O n s o m e installations, t h i s t h r e s h o l d m a y b e 2 5 V , e s p e c i a l l y w h e r e l i v e s t o c k a r e p r e s e n t . For low current disconnect (non-trip) tests, the instrument the test if the e a r t h voltage must monitor the e a r t h voltage and is exceeded. Sources o f error T h e l o w e r t h e l o a d c u r r e n t e m p l o y e d i n t h e test, t h e m o r e v a r i a t i o n a n d e r r o r i s likely i n t h e result, supply as t h e voltage drop i s p r o p o r t i o n a l l y lower. will a l s o c o m p r o m i s e accuracy a n d repeatability, differentiate between a voltage drop created i n d u c e d by n o i s e o r h a r m o n i c s , etc. For this D i s t o r t i o n o r n o i s e o n the a s the instrument by the applied c a n n o t easily l o a d o r a voltage r e a s o n , the test with change t h e higher load currents should always b e u s e d w h e r e possible. G u i d a n c e Note © T h e Institution 3: Inspection & Testing of Engineering a n d Technology 141 4 Repeating a test is advised if there is concern about t h e validity of the result, especially o n noisy supplies. RCD u p l i f t RCD uplift is a phenomenon frequently encountered when performing a two- or three-wire non-trip test. During the test, the RCD internal impedance may sometimes be measured, increasing the overall circuit impedance. This may be as high as 0.5 Q or more. RCD uplift can b e avoided by choosing an instrument that declares immunity to this effect. Alternatively, if uplift is suspected, measuring o n the source and load sides of the RCD will identify any additional impedance within the RCD. This can then be deleted f r o m the measurement. This phenomenon is not encountered with high test currents, but these tests will trip the RCD during the test, preventing their use. Transformer impedances can also affect results, as the impedance close to source can b e very reactive, rather than resistive. This is only a real issue when measuring close to the source transformer, but the instrument significant in this location. resolution and accuracy becomes very Test l e a d errors Test leads can induce errors from: (a) internal lead resistance; (b) contact resistance of the probes or clips; and (c) internal fusing of t h e test leads. As with t h e low resistance ohmmeter section earlier, t h e test lead resistance can b e ’nulled' or may already b e accounted for in the instrument. If not, the lead resistance should b e measured and deducted f r o m future measurement values. Contact resistance can add significantly to t h e circuit impedance. Inspectors should ensure that probes are sharp and that clips grip tightly. Fused leads can add significantly to lead resistance. A 5 0 0 mA fuse can add as much as 1.8 Q in a test lead pair. If fused leads are used for loop impedance testing, they will need to b e fused with higher rating fuses, typically 7 A or 10 A fuses, t o prevent the test current rupturing the fuse. Leads compliant to HSE GS38 should be adequate. Instrument accuracy and resolution The resolution of a n instrument is the smallest increment that the instrument can detect and display. This is usually measured in terms of the multiples of the least significant (right-most) digit of t h e instrument display. Instrument resolution can compromise measurement accuracy, especially at the lower loop impedances found near t h e source transformer. When measuring loop impedances below 0.1 Q, caution should b e exercised in the interpretation significantly affects measurement 142 Guidance N o t e 3: Inspection © T h e Institution & Testing of Engineering a n d Technology of the results, as the instrument accuracy values close to t h e lowest end of the range. For example, when attempting to measure a l o o p impedance of 0.03 Q , an instrument that declares a ± 5 °/o±3 digits o n a digital display could give an answer between zero and 0.06 Q and b e within its declared accuracy. Instruments conforming to BS EN 61557-3 will fulfil the above requirements under m o s t situations. These instruments may also offer additional facilities for deriving prospective fault current. The basic measuring principle is the same as for EFLI testers. The current is calculated by dividing the loop impedance Instrument accuracy is determined instrument value into the nominal mains voltage. by the same factors as for EFLI testers. In this case, accuracy decreases as scale reading increases, because the loop value is divided into the mains voltage. It is important to note these aspects and to consult the manufacturer's documentation. 4.6 Earth electrode resistance testers There are three general methods referred to in Section 2 of this Guidance Note: (a) test method E l , using a dedicated earth electrode tester (fall of potential, three- or four-terminal type); (b) test m e t h o d E2, using a dedicated earth electrode tester (stakeless o r clamp-type); and (c) test m e t h o d E3, using an EFLItester. The most accurate of these is test method E l . Test method E2 is more accurate if there are a number of earth electrodes. The method the stakeless or probe tester cannot b e used to measure the resistance of a single earth electrode unless there is at least one other earth electrode connected, which may b e formed from extraneous-conductive-parts or, in TN systems, the means of earthing of the supply. 4.7 RCD testers The trip times of RCDs are required to b e verified, to ensure adequate disconnection under fault conditions. RCDs are tested by applying a test load to t h e RCD, inducing a calibrated test current to flow in t h e L-E circuit. This creates a n imbalance in t h e L-N currents in t h e RCD and the device trips. The t i m e it takes to trip is then displayed. The test instrument should b e capable of applying the full range of test current to an in-service accuracy as given in BS EN 61557-6. This in-service reading accuracy will include the effects of voltage variations around the nominal voltage of the tester. The range of RCD operating currents supported is generally limited to between 10 m A and 1 A; exceeding these limits presents severe design and cost implications to the instrument design. As with loop impedance testing, the Earth voltage is monitored and prevented f r o m exceeding the touch voltage limit, either 5 0 V or 2 5 V, depending o n t h e requirements of t h e location. Guidance N o t e 3 : Inspection & Testing © The Institution of Engineeringand Technology 143 4 RCDs a r e u s u a l l y tested to ensure: (a) t h e y d o n o t t r i p w i t h f a u l t c u r r e n t s less t h a n 5 0 7o o f t h e i r o p e r a t i o n a l rating. (b) they trip in the required time at fault current of 100 7o of their operational rating. (c) In addition to t r i p time testing, i n s t r u m e n t s offer the ability to test the RCD's t r i p p i n g c u r r e n t t h r e s h o l d . For t h i s test, a r a m p c u r r e n t i s a p p l i e d f r o m less t h a n 5 0 7 o o f t h e R C D r a t i n g t o 110 7 o . T h e c u r r e n t a t w h i c h t h e R C D t r i p s is t h e n displayed: this identifies if the R C D i s overly sensitive and may cause nuisance tripping. I n s t r u m e n t s c o n f o r m i n g t o B S E N 6 1 5 5 7 - 6 w i l l f u l f i l the a b o v e r e q u i r e m e n t s . 4.8 Phase rotation instruments BS EN 6 1 5 5 7 - 7 gives t h e r e q u i r e m e n t s for m e a s u r i n g e q u i p m e n t for testing t h e p h a s e s e q u e n c e i n t h r e e - p h a s e d i s t r i b u t i o n systems, mechanical, visual and/or audible w h e t h e r t h e i n d i c a t i o n is given by means. BS E N 61557-7 includes requirements that: (a) indication system shall b e unambiguous voltage o r within between 8 5 7o a n d 110 7o of the t h e range of t h e n o m i n a l voltage a n d between nominal 9 5 7o a n d 1 0 5 7o o f t h e n o m i n a l s y s t e m f r e q u e n c y ; (b) t h e m e a s u r i n g e q u i p m e n t s h o u l d b e s u i t a b l e f o r c o n t i n u o u s operation; (c) the measuring equipment should be s o designed that when either one o r two measuring l e a d s a r e c o n n e c t e d t o e a r t h a n d t h e r e m a i n i n g m e a s u r i n g lead(s) r e m a i n c o n n e c t e d to their corresponding line conductors, t h e resulting total current (d) the to e a r t h should measuring not exceed equipment should 3.5 m A rms; not be damaged, nor should the user b e e x p o s e d to danger i n situations w h e r e t h e m e a s u r i n g e q u i p m e n t is c o n n e c t e d to 1 2 0 7o voltage of t h e rated system voltage o r to 1 2 0 7o of its rated m a x i m u m range; a n d (e) portable measuring equipment should be provided with permanently attached leads or with a plug device with live parts not accessible, whether plugged o r unplugged. 4.9 Thermographic equipment A l t h o u g h t h e r m o g r a p h i c s u r v e y i n g e q u i p m e n t i s not test instrument, especially notes such r e c o g n i z e d by B S 7 6 7 1 as a e q u i p m e n t c a n b e i n v a l u a b l e i n assisting e l e c t r i c a l i n s p e c t i o n s , in the early identification a r e t h e r e f o r e included of possible points of overheating h e r e o n this t y p e of equipment. in circuits. S o m e It must, however, be r e m e m b e r e d that e q u i p m e n t m u s t b e operating a n d m u s t b e 'thermally transparent' i n o r d e r f o r a t h e r m o g r a p h i c survey to b e a b l e to s e e t e m p e r a t u r e changes. Important note: it is recommended that persons refer to the requirements of the EAWR and the HSE's guidance in HSR25 prior t o undertaking any work activity which places themselves or those under their control in close proximity to live parts. 144 G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology 4 It is relatively easy to make arrangements to disconnect small installations, such as those at domestic premises, f r o m the supply, to facilitate periodic inspection and testing. However, asthe size and complexity of an installation increases, isolation f r o m the supply becomes increasingly difficult. This is particularly true where continuity of supply has health implications, as may b e the case in hospitals and similar premises, or financial implications, as would b e the case in banks, share-dealing and commodities markets, and t h e like. Nevertheless, i t remains necessary to confirm the continuing of such installations suitability for use. Therefore, they must still b e subjected to planned and preventative maintenance or regular periodic assessment of their condition. It may well b e possible to carry o u t a thorough visual inspection of such installations without subjecting the inspector or others in t h e building to any danger, and such an inspection may identify many common defects caused by use/abuse. Furthermore, experience of such installations may provide a valuable insight into commonly occurring cases of wear a n d tear. Some defects, however, cannot b e discovered by visual inspection alone. For example, incorrectly tightened connections can result in a high resistance joint, which can t h e n cause a high temperature to occur locally to t h e connection. If left uncorrected over time, further deterioration of t h e connection may well occur, leading to a continuing increase in temperature, which may subsequently present a risk of fire. This fire risk will b e significantly increased in installations where a build-up of dust or other flammable materials can occur in close proximity to the source of heat. It should also b e remembered that increased heat at terminations can result in accelerated deterioration of the insulation locally. Heating effects symptomatic of a fault or other problem within an electrical installation can also occur as a result of cyclical-load operations, use of conductors of inadequate current-carrying capacity, incorrect load balancing and more mechanically related issues, such as incorrect alignment of motor drive couplings and overtightened belt-drives. A number of manufacturers offer infrared imaging equipment which can b e used to identify such ’hot spots'. Infrared thermography works o n t h e principle that all materials emit electromagnetic radiation in the infrared region, which can b e detected by a thermal imaging camera. The amount of radiated energy detected can b e presented in a readily usable form, typically being shown as differences in colour that vary with the temperature being detected. Figure 4.1 shows a colour/temperature correlation indicator such as those that may accompany images. Such scales will aid the person ordering t h e inspection or responsible for maintenance activities in their interpretation of t h e thermal images. Guidance Note 3: Inspection & Testing © The Institution of Engineering and Technology 145 4 ▼ Figure 4 . 1 A colour/ temperature correlation indicator In terms of visual inspection, t h e busbar connections in Figure 4.2 appear to be satisfactory. However, if the same connections are viewed using a [ thermal imaging camera (Figure 4.3), it is evident that t h e connections to t h e centre are running significantly 160.0 - hotter than those to either side. 150.0140.0 - This higher temperature may indicate a loose connection 130.0 - or connections, but in this case is probably d u e to the 120.0 - | centre bar carrying a significantly higher current than those to either side of it. The person carrying out the inspection 110.0 - " could suggest that their client looks into improving t h e 100.0 -■ load balancing of this part of the installation. | <99.3°F 1 ▼ Figure 4.2 Bolted connections at a busbar as seen by the eye In a further example, Figure 4.4 shows a contactor with t h e thermal image highlighting a potential loose termination. After this has been tightened, Figure 4.5 shows the result, with all three terminations now operating at a m u c h more uniform temperature. Whilst such remedial work is being carried out, it is sensible to inspect t h e insulation of t h e conductors i n t h e terminations to confirm that the insulation remains ▼ Figure effective and has not suffered significant damage. 4.3 Bolted connections at a busbar viewed using thermal imaging The requirements of the EAWR m u s t b e taken into account w h e n considering t h e use of thermographic surveying equipment, as its use may necessitate t h e temporary removal or bypassing of measures that provide basic protection (as defined in BS 7671), such as opening doors to electrical panels and/or t h e removal of barriers and covers. The requirements of Regulation 14 of t h e EAWR (Work o n or near live conductors), which is ▼ F i g u r e 4 . 4 Thermal image of contactor showing termination on right is too hot 2200- reproduced as follows, are particularly pertinent: "No person shall b e engaged in any work activity on or so near any live conductor (other than one suitably covered with insulating material so as t o prevent danger) that danger may arise unless - XBQfOOib 1SJ0- (a) it is unreasonable MOOt200- in all the circumstances for it to be dead; and ttuo- (b) it is reasonable in all the circumstances for him to ▼ F i g u r e 4 . 5 Thermal image of contactor after loose termination has been tightened 0FL1R 220 C-if] m-|J MOO' 1200' icoo- 146 Guidance N o t e 3: Inspection & Testing © The Institution of Engineering and Technology be at work on or near it while it is live; and (c) suitable precautions the provision (including o f suitable are taken to prevent injury" where protective necessary equipment) 4 HSR25 recognizes that it may b e necessary, in some circumstances, for conductors to remain live during testing or diagnostic work. However, such work in close proximity to live conductors may only b e carried out if it can b e done safely and if all precautions required to allow it to b e done so are put in place. Additionally, the work m a y only b e performed by persons w h o are suitably competent with regard to the type and nature of the work activity being performed, as required by Regulation 16 of the EAWR (Persons to be competent to prevent danger or injury). HSR25 also makes clear that although live testing may b e justifiable, it does n o t follow that there will necessarily b e justification for subsequent repair work to b e carried out live. Persons carrying out thermographic surveying should: (a) have sufficient competence to prevent danger and injury. (b) understand the system being worked on, t h e hazards that may arise as a result of t h e work and t h e precautions that are required to prevent danger. being inspected which are, or are (c) b e able to identify those parts of equipment capable of being, live when the supply to the equipment is switched on. (d) implement all precautions required to prevent injury that have been identified as part of t h e risk assessment for the work. (e) maintain the maximum possible distance f r o m the live or potentially described above at all times. (f) maintain effective control of the area in which the equipment live parts being inspected is situated. (g) ensure that all protective measures that m a y have been affected by their actions when carrying out t h e inspection work are fully reinstated. All guards and barriers must b e replaced and panel doors, lids and covers must b e closed and secured properly after t h e inspection is completed. As previously mentioned, thermographic inspection can b e an effective m e t h o d of identifying potential defects that may not be identified by a more conventional visual inspection. However, such thermal surveying should not b e seen as a substitute for periodic inspection and testing, but rather as an additional tool that can b e used by t h e inspector. Thermographic surveys can b e a highly effective means of targeting preventative maintenance where it is m o s t required. Defects identified may b e factored into the planned maintenance programme for t h e installation, or, where necessary, may justify the remedial work being performed without delay. Guidance Note 3: Inspection & Testing © The Institution of Engineering and Technology 147 NOTES 148 G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology Forms This section provides guidance on completing the necessary schedules, certificates and reports associated with inspection and testing. Sample certificates a n d report, completed with typical entries, are provided, together with sample Schedules of Inspection, Circuit Details and Test Results, again completed The section also contains some notes on completion with typical results. of the forms, although helpful information on this will also b e gained by reading earlier sections of this Guidance Note. 5.1 Initial verification (inspection and testing) forms Following the initial verification of a new installation o r of an addition or alteration to an existing installation, an Electrical Installation Certificate (EIC) or Minor Electrical Installation Works Certificate (MEIWC) is required to b e completed and issued, together with inspection schedule(s) and test result schedule(s). (a) Form 1 : EIC (three-signatory version from Appendix 6 of BS 7671). When an EIC is used, appropriate numbers of t h e following forms are required to accompany the Certificate: (b) Form 2: Schedule of Inspections for domestic and similar premises with u p to 100 A supply, or a more extensive schedule where necessary (see below). (c) Form 3: generic Schedule of Test Results. 642.3 Form 2 is not suitable for the inspection of installations rated at more than 100 A or that are more complex. For such installations, t h e inspector will probably need to formulate their own inspection schedules. These should b e based o n the requirements of Regulation 642.3 and t h e list of examples of items requiring inspection during initial verification, given i n Appendix 6 of BS 7671. For completeness, two samples of typical completed Form 3 s (Schedule of Circuit Details and Test Results) are included here, one being for a single-phase installation a n d the other for a three-phase installation. Guidance N o t e 3 : Inspection & Testing © The Institution of Engineering and Technology 149 5 5.2 Minor works The complete set of forms for initial verification (inspection and testing) may not b e necessary for minor works. When an addition to a n electrical installation does not extend to the installation of a n e w circuit, t h e MEIWC may b e used. This one-page certificate is intended for such work as the addition of a socket-outlet o r lighting point to an existing circuit, or for a repair or modification to each circuit worked on. Where multiple circuits are worked on, all of the work could b e detailed on a n EIC. A MEIWC must not b e used for t h e replacement of a consumer unit. The MEIWC (Form 4) is included here, taken from Appendix 6 of BS7671. Notes o n completion and guidance for recipients are provided with the form. 5.3 Periodic inspection and testing The inspection and testing of an existing electrical installation is reported o n using an EICR(Form 5). As with an EIC, this document is issued with the appropriate number of generic Schedule(s)of Circuit Details and Test Results (Form 3). For periodic inspections, the Schedule of Inspections for initial verification (Form 2) should not b e used. The dedicated model suggested in BS7671 (Form 6) may b e used for inspections of domestic installations a n d installations up to 1 0 0 A. For larger and m o r e complex installations, t h e inspector will need to formulate bespoke inspection schedules. These should be based on the requirements of Regulation 642.3 and t h e list of examples of items requiring inspection for an EICRwhich are applicable, given in Appendix 6 of BS7671. 150 Guidance Note 3: Inspection & Testing © The Institution of Engineering and Technology 5 5.4 Examples of completed model forms for certification and reporting ▼ Figure 5.1 Example Electrical Installation Certificate (EIC) (page 1) ELECTRICAL INSTALLATION CERTIFICATE (REQUIREMENTS FOR ELECTRICAL INSTALLATIONS - BS 7671) Certificate No.: ...555514 DETAILS OF THE CLIENT Galbraith ...instruction St, Paul's VJag K Leeds LSg. OMCj ....................................................................... INSTALLATION ADDRESS , , .x , _ _ , _ , „ . _ x Un/t 3 , The Quadrant, Sovnetown Business .......................................Park, .Sawetawn..SL1.QZZ....................................................................... DESCRIPTION AND EXTENT OF THE INSTALLATION Description of installation: Complete electrical installation, New installation |?[ Addition to an existing installation i—i Alteration to an existing installation |—| new Z-floor office building Extent of installation covered by this Certificate: Complete electrical installation, comprising main switchboard, submains and distribution boards. To include all power and lighting circuits, excluding car park lighting (supplied from adjacent building) (Use continuation sheet if necessary) u _______See continuation sheet No: ........ FOR DESIGN l/We, being the person(s) responsible for the design of the electrical installation (as indicated by my/our signatures below), particulars of which are described above, having exercised reasonable skill and care when carrying out the design, hereby CERTIFY that the design work for which l/we have been responsible is to the best of my/our knowledge and belief in accordance with BS 7671:2018, amended to .ZQZZ(date) except for the departures, if any, detailed as follows: Details of departures from BS 7671 (Regulations 120.3, 133.1.3 and 133.5): Details of permitted exceptions (Regulation 41 1.3.3). Where applicable, a suitable risk assessment(s) must be attached to this Certificate. Risk assessment attached The extent of liability of the signatory or signatories is limited to the work described above as the subject of this Certificate. For the DESIGN of the installation: Signature: ...... ............ Signature: .................................. **(Where there is mutual responsibility for the design) Date: 7/C?7/ >22Name (IN BLOCK LETTERS): ...... P. Date: ............... ............................ Designer No 1 Name (IN BLOCK LETTERS): .................................................. Designer No 2** FOR CONSTRUCTION I, being the person responsible for the construction of the electrical installation (as indicated by my signature below), particulars of which are described above, having exercised reasonable skill and care when carrying out the construction hereby CERTIFY that the construction work for which I have been responsible is to the best of my knowledge and belief in accordance with BS 7671:2018, amended to P. -.(date) except for the departures, if any, detailed as follows: Details of departures from BS 7671 (Regulations 120.3 and 133.5): None The extent of liability of the signatory is limited to the work described above as the subject of this Certificate. For CONSTRUCTION of the installation: Signature: .......... Date: .P.7/. 2 Name (IN BLOCK LETTERS): .......P.kLNNETH..................... Constructor FOR INSPECTION & TESTING I, being the person responsible for the inspection & testing of the electrical installation (as indicated by my signature below), particulars of which are described above, having exercised reasonable skill and care when carrying out the inspection & testing hereby CERTIFY that the work for which I have been responsible is to the best of my knowledge and belief in accordance with BS 7671:2018, amended to2Z?.2r£.(date) except for the departures, if any, detailed as follows: Details of departures from BS 7671 (Regulations 120.3 and 133.5): None The extent of liability of the signatory is limited to the work described above as the subject of this Certificate. For INSPECTION AND TESTING of the installation: Signature: ............. Date:27/O7/2C>22Name (IN BLOCK LETTERS): ....... ....................... Inspector NEXT INSPECTION l/We, the designer(s), recommend that this installation is further inspected and tested after an interval of not more than ...... Guidance Note 3: Inspection & Testing © The Institution of Engineering and Technology 151 5 ▼ Figure 5 . 2 Example Electrical Installation Certificate (EIC) (page 2) Certificate No.: PARTICULARS OF SIGNATORIES TO THE ELECTRICAL INSTALLATION CERTIFICATE Designer (No 1) N a m e ; P JpnfcS Company: Address: .... E A.tejp rise . Way,. . .............................................................................................. .......................................................................... Postcode: Tel No: .... . Designer (No 2) (if applicable) /A. Company: Address; Tel No: Postcode: Constructor R Ngme; ................................ Company: ........................................ Address: . .. . P. Clt .ScQtlavyd ................................................................ Postcode: .EH&k-.&QU. Tel No: Inspector Name: Address: Company: Electrics .................................... g SUPPLY CHARACTERISTICS AND EARTHING ARRANGEMENTS Supply Protective Device Nature of Supply Parameters Number and Type of Live Earthing Conductors ______ arrangements m AC 0 DC TN-C Nominal voltage, U I Uo <K?.C?Z2;3C?V BS(EN) 1 -phase, 2-wire 2-wire TN-S Nominal frequency, 5Q. ...... Hz Type ........... U. ............... 2-phase, 3-wire 3-wire TN-C-S Prospective fault current, l p / 2J kA Rated current ...7PP. A 3-phase, 3-wire Q, Other TT External earth fault loop impedance, Ze(2) P.:P.P.. Q 3-phase, 4-wire [V] IT (Note:(1) by enquiry (2) by enquiry or by measurement) Confirmation of supply polarity 0 Other sources of supply (as detailed o n attached schedule) N/A PARTICULARS OF INSTALLATION REFERRED TO IN THE CERTIFICATE Maximum Demand Means of Earthing ....................................................................... -kWW Amps (Delete as appropriate) Maximum demand (load) Distributor’s facility [Zf Details o f Installation Earth Electrode (where applicable) Type (e.g. rod(s), tape etc) N/A.. Installation earth Location electrode Q Electrode resistance to Earth Main Protective Conductors ___________________ g. Ef ~| Earthing conductor Main protective bonding conductors Material ....... csa 7.P...... mm 2 Connection / continuity verified [Zf .. . . Copper Material ........... L.C csa 7.P..... mm 2 Connection / continuity verified [Zf To gas installation pipes IZl | To oil installation pipes EN/4 To structural steel N/A Toother Specify .N/A ............................................................................................................... To wateZinstallation pipes To lightning protection N/A Location . BS(EN) No of poles . SWftf hroovyy A A V If RCD main switch RCD Type NZA .................... Rated residual operating current (l An) Rated time delay Measured operating time Current rating ..7.QP. Fuse / device rating or setting Voltage rating ..4PP .NZA Outcome Z / N/A Item No. Description 8.0 9.0 10.0 Circuits (Distribution and Final) Isolation and switching Current-us equipment (permanently connected) 4........ .mA .ms .ms Schedule of Inspections Item No. 1.0 2.0 3.0 Description 1 Condition of consumer's intake equipment (Visual inspection only) ' z 1 Parallel or switched alternative sources of supply Protect! measure: Automatic Disconnection of Supply (ADS) N/A Bas protection 4.0 5.0 ___ Protective measures other than ADS __________ 6.0 Addition protection 7.0 Distributi equipment Z z z z z Outcome Z/n/A 11.0 Identification and notices z z z 12.0 13.0 Location(s) containing a bath or shower Other special installations or locations N/A N/A 14.0 Prosumer's low voltage electrical installation(s) N/A COMMENTS ON EXISTING INSTALLATION (in the case of an addition or alteration see Regulation 644.1 .2): ...None................................................................................................................................................................ SCHEDULES This Certificate is valid only when. .Schedules of Circuit Details and Test Results are attached. (Enter quantities of schedules attached). ELECTRICAL INSTALLATION NOTES (from 1 B S 7671) The Electrical Installation • the initial certification a n existing installation • t h e replacement • certifying works CERTIFICATE is t o b e u s e d f o r : of a new installation or f o r a n addition where have been new circuits of a c o n s u m e r unit/distribution for where to the Certificate there are multiple existing installation alternative to the issue of multiple 152 Guidance Note 3: Inspection & Testing © The Institution of Engineering and Technology which d o not introduced, board, additions, o r alteration or or or alterations extend to to new or remedial circuits as a n Minor Electrical Installation Works Certificates. 5 It i s not to be u s e d f o r a periodic Installation inspection C o n d i t i o n R e p o r t should and testing, f o r which b e u s e d . For a n addition a n Electrical or a l t e r a t i o n which d o e s n o t e x t e n d t o t h e i n t r o d u c t i o n of n e w circuits, a M i n o r Electrical I n s t a l l a t i o n Works Certificate m a y b e used. The 'original' Certificate is to be issued to the person ordering the work (Regulation 644.4). A duplicate 2 to 3 should b e r e t a i n e d by the p e r s o n issuing the certificate. T h i s C e r t i f i c a t e is o n l y valid if t h e S c h e d u l e o f I n s p e c t i o n s h a s b e e n c o m p l e t e d c o n f i r m t h a t all r e l e v a n t i n s p e c t i o n s h a v e b e e n c a r r i e d o u t a n d w h e r e accompanied by S c h e d u l e ( s ) of Circuit Details The signatures appended a r e those e x e c u t i n g t h e w o r k of design, a n d Test Results. of the p e r s o n s a u t h o r i z e d by the companies c o n s t r u c t i o n , i n s p e c t i o n a n d t e s t i n g respectively. A s i g n a t o r y a u t h o r i z e d t o c e r t i f y m o r e t h a n o n e c a t e g o r y o f w o r k s h o u l d sign i n each of t h e a p p r o p r i a t e p l a c e s . ( W h e r e a single Certificate is used, construction, 4 the inspection person authorized a n d testing The time interval recommended for signature executing Electrical I n s t a l l a t i o n the design, before the first periodic inspection must be inserted. T h e p r o p o s e d d a t e f o r t h e n e x t i n s p e c t i o n s h o u l d t a k e into consideration t h e f r e q u e n c y a n d q u a l i t y of maintenance t h a t t h e installation c a n reasonably b e e x p e c t e d t o receive life, should during b e t w e e n t h e designer, 5 w o r k of shall sign the certificate.) its intended a n d the period b e agreed installer a n d o t h e r r e l e v a n t p a r t i e s . T h e p a g e n u m b e r s f o r t h e S c h e d u l e ( s ) of Circuit D e t a i l s a n d Test Results s h o u l d b e indicated, together with the total n u m b e r of pages a s s o c i a t e d with the c e r t i f i c a t i o n provided. 6 T h e m a x i m u m p r o s p e c t i v e v a l u e of f a u l t c u r r e n t (I P f) recorded s h o u l d b e the g r e a t e r of e i t h e r t h e p r o s p e c t i v e v a l u e of s h o r t - c i r c u i t c u r r e n t o r t h e p r o s p e c t i v e value of e a r t h f a u l t current. GUIDANCE F O R RECIPIENTS (to b e appended t o the C e r t i f i c a t e ) T h i s s a f e t y C e r t i f i c a t e h a s b e e n i s s u e d t o c o n f i r m t h a t t h e e l e c t r i c a l installation w o r k t o which with it relates h a s been designed, constructed, inspected and tested in a c c o r d a n c e BS 7671. Y o u s h o u l d h a v e r e c e i v e d a n 'original' C e r t i f i c a t e a n d t h e p e r s o n t h a t i s s u e d t h e Certificate should have r e t a i n e d a duplicate. but not the o w n e r of the installation, If you were the person you should it i n c l u d i n g the s c h e d u l e s , immediately ordering p a s s this Certificate, to t h e owner. T h e 'original' C e r t i f i c a t e s h o u l d b e r e t a i n e d i n a safe p l a c e a n d b e shown inspecting o r undertaking f u r t h e r work you later v a c a t e t h e property, the work, o r a f u l l copy of on t h e e l e c t r i c a l installation to a n y p e r s o n i n the future. t h i s C e r t i f i c a t e will d e m o n s t r a t e t o the new owner If that t h e e l e c t r i c a l i n s t a l l a t i o n c o m p l i e d w i t h t h e r e q u i r e m e n t s of B S 7 6 7 1 a t t h e t i m e t h e C e r t i f i c a t e w a s i s s u e d . T h e C o n s t r u c t i o n (Design require that, f o r a p r o j e c t covered together with schedules, by those a n d Management) Regulations, is i n c l u d e d i n t h e project a copy Regulations of this Certificate, h e a l t h a n d safety documentation. For safety reasons, t h e electrical installation will n e e d to b e inspected at appropriate intervals by a skilled person recommended or persons, competent before the next inspection in such work. The maximum time interval is stated on Page 1 under 'NEXT INSPECTION'. G u i d a n c e N o t e 3 : I n s p e c t i o n & Testing © The Institution o f Engineering and Technology 153 This Certificate is intended to b e issued only for a new electrical installation or for new work associated with an addition or alteration to an existing installation. It should not have b e e n issued for t h e inspection and testing of an existing electrical installation. An "Electrical Installation Condition Report" should b e issued for such an inspection. This Certificate is only valid if the Schedule of Inspections has been completed to confirm that all relevant inspections have been carried out and where accompanied by Schedule(s) of Circuit Details a n d Test Results. Where the installation includes a residual current device (RCD) it should b e tested six-monthly by pressing the button marked T or 'Test'. The device should switch off the supply and should then be switched on to restore the supply. If the device does not switch off the supply when the button is pressed, seek expert advice. For safety reasons it is important that this instruction is followed. Where the installation includes an arc fault detection device (AFDD) having a manual test facility it should b e tested six-monthly by pressing the test button. Where a n AFDD has both a test button and automatic test function, manufacturer's b e followed instructions shall with respect to test button operation. Where the installation includes a surge protection device (SPD)the status indicator should b e checked to confirm it is in operational condition i n accordance with manufacturer's information. If t h e indication shows that t h e device is not operational, seek expert advice. For safety reasons it is important that this instruction is followed. Where the installation includes alternative or additional sources of supply, warning notices should b e found at the origin or meter position, or if remote f r o m the origin, at the consumer unit or distribution board and at all points of isolation of all sources of supply. 154 G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology Generic schedule of circuit details for a single-phase installation ▼ Figure 5 . 3 E x a m p l e S c h e d u l e of C i r c u i t Details (single-phase installation) GENERIC SCHEDULE OF CIRCUIT DETAILS Certificate/Report number:.. "?. Distribution board details Consumer DB reference: Location: Under stairs cupboard Supplied from: Supply meter Unit Distribution circuit OCPD: BS (EN): SPD Details: Type(s)*: T1 1361 T2 gf _________ Type: t T3 D H 80 Rating/Setting: A N/AD CIRCUIT DETAILS 102# 8 2x2.5 1.5 61001 A A A 1 1O1# 7 2x6.0 2X1.0 2.5 1.0 61001 61001 A A 1OO# 7 7 Lights - downstairs Lights - garage 8 7 2X1.0 2X1.0 1.0 1.0 8 SPARE - - - 5* Guidance Note 3: Inspection & Testing © The Institution of Engineering and Technology <c> socket- outlets - B B B 32 6 6 32 1.37 1.37 14 61001 61001 Rating (A) Maximum permitted Zs (Q)§ Breaking capacity (kA) Rating (A) - A Cooker - kitchen Lights - upstairs 61001 61001 O Ring - kitchen 4 102# ID cpc (mm 2) 3 2 Type Live (mm2) BS (EN) o> 00 Number of points served cn Reference method* Type of wiring w 1.5 1.5 (D IS 2X2.5 2X2.5 102.# (Viu) "’i IO 8 A A ? 2 Number & size Ring - downstairs socket- outlets Ring - upstairs socket- outlets 1 RCD (N3) sa Circuit description Overcurrent protective device ______ Circuit number Conductor details A 30 32 A 39 32 32 6 1.37 61001 A 39 32 B B 32 1.37 61001 61001 A 39 32 6 6 6 A 50 6 61001 61001 B B 6 6 6 6 7.28 61001 61001 A 7.28 A 50 50 6 6 - - - - - - - - - 7.28 CODES FOR TYPES OF WIRING A Thermoplastic insulated/ s h e a t h e d cables c B Thermoplastic cables metallic conduit in Thermoplastic non-metallic D cables in conduit Thermoplastic cables metallic trunking F E in Thermoplastic non-metaliic cables i n trunking G H 0 Other Thermoplastic SWA cables Thermosetting SWA cables Mineral - please state insulated cables 155 * SPDType. Where a combined T1 + T2 orT2 + T3 device is installed, indicate by ticking both Type boxes. t Where a T3 SPD is installed to protect sensitive equipment, enter details in Remarks’, column 31 , of the Schedule of Test Results. (See Section 534 of BS 7671;2018+A2:2022.) t See Table 4A2 of Appendix 4 of BS 7671 :2018+A2:2022. § Where the maximum permitted earth fault loop impedance value slated in column 12 is taken from a source other than the tabulated values given in Chapter 41 of BS 7671 :2018+A2:2022, state the source of the data in the appropriate cell for the circuit in the ‘Remarks’, column 31, of the Schedule of Test Results. 5 Generic schedule of circuit details - Notes The fields of the f o r m are used as follows: 1 The circuit number as marked o n the distribution board or consumer unit. The normal convention for single-phase distribution boards and consumer units, circuit 1 is closest to t h e main isolator of the assembly. For single-phase circuits in three-phase installations, it is preferred to use the designation L I , L2, L3. For example, for single-phase circuits in the fifth compartment, the designation would b e 5L1, 5L2 and 5L3. 2 3 Brief description of t h e circuit. The type of wiring is identified by a code, following b o t t o m of t h e form. 4 The reference method is identified 5 BS 7671. The number of points served is the total number according the convention at t h e to Table 4 A 2 in Appendix 4 of of accessories or other connection points for current-using or generating equipment. A double or triple socket-outlet to BS 1363-2 is usually considered to b e a single point. 6 Number and size of live conductors. this should also b e identified example: • • Where the conductors using the chemical are not copper, symbol in this column. For 2x1.5 indicates two copper live conductors with cross-sectional area 1.5 m m 2 ; 4 x 1 6 Al indicates four aluminium live conductors with cross-sectional area 1 6 m m 2. 7 Number and size of cpc. Where the conductors are not copper, this should also b e identified using the chemical symbol in this column. 8 9 Number of the standard for the overcurrent protective device, for example: • ’ 6 0 8 9 8 ' for an MCB to BS EN 60898; • ' 3 0 3 6 ' for a re-wireable fuse BS 3 0 3 6 . Type of overcurrent protective device, where applicable. For example, B, C or D for MCBs and RCBOsto BS EN 6 0 8 9 8 or BS EN 61009. 10 Rated operating current l n of the overcurrent protective device. 11 Rated breaking capacity o f t h e overcurrent protective device. 12 Maximum permitted earth fault loop impedance Z s of the circuit for automatic disconnection of supply. These figures are usually obtained f r o m Tables 41.1 to 41.6 in BS 7671 (see Appendix A). Where table 41.5 of BS 7671 applies for TT systems served by a public supply, an earth fault loop impedance exceeding 2 2 5 Q is unlikely to b e acceptable, as this implies the earth electrode resistance is unlikely to b e stable as indicated in the Note to Table 41.5 of BS 7671. 13 Number of the standard for the RCD protecting the circuit (if any), for example '610009' for an RCBO to BS EN 61009. 14 Type of t h e RCD protecting t h e circuit (if any), either 'AC','A’,'F' or 'B'. 15 Residual current rating of the RCD protecting the circuit (if any). 16 Maximum operating current of t h e RCD protecting the circuit (if any). 156 G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology Generic Schedule of Test Results for a single-phase installation ▼ Figure 5 . 4 E x a m p l e S c h e d u l e of Test Results (single-phase installation) GENERIC SCHEDULE OF TEST RESULTS Certificate/Report number: . . . Details of test instruments used (serial and/or asset numbers) Distribution board details 0.2 db Correct polarity gf SPD: Operational status confirmed | Multifunction: S e r 1020304 Continuity: _ _ ____ _______N/A _ _________________ _ _ _ Insulation resistance: N/A Earth fault loop impedance: N/A RCD:. . . .............................. N/A Earth electrode resistance: _N/A ..... ........................... ............ 0 . 2 kA pf Phase sequence [?f N/A TEST RESULT © g g § 8 ™ 500 >999 N/A N/A 500 >999 >999 500 >999 >999 2 0.62 0.62 1.02 0.41 3 0.22 0.22 0.37 0.15 4 N/A N/A N/A N/A 0.16 5 N/A N/A 2.56 6 N/A N/A 7 N/A N/A N/A N/A 1.57 N/A N/A 8 N/A 8.20 N/A N/A N/A N/A N/A >999 500 >999 >999 250 N/A >999 500 >999 >999 500 >999 >999 N/A N/A N/A J J Y J N/A CO Disconnection N/A 0) 5 Maximum measured 0.41 22 > 0.71 28 ro 1.02 u? 1 M O> Polarity# 0.62 CJ1 Live - Earth (MQ) r n (neutral) 0.62 w Test voltage (V) 00 r, (line) (0) 1 24 Q. 20 RCD Z.(O) (R 1 + R 2) or R 2 (R, + R 2 ) =4 Circuit number Ring final circuit Insulation resistance AFDD time (ms)** Continuity (Q) DETAILS 0.71 36 </ 0.44 25 J N/A N/A J N/A N/A N/A N/A N/A 0.46 34 2.85 29 2.86 33 1.90 31 N/A N/A N/A CD -I f o Q THOMPSON o I <8 Signature: G Date: 1S/O7/ fl Not all SPDs have visible functionality indication. # Where this schedule is issued with an Electrical Installation Condition Report, and incorrect polarity is identified, an 'X' should be entered. ** RCD effectiveness is verified using an alternating current test at rated residual operating current (lAn)ft Not all AFDDs have a test button Remarks Include details of circuits and/or installed equipment vulnerable to damage when testing (continue on a separate sheet if necessary) 31 N/A <§• Tested by name (Capitals): Manual test button operation Confirmed: q o Unit £1 Test button operation Consumer to LD DB reference: 2.022 Circuit S insulation 2.50 V (L+N)-E due to LEO drivers High Zs on U/S lighting (circuit 6) found to be due to loose terminals at the point of connection of additional lighting circuitry. With the additional circuitry disconnected } a satisfactory Zs of 2.86 O. was obtained. Conductors remain damaged and cabling requires replacement. 58 Form 2 Generic Schedule o f Circuit Details f o r a three-phase installation installation) GENERIC SCHEDULE OF CIRCUIT DETAILS Certificate/Report number:..5*333 7 3 Distribution board details DB reference: Location: Distribution circuit OCPD: BS (EN): SPD Details: Type(s)*: T 1 Switch 88-3 T2 gf Room Type: f T3 D Supplied from: Supply Rating/Setting: 80 meter A N/A CIRCUIT DETAILS o Rating (A) Breaking capacity (kA) Maximum permitted Z s (Q)§ £ Type B 1 4x2.5* 1X10 608 9 8 B 6 IO 7.28 N/A N/A N/A N/A E B 14 2x4.0 1X1.5* 61009 B 32 IO 1.37 61009 A 30 32 A A N/A 30 16 30 32 N/A N/A A N/A 30 32 N/A N/A co BS (EN) 00 o» Number of points served C U1 Type floor North cpc (mm 2) - ground Live (mm2) SPPs R/ng Reference method* 1 2.L1 15 ~~ Number & size co 2 RCD (ns) sa Circuit description Overcurrent protective device Type of wiring Conductor details Circuit number Guidance Note 3 : Inspection & Testing © The Institution of Engineering and Technology ▼ Figure 5 . 5 Example Schedule of Circuit Details (three-phase 2.L2. External lighting G C&P 16 2x2.5* 1X2-5* 61009 B 16 IO 2.73 61009 2L3 Radial - Kitchen A 102# 7 2X4.0 1X1.5* 61009 B 32 IO 1.37 61009 3L1 Lighting C B 23 2X2.5* 1X2.5* 608 9 8 B 16 IO 2.73 N/A 3L2 Ring 1.37 61009 Lighting 32 16 IO 3L3 IO 2.73 N/A 4L1 Radial - fire - ground - ground floor South & Circulation floor South QC E B 1X1.5* 61009 B B 14 27 2x4.0 C 2X2.5* 1X2. 5 608 9 8 B B 1 2x2.5* 1X2.5* 608 9 8 B IO IO 4.37 N/A N/A B 8 2X4.0 1x1.5 61009 B 32 IO 2.73 61009 N/A A N/A floor Receptions Circulation B E 30 32 B&D B 5* 2X4.0 1X1.5 60898 B 20 IO 2.19 N/A N/A N/A N/A E 1 4X2.5* 1x22 Fe 60947-2 C 25* IO 0.87 60947-2 B 30 25* floor North alarm 412 Ring 4L3 Radial - a/c plant room ___5 Laundry 6 I 16 & Reception - ground - ground 1 - 3ph washing a machine SPARE CODES FOR TYPES OF WIRING B A Thermoplastic sheathed insulated/ cables Thermoplastic cables in metallic conduit c Thermoplastic non-metallic D cables in conduit Thermoplastic cables metallic trunking E in Thermoplastic non-metallic F cables in trunking G H 0 Other Thermoplastic SWA cables Thermosetting SWA cables Mineral insulated - please state cables * SPD T)pe. Where a combined T1 + T2 or T2 + T3 device is installed, indicate by ticking both Type boxes. •f Where a T3 SPD is installed to protect sensitive equipment, enter details in ‘Remarks', column 31, of the Schedule of Test Results. (See Section 534 of BS 7671:201 8+A2:2022. ) t See Table 4A2 of Appendix 4 of BS 7671 ;2018+A2:2022. § Where the maximum permitted earth fault loop impedance value stated in column 12 is taken from a source other than the tabulated values given in Chapter 41 of BS 7671:201 8+A2:2022, state the source of the data in the appropriate cell for the circuit in the ‘Remarks’, column 31, of the Schedule of Test Results. Form 3 Generic Schedule of Test Results for part of a three-phase installation ▼ Figure 5 . 6 E x a m p l e Schedule of Test R e s u l t s (three-phase installation) GENERIC SCHEDULE OF TEST RESULTS Certificate/Report number: Distribution b o a r d details 575. Details of test instruments u s e d (serial and/or asset n u m b e r s ) D B reference: .....QBX ............. Z db ____O»3O Confirmed: Correct polarity |Vf SPD: Operational status confirmed ______ __________ Q I f ____ 0,8 __ ... _____ M ultifu notion: ................. ....... . .Ser 1022305 Continuity: ................ N/A Insulation resistance: N/A E a r t h fault l o o p impedance: N/A RCD: ..... _ N/A Earth electrode resistance: ..... ..... N/A kA P h a s e sequence [Vf |Vf N/A ..................... ....... ......... TEST RESULT DETAILS 3L2 0.51 3L3 N/A N/A 5 Manual test button operation+t N/A N/A N/A N/A N/A 250 500 250 500 250 500 250 >999 >999 >999 N/A >999 >999 >999 N/A >999 >999 >999 N/A 0.52 N/A 0.42 N/A 1.15 N/A 0.42 N/A 500 500 500 500 >999 >999 >999 >999 >999 >999 >999 >999 CD O 26 J / 31 N/A N/A 0.91 52 1.65 22 J 23 O.S4 1 . 3 2 N/A N/A J 25 0.92 0 . 2 1 N/A N/A N/A N/A N/A N/A N/A N/A N/A Insulation 250 V (Ll+L2 L3-t-N)-E: SPDs in circuit * Y / </ J / J M a x i m u m measured Live - Earth ( M Q ) U1 N/A 1.39 N/A N/A NJ N/A N/A N/A 1.20 N/A X.8X Live - Live ( M Q ) N/A N/A Test voltage (V) 22 0.00 0.61 1.35 0.54 1.02 0.62 0.51 W 21 0.00 NJ r 2 (cpc) rn (neutral) N/A 0.51 N/A N/A o Guidance Note 3: Inspection & Testing s Institution of Engineering and Technology 3 LX N/A N/A N/A N/A 0.67 N/A of * AFDD Test button operation © 0.00 0.65 of + RCD Z,(Q) (R. + R J o r R 2 o 0.00 0.65 2L1 2.L2. N/A 2.L3 N/A 3 L 1 N/A 0.67 3L2 3L3 N/A 1 <D 2 r, (line) (0) Circuit n u m b e r R i n g final circuit Insulation resistance 0.30 Disconnection t i m e (ms)** Continuity ( Q ) Remarks Include details of circuits and/or installed equipment vulnerable to d a m a g e w h e n testing (continue o n a separate s h e e t if necessary) Insulation 250 V (L.+N)-E: dawn to dusk sensors Insulation 250 V (L N)-E: PIRs in circuit * Insulation 250 V (L+N)-E: PIRs in circuit 0 . 2 2 N/A N/A N/A 0.72 21 N/A 1.36 N/A N/A N/A J 0.20 34 N/A 6 Tested by n a m e (Capitals): Signature: 6? WILSON Date: 2 2 Ju ly 2022 159 U Not all SPDs have visible functionality indication. # Where this schedule is issued with an Electrical Installation Condition Report, and incorrect polarity is identified, an 'X' should be entered. ** RCD effectiveness is verified using an alternating current test at rated residual operating current ( lAn ). tt Not all AFDDs have a test button * Cables for these circuits were tested at 500 V L-L, L - N , L-E and N-E as appropriate, prior to connection of sensitive equipment in circuit. All readings > 9 9 9 Mil. 5 GENERIC SCHEDULE OF TEST RESULTS NOTES The following notes relate to the column number in the f o r m (Form 3). 17 The circuit number as marked o n t h e distribution board or consumer unit. The normal convention for single-phase distribution boards and consumer units, circuit 1 is closest to t h e main isolator of t h e assembly. For single-phase circuits in three-phase installations, it is preferred to use the designation LI, L2, L3. For example, for single-phase circuits in the fifth compartment, the designation would b e 5L1, 5L2 and 5L3. 18 Ring line-line open resistance continuity in Q : see Section 2.6.6. 19 Ring neutral-neutral open resistance continuity in Q: see Section 2.6.6. 20 Ring cpc-cpc open resistance continuity in Q : see Section 2.6.6. 21 Ring (R] + R2) : enter the highest value recorded while carrying out step 3 of t h e ring continuity test (see Section 2.6.6). Note that where meaningless results are recorded, due to parallel return paths, and it has been established and t h e inspector has verified continuity, a value is not necessary in this cell, and the cell may b e ticked. 2 2 Continuity R2 : a d d the value of t h e cpc continuity reading. If using test m e t h o d 2 (the 'wandering lead' method), readings that were measured o n the circuit. Note that where enter the m a x i m u m value of the various meaningless results are recorded, d u e t o parallel return paths, and it has b e e n established and the inspector has verified continuity, a value is not necessary in this cell, and the cell may b e ticked. 2 3 Insulation resistance test voltage: usually 5 0 0 V unless the circuit contains equipment that m a y b e damaged by, or otherwise affect, a test at 5 0 0 V. 24 Insulation resistance, L-L: enter the minimum value recorded during testing of the circuit for each of t h e various configurations (see Section 2.6.7). 25 Insulation resistance, L-E: enter t h e minimum the circuit for each of the various configurations value recorded during testing of (see Section 2.6.7). 2 6 Polarity: tick this cell w h e n the polarity for the circuit has been confirmed (see Section 2.6.13). A cross may b e use to indicate polarity only where the f o r m accompanies an EICR. 2 7 Z s : enter t h e circuit EFLIby whatever method you have selected t o determine it (see Section 2.6.15). 28 Enter maximum disconnection t i m e measured for a test current at | An . 29 Tick this cell when t h e operation of the RCD is confirmed when pressing the test button. 30 Tick this cell when AFDD that has a test button operates correctly w h e n the test button is pressed. 3 1 Remarks: this cell is provided to note anything relevant to the circuit and testing. 160 G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology ▼ Figure 5.7 Example M i n o r Electrical Installation Works Certificate (MEIWC) MINOR ELECTRICAL INSTALLATION WORKS CERTIFICATE Certificate No.: ...4.43g. (REQUIREMENTS FOR ELECTRICAL INSTALLATIONS - BS 7671) To be used only for minor electrical work which does not include the provision of a new circuit PART 1: Description of the minor works ............................................. Date minor works completed 1 . Details of the Client . .&£.&. .lighting 3. Description of the minor works points “3“# 202-2. 2A. Y. ............................................................. Little. 2. Installation location/address . 2 kP.YP,. ................................ t o .office/b 4. Details of any departures from BS 7671 :2018 as amended to 2022 (date) for the circuit altered or extended (Regulation 120.3, 133.1.3 and 133.5). Details of permitted exceptions (Regulation 411.3.3). Where applicable, a suitable risk assessment(s) , ,m . must be attached to this Certificate. Risk assessment attached |_| None. 5. Comments on (including any defects observed in) the existing installation (Regulation 644.1.2): No protection against overvoltage. Distributor's equipment issue - cut-out ruseholder corner cracked. Customer- advised ■to ■contact -supplier .............................................................................................................................. PART 2: Presence and adequacy of installation earthing and bonding arrangements (Regulation 132.16) TN-C-S L3 TT TN-S 1 . System earthing arrangement: Q 2. Earth fault loop impedance at distribution board (Zdb) supplying the final circuit ........ 3. Presence of adequate main protective conductors: LET Earthing conductor Main protective bonding conductor(s) to: Water E Gas S Oil Structural steel Other (Specify).................. PART 3: Circuit details DB Reference No.: ....... /. ................................. DB Location and type: . Tpp.of .stairs, 8 Circuit description: ...... Qpstgjrs, lighting .......................... Installation reference method ................. Circuit No.: ..... mm 2 cpc .... A4?........... mm 2 Number & size of conductors: Live . Circuit overcurrent protective device: BS (EN) ..£■£<?<?.?... Type RCD: BS (EN) ..£*£*?.?.. Type .....4... ..... Rating ,.A AFDD: BS (EN) SPD: PN. ..................................... Rating ..... .f...A Rating ..... £ . . A Rated residual operating current (I J .... ..mA ..A ..... Type BS(EN) ...W* PART 4: Test results for the altered or extended circuit (where relevant and practicable) R 2)......................................... Q or R 2 .................. <24 ............... Q Protective conductor continuity: (R Continuity of ring final circuit conductors: L/l ___bt/A. ........... Q N/N ..... Insulation resistance: Test voltage3Z?<?.V Live - Live Z.9.9.9MQ Polarity satisfactory: Live - Earth .>9.9.9... Maximum measured earth fault loop impedance: 0 MQ Zs Q Satisfactory test button operation: RCD disconnection time at rated residual operating current (l An) .../2-?-4.ms AFDD satisfactory test button operation: SPD functionality confirmed: Q .......... Q cpc/cpc ...... bf/A ........ Q NOTE: Not all AFDDs have a test button NOTE: Not all SPDs have visible functionality indication PART 5: Declaration I certify that the work covered by this certificate does not impair the safety of the existing installation and the work has been designed, constructed, inspected and tested in accordance with BS 7671:2018 amended to .4<?42..... (date) and that to the best of my knowledge and belief, at the time of my inspection, complied with BS 7671 except as detailed in Part 1 above. Name: ..... G.-..Stokes ................................................. For and on behalf of: ...StP.keS.El Address; . .. .................................... Signature: Newtown Position: ...P.UC Etor ................................................. WA4 SXX Date; Au uStjZOZZ Guidance N o t e 3: Inspection & Testing © The Institution of Engineering and Technology 161 5 MINOR ELECTRICAL INSTALLATION WORKS CERTIFICATE(MEIWC) Notes for the person producing the Certificate Scope The MEIWC is intended to be used for alterations or additions to an installation that do not extend to the provision of a new circuit. Examples include the addition of socket outlets or lighting points to an existing circuit, the relocation of a light switch, and similar. This Certificate may also be used for the replacement of equipment such as accessories or luminaires, but not for the replacement of distribution boards, consumer units or similar items. Appropriate inspection and testing, however, should always be carried out, irrespective of the extent of the work undertaken. Part 1 Description of the minor works 1,2,3 4 5 The minor works must be so described that the work that is the subject of the certification can be readily identified. See Regulations 120.3 and 133.5. No departures are to be expected, except in the most unusual circumstances. See also Regulation 644.1. Note any defects observed in the existing installation that are not related to the work being carried out. Under the "Comments on existing installation ..." heading, only deficiencies that do not impair the safety of any alteration or addition covered by the Certificate may be referred to. An example would b e existing main bonding conductors identified by the colour green only (rather than green-and-yellow) or which have a csa less than that required by Chapter 54, but which are nevertheless considered adequate by the designer of the alteration or addition. Any deficiency liable to impair the safety of the alteration or addition must be corrected before the alteration or addition is carried out (see Regulation 132.16). It would be unacceptable simply to refer to the deficiency on the Certificate. Part 2 Installation earthing and bonding: existing installation The existing earthing and bonding must be inspected and tested to confirm that it is adequate for the new works. Any extension to earthing and bonding must be installed for the works, if required. Part 3 Circuit details Generally, for domestic installations, this is simple: record details of the circuit protective device and circuit conductors. COMPLETE THE CIRCUIT CHART DETAILS ON THE DISTRIBUTION BOARD OR CONSUMER UNIT. Part 4 Essential tests The relevant provisions of Part 6 (Inspection and testing) of BS7671 must be applied in full to all minor works. For example, where a socket-outlet is added to an existing circuit, it is necessary to: 162 Guidance N o t e 3: Inspection & Testing © The Institution of Engineering and Technology 5 (a) establish that t h e earthing contact of the socket-outlet is connected to a suitable means of earthing via the MET; (b) measure the insulation resistance of t h e circuit that has been added to and establish that i t complies with Table 6 4 of BS 7671; (c) measure the EFLIto establish that the maximum permitted disconnection time is not exceeded; (d) check that t h e polarity of t h e socket-outlet is correct; and (e) if t h e work is protected by an RCD, verify the effectiveness of the RCD. Part 5 Declaration When filling out a n d signing a form o n behalf of a company or other business entity, individuals m u s t state for w h o m they are acting. GUIDANCE FOR RECIPIENTS (to be a p p e n d e d t o the Certificate) This Certificate has been issued to confirm that t h e electrical installation work to which it relates has been designed, constructed, inspected and tested in accordance with BS 7671. You should have received an 'original' Certificate and t h e person that issued the Certificate should have retained a duplicate. If you were the person ordering the work, but n o t t h e owner of t h e installation, you should pass this Certificate, or a copy of it, to the owner. A separate Certificate should have been received for each existing circuit o n which minor works have been carried out. This Certificate is not appropriate if you requested the person that issued the Certificate to undertake m o r e extensive installation work, for which you should have received an EIC. The Certificate should b e retained in a safe place and b e shown to any person inspecting or undertaking further work o n the electrical installation in the future. If you later vacate the property, this Certificate will demonstrate to the n e w owner that the minor electrical installation work carried out complied with the requirements of BS7671 at the time t h e Certificate was issued. For safety reasons, the electrical installation will need to b e inspected at appropriate intervals by a skilled person or persons, competent in such work. Where the installation includes a residual current device (RCD) it should b e tested six-monthly by pressing t h e button marked T or 'Test'. The device should switch off t h e supply and should then b e switched o n to restore t h e supply. If the device does not switch off t h e supply w h e n the button is pressed, seek expert advice. For safety reasons it is important that this instruction is followed. Where t h e installation includes an arc fault detection device (AFDD) having a manual test facility it should b e tested six-monthly by pressing the test button. Where a n AFDD has both a test button and automatic test function, manufacturer's instructions shall b e followed with respect to test button operation. Where the installation includes a surge protection device (SPD) the status indicator should b e checked to confirm it is in operational condition in accordance with manufacturer's information. If the indication shows that t h e device is n o t operational, seek expert advice. For safety reasons it is important that this instruction is followed. Guidance Note 3: Inspection & Testing © The Institution of Engineering and Technology 163 5 Where the installation includes alternative or additional sources of supply, warning notices should be found at the origin or meter position, or if remote from the origin, at the consumer unit or distribution board and at all points of isolation of all sources of supply. ▼ Figure 5 . 8 Example Electrical Installation Condition Report (EICR) (page 1) ELECTRICAL INSTALLATION CONDITION REPORT Report No.: . A 3 4 2 SECTION A. DETAILS OF THE PERSON ORDERING THE REPORT Name M. ......................................................................................................................................... Address EAiX ............................................................................................................ SECTION B. REASON FOR PRODUCING THIS REPORT Date(s) on which inspection and testing was carried out ....... l.tL August ,2022 .................................. SECTION C. DETAILS OF THE INSTALLATION WHICH IS THE SUBJECT OF THIS REPORT Occupier Address Description of premises Residential Ef Commercial Industrial Other (include brief description) Estimated age of wiring system years Evidence of additions I alterations? Yes ST No Installation records available? (Regulation 651.1) Not apparent Yes □ If yes, estimate age No |Vf £ .........years Date of last inspection ....................................... (date) __________ SECTION D. EXTENT AND LIMITATIONS O F INSPECTION AND TESTING Extent of the electrical installation covered by this report . a n d .test of c p uwier unit ..Visual .inspeetion..o.f..suprilier!s..ter.nninal..eauipi(nent i ..inspection. Agreed limitations including the reasons (see Regulation 653.2) Bu tiding. fabric ,not ,to b e , distu rbed Agreed with: .....Client ....................... ................. ....... .......... ...................................................... ............................................................ .......... Operational limitations including the reasons (see page no ) ...None The inspection and testing detailed in this report and accompanying as amended to ............................... schedules have been carried out in accordance with BS 7671:2018 It should be noted that cables concealed within trunking and conduits, under floors, in roof spaces, and generally within the fabric of the building or underground, have not been inspected unless specifically agreed between the client and inspector prior to the inspection. An inspection should be made within an accessible roof space housing other electrical equipment. SECTION E. SUMMARY O F THE CONDITION O F THE INSTALLATION General condition of the installation (in terms of electrical safety) .lnst.alLatio.n.d.Q.e$..nQt.cp. .p additional, ,i Iighti ,,poin .wlth..D$.7 7 alled, l.n2977.-. :2Q tA2:2Q22,.EidJS.in.gQQ.d.cpnditiQn.ApartJrp.rn.the..connect.lQn...Qf .This, led to flickering , lights, and possible risk of fire ,and ,shock. Overall assessment of the installation in terms of its suitability for continued use SATISFACTORY / UNSATISFACTORY* (Delete as appropriate) *An unsatisfactory assessment indicates that dangerous (code C1) and/or potentially dangerous (code C2) conditions have been identified. _______ SECTION F. RECOMMENDATIONS Where the overall assessment of the suitability of the installation for continued use above is stated as UNSATISFACTORY, 11 we recommend that any observations classified as ‘Danger present’ (code C1 ) or ‘Potentially dangerous’ (code C2) are acted upon as a matter of urgency. Investigation without delay is recommended for observations identified as ‘Further investigation required’ (code Fl). Observations classified as ‘Improvement recommended’ (code C3) should be given due consideration. 13/08 /2.032 Subject to the necessary remedial action being taken, I / We recommend that the installation is further inspected and tested by ..................... (date) for the following reasons this. .is.t h e . usual. period, recommended, for. private . residences SECTION G. DECLARATION l/We, being the person(s) responsible for the inspection and testing of the electrical installation (as indicated by my/our signatures below), particulars of which are described above, having exercised reasonable skill and care when carrying out the inspection and testing, hereby declare that the information in this report, including the observations and the attached schedules, provides an accurate assessment of the condition of the electrical installation taking into account the stated extent and limitations in section D of this report. Report authorised for issue by: Inspected and tested by: Name (Capitals) ....... fdECEE..TH.QM ................. Name (Capitals) PFF THOMPSON For/on behalf of . . . . T . a n d C , Electrical Forton behalf of Position Position Prwrfe.r Address Whiteleaf .................................................................. SECTION H. SCHEDULE(S) .....i Inspection Schedule(s) and Date Schedule(s) T.and.C Electrical. Proprietor 14 August iozi of Circuit Details and Test Results are attached. The attached schedule(s) are part of this document and this report is valid only when they are attached to it. G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology .................................. ................................................................ U/hrte/eaf Close, Ne pwn .EA.4 SXX Address Close, Date 164 ........................... Signature Signature Figure 5 . 9 Example Electrical Installation Condition Report (EICR) (page 2) Report N o . : ...1342. SECTION I. SUPPLY CHARACTERISTICS Nature of Supply Parameters Supply Protective Device Conductors DC TN-C AC Ef TN-S 1 -phase, 2-wire TN-C-S AND EARTHING ARRANGEMENTS _________________________________________________________ Number and Type of Live Earthing arrangements S’ TT Nominal voltage, U / Uo ............ V BS(EN) ..... ............. Nominal frequency, fW ......... so ........... Hz Type ................? ................ 2-phase, 3-wire 3-wire Other Prospective fault current, I P ..... &.?. ...... kA External earth fault loop impedance, Ze .............. Q Rated current 3-phase, 3-wire 3-phase, 4-wire IT ..... 2-wire EF (Note: Confirmation of supply polarity 0 .......1Q.9.. ... A (1) by enquiry (2) by enquiry or by measurement) Other sources of supply (as detailed on attached schedule) E SECTION J. PARTICULARS OF INSTALLATION REFERRED TO IN THE REPORT ______________________________________________________ Details of Installation Earth Electrode (where applicable) Means of Earthing Distributor’s facility IZT Type ............. NZA ............................................................................................................................................................ Installation earth electrode Location ......... W/A .......................................................................................................................................................... Resistance to Earth ... N/A. .. O Main Protective Conductors ________________________________________________ Material Earthing conductor Main protective bonding conductors To water installation pipes 0 Connection / continuity verified 0 .......... csa ........ «?. .......... mm* Connection / continuity verified 0 0 To structural steel Material To gas installation pipes Toother To lightning protection ....Copper,......... csa ....... .9........... mm 2 | To oil installation pipes Specify ................................................................................................................................................. Main switch / Switch -fuse / Circuit-breaker I RCD Location ........................................................ Current rating ........ 1Q.Q.................. A Under-stairs cupboard Fuse / device rating or setting BS(EN) ...... 4 7 - 3 ........................... Voltage rating .N/A If RCD main switch RCD Type .......... .A ............................................... Rated residual operating current (Jap) ...... .C/ZA...... m A ZZQ .................. V Rated time delay ........ NZA ..................................... ms No of poles ...... £ .......................................... Measured operating time ..... ............................. ms SECTION K. OBSERVATIONS Referring to the attached inspection schedule(s) and schedule(s) of circuit details and test results, and subject to the limitations specified at the Extent and limitations of inspection and testing section No remedial action is required The following observations are made EF (see below): CLASSIFICATION CODE OBSERVATION(S) Include schedule reference, as appropriate 1-. . .tP.,lighting, circuit at Junction Loose connections box.. Arcing ,and, burnt .insulation evident ......................................... as above, causing unreliable earthing 2. No additional protection bg RCD, or earthed NOTE: Faulty section of lighting Cl t/‘ of circuit and risk of fire. mechanical protection, for cables concealed in walls ....UM circuit disconnected with Clients .approval. One of the following codes, as appropriate, has been allocated to each of the observations made above to indicate to the person(s) responsible for the installation the degree of urgency for remedial action. C1 - Danger present. Risk of injury. Immediate remedial action required 02 - Potentially dangerous - urgent remedial action required C3 - Improvement recommended Fl - Further investigation required without delay G u i d a n c e N o t e 3: I n s p e c t i o n & Testing © The Institution of Engineering and Technology 165 5 ELECTRICAL INSTALLATION PRODUCING 1 CONDITION REPORT NOTES FOR THE PERSON THE REPORT This Report should only b e used for reporting o n the condition of an existing electrical installation, and n o t for the replacement of a consumer u n i t / distribution board. An installation which was designed to an earlier edition of BS 7671 or the IEE Wiring Regulations and which does not fully comply with the current edition is not necessarily unsafe for continued use, or requires upgrading. Only damage, deterioration, defects, dangerous conditions and non- compliance with the requirements of BS 7 6 7 1 or t h e IEE Wiring Regulations, which may give rise t o danger, should b e recorded. 2 The Report, normally comprising at least five pages, should include schedules of both the inspection a n d t h e test results. Additional pages may be necessary for other than a simple installation a n d for the "Guidance for recipients". The number of each page should b e indicated, together with the total number pages involved. of 3 The reason for producing this Report, such as change of occupancy or landlord's 4 Those elements of the installation that are covered by the Report and those that are not should b e identified in Section D (Extent and limitations). These periodic maintenance, should b e identified in Section B. aspects should have b e e n agreed with the person ordering the report and other interested parties before the inspection and testing commenced. Any operational limitations, such as inability t o gain access t o parts of the installation or an item of equipment, should also b e recorded in Section D. 5 The maximum prospective value of fault current (l p f) recorded should b e the greater of either the prospective value of short-circuit current or the prospective value of earth fault current. 6 Where a n installation has an alternative source of supply a further schedule of supply characteristics and earthing arrangements based u p o n Section I of this 7 A summary of the condition of the installation in terms of safety should b e clearly stated in Section E. Observations, if any, should b e categorized in Report should b e provided. Section K using the coding C l to C3 as appropriate. Any observation given a code C l or C 2 classification should result in the overall condition of t h e installation being reported as unsatisfactory. 8 Wherever practicable, i t e m s classified as 'Danger p r e s e n t ' ( C l ) should b e m a d e s a f e o n discovery. Where this is not possible the owner or user should b e given written notification 9 as a matter of urgency. Where an observation requires further investigation (Fl) because the inspection has revealed an apparent deficiency which could not, owing to the extent or limitations of the inspection, b e fully identified and further investigation may reveal a code C l o r C2 item, this should b e recorded within Section K, given the code Fl and marked as unsatisfactory in Section E. 10 If the space available for observations in Section K is insufficient, additional pages should b e provided as necessary. 11 The date by which the next Electrical Installation Condition Report is recommended should b e given i n Section F. The interval between inspections should take into account t h e requirements of Regulation 652.1 and the overall condition of the installation. 12 Any deficiencies ordering the work. 166 G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology with intake equipment should be reported to the person 5 ELECTRICAL INSTALLATION C O N D I T I O N R E P O R T GUIDANCE F O R RECIPIENTS (to b e appended t o the Report) This Report is a n i m p o r t a n t and valuable d o c u m e n t which should b e r e t a i n e d f o r future reference. 1 The purpose of this Condition Report is to confirm, so far as reasonably practicable, whether or not the electrical installation is in a satisfactory condition for continued service (see Section E). The Report should identify any damage, deterioration, defects and/or conditions which may give rise to danger (see Section K). 2 This Report is only valid if accompanied by the Inspection Schedule(s) and the Schedule(s) of Circuit Details and Test Results. 3 The person ordering the Report should have received the 'original' Report and the inspector should have retained a duplicate. 4 The 'original' Report should b e retained in a safe place and be made available to any person inspecting or undertaking work o n t h e electrical installation in the future. If t h e property is vacated, this Report will provide the n e w o w n e r / occupier with details of t h e condition of the electrical installation at the t i m e the Report was issued. 5 Section D (Extent and Limitations) should identify fully t h e extent of the installation covered by this Report and any limitations o n the inspection and testing. The inspector ordering the Report should and with have agreed other these interested aspects with parties the (licensing person authority, insurance company, mortgage provider and the like) before t h e inspection was carried out. 6 Some operational limitations such as inability to gain access to parts of t h e installation or an item of equipment m a y have been encountered during the inspection. The inspector should have noted these in Section D. 7 For items classified in Section K as C l ('Danger present'), t h e safety o f t h o s e using the installation is at risk, and it is recommended that a skilled person or persons competent in electrical installation work undertakes the necessary remedial work immediately. 8 For items classified in Section K as C2 ('Potentially dangerous'), the safety o f those using the installation may b e a t risk and it is recommended that a skilled person or persons competent in electrical installation work undertakes the necessary remedial work as a matter of urgency. 9 Where it has been stated in Section K that an observation requires further investigation (code Fl) the inspection has revealed an apparent deficiency which may result in a code C l or C2, and could not, due to the extent or limitations of t h e inspection, without b e fully identified. Such observations should b e investigated delay. A further examination determine of the installation will be necessary, to the nature and extent of the apparent deficiency (see Section F). 10 For safety reasons, t h e electrical installation should b e re-inspected at appropriate intervals by a skilled person or persons, competent in such work. The recommended date by which t h e next inspection is due is stated in Section F of the Report under 'Recommendations'. 11 Where the installation includes a residual current device (RCD) it should b e tested six-monthly should switch by pressing the button off the supply and should marked then T or 'Test'. The device b e switched o n to restore the supply. If t h e device does n o t switch off t h e supply when t h e button is pressed, seek expert advice. For safety reasons i t is i m p o r t a n t t h a t this instruction is followed. Guidance N o t e 3 : Inspection & Testing © The Institution of Engineering and Technology 167 5 1 2 Where t h e installation includes an arc fault detection device (AFDD) having a manual test facility it should b e tested six-monthly by pressing t h e test button. Where an AFDD has both a test button and automatic test function, manufacturer's instructions shall b e followed with respect to test button operation. CONDITION 1 R E P O R T INSPECTION SCHEDULE GUIDANCE F O R INSPECTORS Section 1.0. Where inadequacies in t h e intake equipment are encountered t h e inspector should advise t h e person ordering the work to inform the appropriate authority. 2 The schedule is not exhaustive. 3 Numbers in brackets are regulation references to specified requirements. ▼ Figure 5.10 Example Condition Report Inspection Schedule (page 1) Certificate/Report £342 Number .................... CONDITION REPORT INSPECTION SCHEDULE FOR RESIDENTIAL AND SIMILAR PREMISES WITH UP TO 100 A SUPPLY Note: This form is suitable for many types of smaller installation, not exclusively residential. The persons responsible for the periodic inspection of the installation should include the relevant items in relation to the electrical installation, the inspection schedule can be reduced or expanded depending on the requirements for the installation. State Further C3 investigation Improvement Unacceptable State condition ____ C1 or C2 recommended Acceptable condition OUTCOMES Fl Not verified N/V Limitation LIM Not applicable N/A OUTCOME ITEM NO 1.0 1.1 SUPPLY INTAKE EQUIPMENT (visual inspection only) Distributor/supplier • Service intake equipment Where inadequacies are found a cross should be put against the appropriate item a n d a comment made in section K. An outcome against a n item in section 1 . 0 , other t h a n access to live parts, should not be used to cable • Service head • Earthing arrangement • Meter tails • Metering equipment • Isolator (where present) Where inadequacies in t h e intake equipment potentially i s strongly Person 1.2 determine are encountered, which may result ordering word / Duty holder notified -Yf Consumer's meter 2.0 PRESENCE OF ADEQUATE ARRANGEMENTS FOR OTHER SOURCES SUCH AS MICROGENERATORS (551 .6; 551.7) J tails 3.0 EARTHING / BONDING ARRANGEMENTS (411.3; Chap 54) Presence 3.2 Presence a n d condition 3.3 Provision and condition of distributor’s earthing arrangement of earth electrode connection of earthing/bonding l a b e l s at all appropriate Confirmation Accessibility a n d condition of earthing 3.6 Confirmation 3.7 Condition 3.8 Accessibility 4.0 CONSUMER UNIT(S) / DISTRIBUTION BOARD(S) Adequacy Security conductor size (542.3; of o t h e r protective of working space/accessibility of fixing to consumer Condition of enclosure(s) in terms Condition of enclosure(s) in terms of fire rating 4.5 Enclosure not damaged/deteriorated 4.6 Presence of main 4.7 Operation 4.8 Manual operation 4.9 Correct identification 4.10 Presence of R C D six-monthly switch (functional of circuit Presence of alternative supply Presence of other 4.13 Compatibility required board (132.12; 513.1) etc ( 4 1 6 . 2 ) etc (421.1 .201, 526.5) impair safety (651.2) of protective check) ( 6 4 3 . 1 0 ) and RCDs to prove disconnection details and protective warning labelling notice d e v i c e a n d base switching against damage Protection against electromagnetic 522.8.11; RCD(s) provided RCD(s) provided for a d d i t i o n a l protection 4.19 Confirmation for fault protection and Technology unit/distribution board N/A N/A (514.15) 514) components; correct type and rating. (No o r o v e r h e a t i n g ) (536.4.203) in line conductors o n l y ( 1 3 2 . 1 4 . 1 ; 5 3 0 . 3 . 2 ) where cables enter consumer effects where cables enter consumer 4.17 G u i d a n c e N o t e 3 : I n s p e c t i o n & Testing 7 (514.12.2) unit/distribution board (132.14.1; 530.3.2) 4.18 of indication (Section and other o r protective devices mechanical 522.8.5; (643.10) devices ( 5 1 4 . 8 . 1 ; 5 1 4 . 9 . 1 ) at or near consumer (please specify) of u n a c c e p t a b l e thermal d a m a g e , arcing 522.8.1; © The Institution of Engineering unit/distribution test notice, where required 4.11 4.16 of IP rating so a s to of circuit-breakers 4.12 Protection 544.1.2) l i n k e d switch ( a s required by 462.1.201) of main Single-pole (543.3.2; ( 1 34.1 .1 ) 4.3 4.14 (544.1) b o n d i n g connections (543.3.2) 4.4 4.15 at M E T (543.3.2) of m a i n protective b o n d i n g conductor connections and condition N/A J J J (542.1.2.3) (514.13.1) 543.1.1) conductor of m a i n protective b o n d i n g conductor sizes a n d accessibility applicable locations 3.4 of earthing N/A ( 5 4 2 . 1 . 2 . 1 ; 542.1.2.2) where 3.5 4.2 N/A (Delete N/A 1.3 4.1 It (Delete as appropriate) isolator (where present) 3.1 - includes unit/distribution RCBOs (41 1 .4.9; 41 1 .5.2; 5 3 1 .2) board/enclosures y (521 .5.1) N/A - i n c l u d e s RCBOs (411 ,3.3; 415.1) that S P D is functional (651.4) the overall outcome. i n a dangerous o r dangerous situation, the person ordering the work and/or duty holder m u s t be informed. recommended t h a t the person ordering the work informs t h e appropriate authority. Consumer's signs 168 (Use codes above. Provide additional comment where appropriate. Cl, C2, C3 and Fl coded items to be recorded in Section K of the Condition Report) DESCRIPTION N/A a s appropriate) 5 ▼ Figure 5.11 Example Condition Report Inspection Schedule (page 2) Certificate/Report OUTCOMES Acceptable Unacceptable condition condition Improvement State Further C 1 or C 2 recommended C3 investigation State Fl Not verified N/V Limitation 1342 Number .................... LIM Not applicable N/A OUTCOME ITEM (Use codes above. Provide additional comment where appropriate. DESCRIPTION NO C1, C2, C3 and Fl coded items to be recorded in Section K of the Condition Report) 4.20 that ALL conductor connections, Confirmation terminals and are tight and secure (526.1) 4.21 Adequate 4.22 Adequate arrangements where a generating 5.0 FINAL CIRCUITS 5.1 Identification 5.2 Cables 5.3 Condition 5.4 Non-sheathed cables ■ To include the integrity 5.5 Adequacy 5.6 Coordination between conductors of protective devices: located in to the public supply (551 .6) set operates as a switched alternative where a generating arrangements are correctly to busbars, connections including in parallel with the public supply (551 .7) set operates ✓ N/A N/A of conductors (514.3.1) correctly their run (522.8.5) throughout supported Cl of live parts (416.1) of insulation capacity with regard for the type and nature of installation of cables for current-carrying 5.7 Adequacy 5.8 Presence a n d adequacy appropriate (433.1; 533.2.1) for fault protection (41 1 .3) devices protective and overload type and rated current Wiring system(s) Concealed 5.11 C a b l e s concealed under floors, above ceilings damage (see Section D. Extent and limitations) 5.12 Provision cables installed i n prescribed D. Extent z o n e s (see Section influences and external for the type and nature of the installation 5.9 5.10 (Section 523) y' (433.1; 543.2.1) conductors protective of circuit and plastic) (metallic systems and trunking of conduit or trunking (521.10.1) in conduit, ducting by enclosure protected adequately protected o r in walls/partitions, (522.6.204) (Section 522) (522.6.202) and limitations) against of additional protection by R C D n o t exceeding 30 mA: ■ for all socket-outlets to m o b i l e e q u i p m e n t not exceeding 32 A rating for u s e outdoors ■ for cables concealed sealing of fire barriers, and protection arrangements Provision B a n d II c a b l e s segregated/separated from Band I cables (528.1) 5.15 Cables segregated/separated from communications 5.16 Cables 5.17 Termination of cables at enclosures visible connected at point of entry to enclosure of accessories including 5.19 Suitability of accessories for external influences 5.20 Adequacy of working space/accessibility 5.21 Single-pole (526.5) (glands, to equipment LOCATION(S) CONTAINING A BATH OR SHOWER Additional 6.2 Where used as a protective measure, with B S EN 61558-2-5 supply units comply Presence of supplementary 6.5 Low voltage bonding by RCD not exceeding for SELV o r PELV met (701 .414.4.5) for installed location 6.6 Suitability of equipment 6.7 Suitability of accessories a n d controlgear etc. for a particular 6.8 Suitability of current-using equipment by B S 7671:2008 (701.415.2) sited at least 2 . 5 m from z o n e 1 (701.512.3) influences for particular in terms of IP rating (701 .512.2) the location 7.0 OTHER PART 7 SPECIAL INSTALLATIONS OR LOCATIONS 7.1 List all other special installations applied.) particular inspections (701 .55) if any. (Record separately the results of 8.0 CHAPTER 82 PROSUMER’S LOW VOLTAGE ELECTRICAL INSTALLATION(S) 8.1 and recommendations Where the installation includes additional requirements items should be a d d e d to the checklist. Chapter 8 2 , additional Inspection Inspected by: OEOFF THOMPSON Name (Capitals) ................................ y y zone (701.512.3) position within o r locations present, (?3 N/A B S 3535 (701 .512.3) formerly unless not required conductors, (e.g. 2 3 0 volt) socket-outlets for external 30 mA (701.41 1.3.3) (LV) circuits requirements for all low voltage Shaver Cl .y 513.1) (132.12; 6.0 6.3 etc.) (522.8.5) (512.2) 6.1 6.4 bushes devices in line conductors only (132.14.1; 530.3.2) switching o r protective protection Cl switches a n d joint boxes (651.2) socket-outlets, Condition 526) enclosure (526.8) outside 5.18 D of the report (Section in Section strain (526.6) ■ Connections of live conductors adequately enclosed * Adequately y' (528.3) - indicate extent of sampling made a n d under n o undue ■ No b a s i c insulation of a conductor 527) cabling (528.2) services segregated/separated from non-electrical • Connections soundly effects (Section thermal against 5.13 5.14 LIM N/A of depth (522.6.203) metal parts regardless containing ( 4 11 .3.3) 522.6.203) in walls at a depth of less than 5 0 m m (522.6.202; ■ for cables concealed in walls/partitions y' (411.3.3) of rating 32 A or less, unless an exception is permitted ■ for supply Signature relating to N/A N/A 14/OS/2O22 TpwzmjWWx ...................................... Date .................... Guidance Note 3: Inspection & Testing © The Institution of Engineering and Technology 169 NOTES 170 G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology Appendix A Maximum permissible measured earth fault loop impedance (EFLI) Al 643.7.3 Tables The tables in this appendix provide maximum permissible measured EFLI (Z s) for 411.4.201 compliance with BS 7671, which must not b e exceeded when the tests are carried 411.4.202 out at an ambient temperature of 10 °C. Table A7 provides correction factors for other 411.4.203 ambient temperatures. Where t h e cables to b e used are to Table 3, 4 or 5 of BS 6004, Table 3, 4 o r 5 o f BS 7211, Table B.l or B.2 of BS EN 50525-3-41 or are other thermoplastic (PVC) or thermosetting (low smoke halogen-free - LSHF) cables to these British Standards, and the cable loading is such that the maximum operating temperature is 70 °C, then Tables A l to A4 give the maximum EFLIfor circuits with: (a) protective conductors of copper and having f r o m 1 m m 2 to 16 m m 2 csa; and (b) an overcurrent protective device (OCPD) (i.e. a fuse) to BS 3 0 3 6 , BS 88-2, BS 88-3 or BS 1361. For each t y p e of fuse, two tables are given: 411.3.2.2 1 where the circuit concerned is a final circuit not exceeding 32 A for circuits supplying only fixed equipment, or 6 3 A for circuits with one o r m o r e socket-outlets, and the maximum disconnection t i m e for compliance with Regulation 411.3.2.2 is 0.4 s for TN systems; and 411.3.2.3 2 where the circuit concerned is a final circuit exceeding 32 A for circuits supplying only fixed equipment, or 63 A for circuits with one or m o r e socket-outlets, or a distribution circuit and the disconnection time for compliance with Regulation 411.3.2.3 is 5 s for TN systems. 543.1.3 In each table, the EFLI given correspond to t h e appropriate disconnection time f r o m a comparison of the time/current characteristics of t h e device concerned and t h e adiabatic equation given in Regulation 543.1.3. The tabulated values apply only where the nominal voltage to Earth (U o) is 2 3 0 V. Table A5 gives the maximum measured Z s for circuits protected by circuit-breakers to BS 3871-1 and BS EN 6 0 8 9 8 , and RCBOsto BS EN 61009. Guidance Note 3: Inspection & Testing © The Institution of Engineering and Technology 171 A Tables 41.2 to 41.4 543.1.3 Note: The impedances tabulated in this appendix are lower than those in Tables 41.2 to 41.4 of BS 7671. This is because the impedances in this appendix are measured values at an assumed conductor temperature of 10 °C, whilst those in BS 7671 are design figures at the line conductor maximum permitted operating temperature given in Table 52.1 of BS 7671 and the protective conductor assumed initial temperature given in Tables 54.2 to 54.5 of BS7671. The correction factor (divisor) used is 1.25. This corresponds to the line conductor maximum operating temperature and protective conductor assumed initial temperature both being 70 °C. For smaller csa cables, the impedance may also be limited by the adiabatic equation of Regulation 543.1.3. A value of k of 115 from Table 54.3 of BS 7671 is used. This is suitable for PVCinsulated and sheathed cables to Tables 3, 4 or 5 of BS6004 and forthermosetting (LSHF) insulated and sheathed cables to Tables 3, 4 or 5 of BS 7211 or Table B.l or B.2 of BS EN 50525-3-41 . The k value is based o n both the thermoplastic (PVC) and thermosetting (LSHF) cables operating at a maximum temperature of 70 °C. ▼ Table Al Semi-enclosed fuses. Maximum measured EFLI (in Q) at ambient temperature where the OCPD is a semi-enclosed fuse to BS 3 0 3 6 (i) 0.4 s disconnection (final circuits n o t exceeding 32 A for circuits supplying only fixed equipment, or 63 A for circuits with one or more socket-outlets, in TN systems) Fuse rating Protective conductor (mm 2) 15 A 5A 20 A 30 A (ii) 5 s disconnection (final circuits exceeding 32 A for circuits supplying only fixed equipment, or 63 A for circuits with one or more socket-outlets, and distribution circuits in TN systems) Protective conductor (mm 2) Note: Fuse rating 20 A 30 A 45 A 60 A ____ 1.0 2.3 NP NP NP 1.5 2.91 1.6 NP NP 2.5 2.91 2.0 1.0 NP 4.0 2.91 2.0 1.2 0.85 >6.0 2.91 2.0 1.2 0.85 NP means that the combination of the protective conductor and the fuse is Not Permitted. ▼ Table A2 BS 88-2 fuses. Maximum measured EFLI (in Q) at ambient temperature where the OCPD is a fuse to BS 88-2 or BS 8 8 - 6 (i) 0.4 s disconnection (final circuits not exceeding 32 A for circuits supplying only fixed equipment, or 63 A for circuits with one or more socket-outlets, in TN systems) Protective conductor (mm 2) 172 Fuse rating 2A 4A 6 A 10 A 16 A 20 A 25 A 32 A 1.0 26.5 12.5 6.2 3.7 1.9 1.3 1.0 0.6 1.5 26.5 12.5 6.2 3.7 1.9 1.3 1.0 0.8 >2.5 26.5 12.5 6.2 3.7 1.9 1.3 1.0 0.8 Guidance Note 3: Inspection & Testing © T h e Institution of Engineering and Technology (ii) 5 s disconnection (final circuits exceeding 3 2 A for circuits supplying only fixed equipment, or 63 A for circuits with one or more socket-outlets, and distribution circuits in TN systems) Protective conductor (mm 2) Fuse rating 20 A 25 A 32 A 40 A 50 A 63 A 80 A 100 A _________1.0 _________ 1.46 1.03 0.63 0.55 NP NP NP NP 1.5 2.13 1.2 0.87 0.83 NP NP NP NP 2.5 2.24 1.76 1.336 1.04 0.5 0.3 NP NP 4.0 2.24 1.76 1.364 1.04 0.76 0.49 0.22 0.12 6.0 2.24 1.76 1.36 1.04 0.79 0.62 0.3 0.19 10.0 2.24 1.76 1.36 1.04 0.79 0.62 0.44 0.32 16.0 2.24 1.7 1.36 1.04 0.79 0.62 0.44 0.34 Note: NP means that the combination of the protectivei conductor and the fuse is Not Permitted. ▼ Table A3 BS88-3 fuses. Maximum measured EFLI(in Q) at ambient temperature where the OCPD is a fuse to BS 88-3 (i) 0.4 s disconnection (final circuits not exceeding 32 A for circuits supplying only fixed equipment, or 63 A for circuits with one or more socket-outlets, in TN systems) Protective conductor (mm 2) Fuse rating 5A 16 A 20 A 32 A 1.0 7.94 1.84 1.54 0.6 1.5 7.94 1.84 1.54 0.73 2.5 to 16 7.94 1.84 1.54 0.73 (final circuits exceeding 32 A for circuits supplying only fixed equipment, or 63 A for circuits with o n e or more socket-outlets, a n d distribution circuits in TN systems) (ii) 5 s disconnection Protective conductor (mm2 ) Note: Fuse rating 20 A 32 A 45 A 63 A 80 A 100 A 1.0 2.13 0.59 NP NP NP NP 1.5 2.57 0.76 NP NP NP NP 2.5 2.57 1.13 0.55 0.24 NP NP 4.0 2.57 1.25 0.76 0.32 0.19 NP 6.0 2.57 1.25 0.76 0.51 0.29 0.16 10.0 2.57 1.25 0.76 0.55 0.4 0.26 16.0 2.57 1.25 0.76 0.55 0.4 0.3 NP means that the combination of the protective conductor and the fuse is Not Permitted. Guidance Note 3: Inspection & Testing © The Institution of Engineeringand Technology 173 ▼ Table A4 BS 1361 fuses. Maximum measured EFLI (in Q) at ambient temperature where the OCPD is a fuse to BS 1361 (i) 0.4 s disconnection (final circuits n o t exceeding 32 A for circuits supplying only fixed equipment, or 63 A for circuits with one or more socket-outlets, in TN systems) Protective conductor (mm 2) Fuse rating 5A 15 A 20 A 30 A 1.0 7.95 2.50 1.29 0.77 1.5to 16 7.95 2.50 1.29 0.86 (ii) 5 s disconnection (final circuits exceeding 32 A for circuits supplying only fixed equipment, or 63 A for circuits with one or more socket-outlets, and distribution circuits in TN systems) Protective conductor (mm 2) Fuse rating 20 A 30 A 45 A 60 A 80 A 100 A 1.0 1.46 0.77 NP NP NP NP 1.5 1.98 0.97 0.32 NP NP NP 2.5 2.13 1.40 0.49 0.20 NP NP 4.0 2.13 1.40 0.67 0.35 0.20 NP 6.0 2.13 1.40 0.73 0.47 0.27 0.13 10.0 2.13 1.40 0.73 0.53 0.38 0.20 16.0 2.13 1.40 0.73 0.53 0.38 0.28 Notes: 1 NP means that the combination of the protective conductor and the fuse is Not Permitted. 2 While BS 88-3 has replaced BS 1361, and BS 1361 has been withdrawn, it can be seen from Table A3 that the maximum measured EFLI for BS 88-3 fuses cannot be applied to circuits protected by BS 1361 fuses, even of the same nominal rating. For example, the maximum permitted EFLI for 20 A fuses to BS 88-3 is far higher than that permitted for a circuit protected by a 20 A fuse to BS 1361. 174 Guidance Note 3: Inspection & Testing © The Institution of Engineeringand Technology A ▼ T a b l e A 5 Circuit-breakers. M a x i m u m m e a s u r e d EFLI ( i n O) at a m b i e n t t e m p e r a t u r e w h e r e t h e o v e r c u r r e n t d e v i c e is a circuit-breaker to B S 3 8 7 1 o r B S E N 6 0 8 9 8 or RCBOto BS EN 6 1 0 0 9 For 0.1 to 5 s disconnection times (includes 0.4 s disconnection time) Circuit-breaker rating (amps) Circuit breaker type 3 5 6 10 15 16 20 25 30 32 40 45 50 63 100 1 14.56 8.74 7.28 4.4 2.93 2.76 2.2 1.76 1.47 1.38 1.1 0.98 0.88 0.7 0.44 2 8.4 5.0 4.2 2.5 1.67 1.58 1.25 1.0 0.83 0.79 0.63 0.56 0.5 0.4 0.25 B 11.65 7.0 5.82 3.5 2.33 2.15 1.75 1.4 1.17 1.1 0.87 0.78 0.7 0.55 0.35 3&C 5.82 3.49 2.91 1.75 1.16 1.10 0.87 0.7 0.58 0.54 0.44 0.38 0.35 0.28 0.18 Circuit-breakers. Maximum measured EFLI (in Q) at ambient temperature where the overcurrent device is a circuit-breaker to BS EN 60898 type D or RCBO to BS EN 61009 type D Circuit breaker type Circuit-breaker rating (amps) 6 10 16 20 25 32 40 D 0.4 sec 1.46 0.87 0.55 0.44 0.35 0.28 - D 5 sec 2.91 1.75 1.09 0.87 0.7 0.55 0.44 50 0.35 63 100 - - 0.28 0.17 Regulation 434.5.2 of BS 7671 :2018 requires that the protective conductor csa meets t h e requirements of BS EN 60898-1-2 or BS EN 61009-1, or t h e m i n i m u m quoted by t h e manufacturer. The sizes given in Table A6 are for energy-limiting Class 3, Types B and C devices only. ▼ T a b l e A6 Minimum protective conductor Energy-limiting Class 3 device rating (A) Fault level (kA) Up to and including 16A size f o r Class 3 Types B a n d C devices Protective conductor csa (mm 2) ’ Type B Type C < 3 1.0 1.5 Up to and including 16A < 6 2.5 2.5 Over 16 A and up to and including 32A < 3 1.5 1.5 Over 16 A and u p to and including 32 A < 6 2.5 2.5 40 A < 3 1.5 1.5 40 A < 6 2.5 2.5 For other d e v i c e types and ratings, or higher fault levels, consult m a n u f a c t u r e r ' s data. S e e Regulation 4 3 4 . 5 . 2 a n d t h e I E T Electrical Installation Design Guide. Guidance Note 3: Inspection & Testing © The Institution of Engineeringand Technology 175 ▼ T a b l e A 7 Ambient temperature correction factors Ambient temperature (°C) Correction factor (from 10 °C) (Notes 1 and 2) Notes: 1 The correction factor is given by: {1 + 0.004 (ambient temp - 20)}/{l + 0.004 (10 - 20)} where 0 . 0 0 4 is t h e simplified resistance coefficient per °C at 20 °C given b y BS EN 6 0 2 2 8 for b o t h copper a n d aluminium conductors. (Alternatively, t h e correction factor is given by (ambient temp + 230)/(10 + 230)). 2 The factors are different f r o m those of Table B.2 because Table A7 corrects f r o m 1 0 °C a n d Table B.2 f r o m 2 0 °C. The ambient correction factor of Table A7 is applied to t h e EFLIof Tables A l to A5 if t h e ambient temperature is other than 10 °C. For example, if t h e ambient temperature is 2 5 °C, t h e measured EFLI of a circuit protected by a 3 2 A Type B circuit-breaker to BS EN 6 0 8 9 8 should not exceed 1.1 x 1.06 = 1.17 Q . A 2 Appendix Anox 3 3 of B S 7671 Appendix 3 of BS 7671 takes into account t h e increase of the conductor resistance with increase of temperature due to load current, which may b e used to verify compliance with t h e requirements of Regulation 41 1.4 for TN systems. The requirements of Regulation 411 .4.4 are considered met when the measured value of fault loop impedance satisfies the following equation: Zs(nn)=0.8x U X min °j where: 176 G u i d a n c e Note Zs (m) is the measured impedance of the earth fault current loop up to the most distant point of the relevant circuit from the origin of the installation (£2) Uq la is the nominal ACrms line voltage to Earth (V) is the current in amps (A) causing operation of the protective device within t h e time stated in Table 41.1 of BS 7671 or within 5 s according to the conditions stated in Regulation 411.3.2.3. Cmin 0.8 isthe minimum voltagefactorto take account of voltagevariationsdepending o n time and place, change of transformer taps and other considerations. is a temperature adjustment factorfor ambient temperature (see Table A7). Note: For an LV supply given in accordance with t h e ESQCR, C m in 's given t h e value 0.95. 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology A3 Methods of adjusting tabulated values of Z s (See also Section 2.6.16 (EFLI verification).) A circuit is wired in flat t w i n and cpc 70 °C thermoplastic (PVC) cable and protected by a 6 A Type B circuit-breaker to BS EN 60898. When tested at a n ambient temperature acceptable measured value of below 20 °C, determine the maximum Z s for the circuit. Solution: Ztest ( m a x ) “ Zs From Table 41.3(a) of BS7671, the maximum permitted value of Zs = 7.28 Q From Table B3 in Appendix B of this Guidance Note, F = 1.20 Ztest (max) = 1 , 2 0 X Ztest (max) = 6 . 0 7 Q A more accurate value can b e obtained if t h e external EFLI,Ze , is known. I n this case, the following formula may b e used: test - Z e + |z (z s Z e) In the example above, assume Ze is 0.35. Thus, t h e m o r e accurate value is: Ztest (max) = 0 . 3 5 + 1 2 -28-0.35) Ztest (max) = 6 . 1 3 Q Where the test ambient temperature is likely to b e other than 2 0 °C, a further correction can b e m a d e to convert t h e value to correspond with the expected ambient temperature, using the following formula: Ztest (max) = 2 e + Z e) where a is given by Table B2 of Appendix B. In the example above, assume the test ambient temperature is 5 °C. From Table B2, a = 0.94 Thus, the accurate reading including temperature Ztest(max)= 0 . 3 5 + Aest compensation is: (7.28-0.35) (max) = 5 . 7 8 Q Guidance Note 3 : Inspection & Testing © T h e Institution of Engineering and Technology 177 Note: Where reduced csa protective conductors are used, maximum EFLIsmay need to be further reduced to ensure disconnection times are sufficiently short to prevent overheating of protective conductors during earth faults. The requirement of the equation in Regulation 543.1.3 needs to be met: where: S k I Zs t Note: is the nominal csa of the conductor in m m 2 means greaterthan or equal to is a factor taking account of the resistivity, temperature coefficient and heat capacity of the conductor material and the appropriate initial and final temperatures; see Tables 54.2-54.4 is the value in amps (rms for AC) of fault current for a fault of negligible impedance, which can flow through the associated protective device, d u e account being taken of the current-limiting effect of the circuit impedances and the limiting capability (12 t) of that protective device is the loop impedance at conductor normal operating temperature is the operating t i m e of the overcurrent device in s corresponding to t h e fault current I a m p s - obtained from the graphs in Appendix 3 of BS7671, as the prospective earth fault current I (= U q X Cm jn /Z s) is known. Cm in is the minimum voltage factor, the meaning of which is explained in Section A2 of this appendix. The following example illustrates h o w measurements taken at 2 0 °C may b e adjusted to 70 °C values, taking t h e (R] + R2) reading for t h e circuit into account. In the previous example, taking t h e (Ri + R2) reading for t h e circuit as 0.2 Q : Z s for t h e circuit at 70 °C = Ze +F(R 1 + R 2)test = 0.35+1.20x0.2 = 0.59 Q The temperature-corrected Z s figure of 0.59 Q is acceptable, as it is less than t h e maximum value of 7.28 Q given in Table 41.3 of BS 7671. The formula above involves taking measurements at 2 0 °C and converting t h e m to 70 °C values. Alternatively, t h e 70 °C values can b e converted to t h e values at t h e expected ambient temperature, for example, 20 °C, when the measurement is carried out. 178 Guidance N o t e 3: Inspection & Testing © The Institution of Engineeringand Technology I A Taking t h e same circuit: Ztest = Ze + ( R i + Rz)test = 0.32+0.2 = 0.55Q From the formula: Z test ( m a x ) = p Z s Z s (m a x) f r o m B S 7 6 7 1 = 7.28 Q Ztest(max) = 1,20 x 7.28=6.07£2 Therefore, as 0.55 Q is less than 6.07 Q, t h e circuit is acceptable. Guidance Note 3: Inspection & Testing © The Institution of Engineering and Technology 179 NOTES 180 G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology Appendix B Resistance of copper and aluminium conductors 434.5.2 To check compliance with Regulation 434.5.2 and/or Regulation 543.1.3, i.e. to evaluate 543.1.3 the equation I2! S2 = 1,2 it is necessary to establish the impedances of the circuit conductors to determine the fault current, I, and hence the protective device disconnection Fault current, I = time, t. Un x 0 where: Uo Cmin is the nominal voltage to Earth is the minimum voltage factor to take account of voltage variations depending o n time and place, changing of transformer taps and other considerations Note: F o r LV supplies given in a c c o r d a n c e with t h e E S Q C R , C m in i s g i v e n the value 0 . 9 5 . Zs is the EFLI,and Zs = Ze + Ri + R2 where: Ze is that part of the EFLI external t o the installation Note: If t h e distribution replaced board i s not in the a b o v e equation a t t h e origin of the installation, Ze is b y Z d b . t h a t p a r t o f t h e E F L I o n the s u p p l y s i d e of t h e d i s t r i b u t i o n b o a r d . Ri is r2 is the resistance of the line conductor from the origin of the circuit to the point of utilization the resistance of the protective conductor from the origin of the circuit to the point of utilization. Similarly, in order to design circuits for compliance with the limiting values of EFLIgiven in Tables 41.2 to 41.4 of BS7671, it is necessary to establish the relevant impedances of the circuit conductors w h e n the line conductor is at t h e appropriate maximum permitted operating temperature, as given in Table 52.1 of BS7671, and the cpc is at t h e appropriate 'assumed initial temperature', as given in Tables 54.2 to 54.5. Guidance Note 3 : Inspection & Testing © The Institution of Engineering and Technology 181 B Table B l gives values of ( R i + R2) p e r m e t r e f o r various c o m b i n a t i o n s of c o n d u c t o r s u p to a n d including 5 0 m m 2 csa. It also gives values of resistance in m i l l i o h m s p e r metre for e a c h size of conductor. These values are a t 20 °C. V Table B l Values of resistance/metre for copper and aluminium conductors and of ( R i + R2) Pe r metre at 20 °C in mQ/m csa (mm 2) 182 Resistance/metre or (R 1 + R2 )/metre (mQ/m) Line conductor Protective conductor Copper 1 — 18.10 1* 1 36.20 1.5 — 12.10 1.5* 1 30.20 1.5 1.5 24.20 2.5 — 7.41 2.5 1 25.51 2.5* 1.5 19.51 2.5 2.5 14.82 4 — 4.61 4* 1.5 16.71 4 2.5 12.02 4 4 9.22 6 — 3.08 6* 2.5 10.49 6 4 7.69 6 6 6.16 10 — 1.83 10* 4 6.44 10 6 4.91 10 10 3.66 16 — 1.15 1.91 16* 6 4.23 — 16 10 2.98 — 16 __________16 2.30 3.82 25 — 0.727 1.20 25 10 2.557 — 25 16 1.877 3.11 25 25 1.454 2.40 35 — 0.524 0.87 35 16 1.674 2.78 Guidance N o t e 3: Inspection & Testing © The Institution of Engineering and Technology Aluminium csa (mm 2) Line conductor Note: Resistance/metre or (Ri + R2 )/metre (mQ/m) Aluminium Copper Protective conductor * identifies copper line/protective conductor combination that complies with Tables 4 and 5 of BS 6004:201 2+A1:2020 for thermoplastic insulated and sheathed cables, single-core and cpc (UK code 6241Y), twin and cpc (UK code 6242Y) or three-core and cpc (UK code 6243Y) and similar cable constructions for thermosetting cables according to Table 5 of BS 7211:2012+AI:2020 (UK codes 6241B, 6242B, 6243B). ▼ Table B2 Ambient temperature multipliers (a) to Table Bl | Expected ambient temperature 1 Correction factor 1 _________1 (°C) The correction factor is given by: {1 + 0.004 (ambient temp - 2 0 °C)} where 0.004 is the simplified resistance coefficient per °C at 20 °C given by BS EN 60228 for copper and aluminium conductors. To assist a n y o n e using Table B l , t h e following two f o r m u l a e m a y b e helpful: mft/mxL 1000 L= Rxiooo m&/m For verification purposes, the designer will need to give t h e values o f the line a n d cpc resistances a t the ambient temperature expected d u r i n g t h e tests. This m a y b e different f r o m t h e reference t e m p e r a t u r e of 2 0 ° C u s e d for Table B l . T h e correction factors in Table B2 m a y b e applied to the Table Bl values to take account of the a m b i e n t t e m p e r a t u r e (for test p u r p o s e s only). Bl Standard overcurrent devices Table 41.2 Table B 3 gives the multipliers Table 41.3 Table 41.4 p u r p o s e of calculating t h e resistance a t m a x i m u m operating t e m p e r a t u r e of t h e line to b e applied to t h e values given in Table Bl f o r the conductors and/or cpcs in order to determine compliance with the EFLIof Tables 41.2, 41.3 o r 41.4 of B S 7 6 7 1 . Guidance Note 3 : Inspection & Testing © The Institution of Engineering and Technology 183 B ▼ Table B3 Conductor temperature factor Ffor standard devices Multipliers t o b e applied t o Table B l f o r devices in Tables 41.2, 41.3, 41.4 Conductor installation Table 54.2 Table 54 Conductor insulation 70 °C thermoplastic (PVC) 85 °C thermosetting (Note 4) 90 °C thermosetting (Note 4) Not incorporated in a cable and not bunched (Notes 1,3) 1.04 1.04 1.04 Incorporated in a cable or bunched (Notes 2, 3) 1.20 1.26 1.28 No,es: 1 2 3 4 See Table 54.2 of BS 7671. These factors apply when the protective conductor is not incorporated or bunched with cables, or for separate bare protective conductors in contact with cable covering but not bunched with cables. See Table 54.3 of BS 7671. These factors apply when the protective conductor is a core in a cable or is bunched with cables. The factors are given by F = 1 + 0.004 {conductor operating temperature - 2 0 °C} where 0.004 is the simplified resistance coefficient per °C at 20 °C given in BSEN 60228 for copper and aluminium conductors. If cable loading is such that the maximum operating temperature is 70 °C, thermoplastic (70 °C) factors are appropriate. GN6 B2 Steel wire armour (SWA), steel conduit and steel trunking Formulae for t h e calculation of t h e resistance and inductive reactance values of t h e SWA of cables and of steel conduit, ducting and trunking are published in Guidance Note 6. Generally, it is accepted that there is approximately a 10 °C difference between t h e conductor temperature and the outer sheath temperature for an SWA cable at full load. BS GN1 184 Mineral-insulated copper-sheathed cable See also t h e guidance i n the appendices of Guidance Note 1 for mineral-insulated copper-sheathed cable temperature data. Guidance N o t e 3: Inspection & Testing © The Institution of Engineering and Technology Appendix C Use of an earth leakage current clamp meter to provide an indication of the state of insulation Where safe access is available to enclose the live conductors in a current clamp, but not t h e protective conductor, a suitably rated earth leakage current clamp meter (sometimes called a tong tester) can b e used to provide an indication of t h e state of insulation in a circuit downstream of the test point, by measuring 'earth leakage'. An example is shown i n Figure C l . In small installations, readings of a few milliamps will indicate protective conductor currents, but readings of many amps may indicate a line-to-earth or neutral-to-earth fault. ▼ Figure Cl Example of the measurement of earth leakage with a current clamp meter RRTE I 00D4 ISHHhWH 0101 -a-+ssx Note: The earth leakage current clamp for this test goes around the live conductors only. Guidance Note 3: Inspection & Testing © The Institution of Engineering and Technology 185 NOTES 186 Guidance Note 3: Inspection & Testing © The Institution of Engineering and Technology Appendix D Safety check for diverted neutral currents DI Dangers associated with diverted neutral currents Diverted neutral currents can occur if there is a break i n the protective earth and neutral (PEN) conductor in the distribution network supplying an installation with a PME earthing arrangement. Diverted neutral currents can cause hazardous touch voltages on the protective earthing system in an installation, including the main earthing terminal, extraneous-conductive-parts, circuit protective conductors, and exposed-conductive-parts. Installations that might b e affected by diverted neutral currents include: (a) installations in which PME conditions apply (TN-C-S earthing arrangement f r o m a public distribution network); and (b) installations with TN-S or TT earthing arrangements, that share extraneousconductive-parts with installations in which PME conditions apply. Precautions should b e taken before working o n any installation to determine if any hazardous touch voltages exist o n conductive parts. This is particularly important when working outdoors and in contact with t h e general mass of Earth. Precautions should also b e taken before disconnecting any earthing or protective bonding conductors. Note: Diverted neutral currents may originate from another installation, and so may be present even if the installation is isolated. D2 How to check for diverted neutral currents There is n o simple test that will indicate the presence of diverted neutral currents. However, some simple checks can b e made with voltage indicators, non-contact voltage testers, and earth leakage current clamp ammeters, along with an external EFLI test. An example of an approach that could b e used in dwellings is shown in Table D I . If an open-ciruit PEN conductor or diverted neutral currents are suspected after carrying out the safety checks, the DNO should b e informed immediately using the emergency number 105. Notes: 1 2 If there is an open-circuit PEN conductor, the line to neutral voltage may rise to 400 V nominal. One way of measuring earth leakage is to use a leakage current clamp ammeter. Leakage current clamp meters are similar to those used for measuring load current, but are more sensitive and therefore more accurate at measuring currents below 5 mA. Guidance Note 3: Inspection & Testing © The Institution of Engineering and Technology 187 The installation may import or export diverted neutral current. Exported neutral current occurs where there is a broken PEN conductor in the supply cable to the installation, so neutral current finds its way back to the supply transformer through extraneousconductive-parts shared with other installations that have an intact PEN conductor. Imported neutral current occurs where neutral currents f r o m another installation are exporting neutral current, and these are returning to the supply transformer through the PEN conductor of t h e installation concerned, via extraneous-conductive-parts. ▼ Table D I Example of checks for diverted neutral currents or broken PEN conductor in a dwelling Step Action Expected result Possible indication of diverted neutral currents or a broken PEN conductor 1. Before isolating t h e installation, measure the current flowing i n t h e m a i n earthing conductor and m a i n protective bonding conductors of t h e installation using a current clamp meter. A small current will b e expected, when compared with line conductor currents. In dwellings, a n d similar installations with a m a x i m u m d e m a n d of u p to 100 A, this is typically a few milliamps. Large currents flowing i n the earthing conductor a n d / o r main bonding conductors. 2. Switch off power to the installation, lock-off or otherwise secure t h e point(s) of isolation, a n d prove the installation is dead using an approved 2-pole contact voltage tester. The test for proving that t h e installation is dead shows it is dead. The installation does not appear to b e dead as expected. 3. Check for current flowing i n the m a i n earthing conductor a n d m a i n protective bonding conductors of t h e installation using a current clamp meter. The current has dropped to zero, or to an extremely small level. Current continues to flow i n t h e earthing conductor and/or main bonding conductors. Current measured in t h e customer bonding conductors orpipework can b e influenced by adding load to the customers installation, using a simple technique such as boiling a kettle or switching a heater on. 4. 188 Check for t h e presence of voltage using a non-contact voltage detector at the main earthing terminal, along the length of t h e m a i n earthing conductor, m a i n protective bonding conductors, and a t extraneous-conductive-parts. Guidance Note 3: Inspection & Testing © The Institution of Engineering and Technology No voltage is indicated. Voltage appears to b e present. Voltage indicators do not detect diverted neutral currents while i t i s able to flow using a n alternative p a t h . A volt-stick should a l s o b e used. D 5. Disconnect t h e main protective bonding conductors. Nothing unusual is noted. Evidence of current flow when the main protective bonding conductors are disconnected. 6. Re-check for t h e presence o f voltage using a non-contact voltage detector at t h e m a i n earthing terminal, along t h e length of t h e m a i n earthing conductor, m a i n protective bonding conductors, and at extraneous-conductive-parts. No voltage is indicated. Voltage appears to b e present. Voltage Re-connect the main protective bonding conductors so that insulation resistance tests can be carried out. Nothing unusual is noted. Evidence of current flow when the main protective bonding conductors is connected. In TN systems, during the course of inspection and testing, check the external EFLI. External EFLI measurement appears t o b e acceptable. The following is a rule o f thumb, b u t occasionally slightly higher readings m a y b e experienced: External EFLI is high, 8. indicators do not detect diverted neutral currents while it is able to flow using an alternative path. A volt-stick should also be used. i n TN-C-S systems, Ze < 0 . 3 5 Q i n TN-S systems, Z e < 0.80 Q A check against previous readings, w h e r e available, w o u l d provide m o r e accurate information. Guidance Note 3: Inspection & Testing © The Institution of Engineering and Technology 189 NOTES 190 G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology Index A Access Accuracy of test instruments 2.5.2 item o 4.2 Additional protection 2.5.2 item h; 2.6.19 Additions and Alterations 1.4; 3.2; Section 5 Alternative supplies warning notices Arc fault detection devices (AFDDs) testing Automatic disconnection of supply (ADS) 3.9.1 2.5.2 item p 2.5.2 item I; 2.5.2 item p 5.4 2.6.14; 3.9.1 B Barriers fire protection by, during erection Basic protection Breaking capacity of devices 2.5.2 item g 2.6.4 2.5.2 item h Table 2.16; 2.6.17; Section 5 Schedule of Test Results British Standards referenced Degrees of protection BS EN 60529 2.5.3 enclosures Emergency lighting BS5266 Preface; Table 3.2 note 3 Fire alarms BS5839 Residual current devices B S E N 61008, 61009 Preface; 2.5.3 General item k; 2.5.3 Flexible cables item h; Table 3.2 note 5 Table 2.6; Table 2.17 2.5.3 Switchgear item a; 2.6.16; 2.6.18; Table 2.6; Table 2.17; Appendix A Guidance Note 3 : Inspection & Testing © The Institution of Engineering and T echnology 191 Index Switchgear B S E N 60947 2.5.2 item j; Table 2.7; 2.5.3 Switchgear item a C Cables routing 2.5.2 item c couplers 2.5.2 item f 4.2 Calibration (checking of accuracy) Certificate, Electrical Installation Client 1.3.1; 1.4; 1.6; 2.1; 2.2; 2.6.2; 2.6.16; 3.4; 3.8.2; 3.8.3; Section 5 Introduction; 1.1; 1.3; 1.6; 3.4; 3.6; 3.8;Table 3.3; 3.11;Section 5 Colour coding (identification of conductors) 2.5.2 item b; 2.5.2 item p; 3.9.1 1.2; 4.9 Competence Condition Report, Electrical Installation 1.3.1; 1.3.2; 1.6; 2.6.16; 3.1; 3.8; 3.11:3.12; Section 5 Conductors classes 2.5.2 item a identification 2.5.2 item b Appx B resistance Construction (Design and Management) Regulations 2015 Connection Introduction; 1.1; 1.3.3; 1.6; 3.4; Section 5 2.5.2 item a of conductors Continuity main bonding protective conductors 2.5.1; Section 5 ; Table 3.4 2.5.2 items b and h; 2.5.3; 2.6; Table 3.4; 3.10.3; 4.3; Appendix A ’all-insulated' installations 2.6.5; Fig 2.5 test method 1 metallic enclosures as protective conductors 2.6.5 test procedure ring final circuit conductors, test method supplementary bonding 2.6.4; 2.6.6; Fig 2.2; Fig 2.3 2.5.2; 2.6.4; 2.6.5; 2.6.1 8;3.7; 3.9.1; Table 3.4; 2.2 D Defects Designer 192 3.7; 3.11; Section 5 Introduction; 1.5; 2.1; 2.2; 2.5; 3.4; Section 5 Diagrams, presence of 2.5.2 item p; 3.9.1 Distribution equipment 2.9.1 Guidance N o t e 3: Inspection & Testing © The Institution of Engineering and Technology Index Diversity factor Diverted neutral currents 2.5.3 3.3.3; Appx D E Earth electrode resistance Earth electrode resistance testers 2.6.4; 2.6.13; Table 3.4; Fig 2.28; Fig 2.29; Fig 2.30 2.6.13; 4.6 Earth fault loop impedance maximum measured values Appx A PEIs temperature correction test method Appx A Section 2; 2.6.13 4.5 testers verification Earth-leakage current testing Electrical Installation Certificate (EIC) Electrical Installation Condition Report (EICR) 2.6.15 2.6; Appx C 1.3.1; 1.4; 1.6; 2.1 ; 2.2; 2.6.2; 2.6.16; 3.4; 3.8; Section 5 1.3.2; 3.1 1 ; 5.4 Electrical separation insulation resistance tests 2.6.9 source of supply inspection 2.6.9 measurement of voltage 2.6.9 Electricity at Work Regulations 1989 Preface; 1.1 ;2.1;Table 3.2 note 2; 3.3; 3.4; 3.5; 4.9 Electromagnetic disturbances 2.5.3; 2.6.23 Electronic equipment 2.6.4; 2.6.7 Electricity Safety, Quality and Continuity Regulations Escape routes Table 3.2 note 1 2.5.2 item c; 2.5.3 F Fault protection 2.5.2 item h Fire barriers, provision of 2.5.2 item g Fire protection Forms Functional extra-low voltage (FELV) Functional testing 2.5.2 item c; 2.5.2 item d; 2.5.3 Section 5 Table 2.9; 2.6.10 2.6.4; 2.6.19; Table 3.4; 3.10.3 G General requirements Section 1 Guidance N o t e 3: Inspection & Testing © The Institution of Engineering and Technology 193 Index H Health a n d S a f e t y a t W o r k etc. Act Introduction; 1974 Health a n d Safety Note Executive 2.3; Guidance 1.1; 4.1 G S 38 1.3.2 H o u s i n g ( S c o t l a n d ) Act 2 0 1 4 Higher 3.4 risk residential b u i l d i n g s (HRRBs) 2.5.2 item 1 I d e n t i f i c a t i o n by c o l o u r 2.5.2 item b I 2.3; 3.6 I n f o r m a t i o n for i n s p e c t o r Initial i n s p e c t i o n general 2.5.1 procedure inspection checklist 2.5.3 inspection items 2.5.2 Section 5 schedule 2.6 Initial t e s t i n g results, 2.6.1 r e c o r d i n g of 2.6.4 test sequence Section 2 certificates 2.2; Section 5 f r e q u e n c y of s u b s e q u e n t i n s p e c t i o n 2.4; Table 3 . 2 Initial verification i n f o r m a t i o n for inspector 2.3 p u r p o s e of 2.1 relevant 2.1 criteria 2.4 scope typical Section 5 forms Inspection checklist 2.5.3 Inspection Schedule Section 5 Inspector's 1.2; 3.8.1 competence 1.1; Section Instruments I n s u l a t i o n resistance 2.6.7; 3.10.3b; Tables 4 2.9 to 2.13 4 . 4 ; Appx Insulation resistance testers C 2.6.24 Inverters J,K, L L a b e l l i n g and L a n d l o r d a n d Tenant 194 G u i d a n c e Note 2.5.2 marking 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology Act 1985 items m, p; 3.9.1 1.3.2; Table 3 . 2 note 10 Index M 1.7; 2.5.2 item h; 2.6; 3.7; Table 3 . 2 Medical locations M i n o r Electrical I n s t a l l a t i o n W o r k s 2.2; 5 . 2 ; 5 . 4 C e r t i f i c a t e (MEIWC) Mobile a n d t r a n s p o r t a b l e units Model forms Motor circuits 3.7 2.2; 2.6.3; Section 5 3.10.3 item a N 2.6.11 Non-conducting location 2.5.2 item p Non-standard colours Notices 2.5.2 item p; 3.9.1 (also signs) O Ohmmeters 2.6.7; i n s u l a t i o n resistance 2.6.5; 2 . 6 . 6 ; 4 . 3 low-resistance Older installations, inspection 3.8.1; 3.12 of Introduction Operational manual Overvoltages 4.4 2.6.21 due to faults O v e r v o l t a g e s of a t m o s p h e r i c origin o r 2.6.22 d u e to switching P PELV Periodic 2.5.2 item h; Table 2.9; 2.6.4; 2.6.8; Table 2.12; Table 2.13; 2.6.10; 3.9.1; 4.4 inspection general procedure 3.8.2 i n s p e c t i o n checklist 3.9.1 3.1 p u r p o s e of 1.3.1; 3.11; 5.3 report 3.8.3; Table 3.3 sampling 3.8.1 visual inspection Periodic i n s p e c t i o n a n d testing Section 5 forms 3.7;Table 3 . 2 f r e q u e n c y of 3.8.2; 3.8.3 general p r o c e d u r e general requirements information for inspector inspector's competence Section 1; Table 3.1 3.6 1.2; 3.8.1 3.2 necessity for 3.1; 3.8.1 p u r p o s e of G u i d a n c e Note © The Institution 3: I n s p e c t i o n & Testing of Engineering a n d Technology 195 Index 1.5 record keeping requirement 3.2; 3.8.1 for checks 3.5; Table 3.1; Table 3 . 2 Periodic testing 3.10; Table 3 . 4 Phase s e q u e n c e 2 . 6 . 4 ; 2.6.17 routine 4.8 instruments verification 2.6.17 of 2.5.2 item e; 2.6.12; 3.10.3c; Polarity Table 3 . 4 2.6.12; Fig 2.27 test m e t h o d P o w e r c o n v e r s i o n e q u i p m e n t (PCE) 2.6.24 Prospective fault current 2.6.16 Prosumers e l e c t r i c a l installations 2.6.24 (PEIs) P r o t e c t i o n by barriers p r o v i d e d d u r i n g e r e c t i o n 2.6.4 enclosures 2.6.4 Protective p r o v i d e d d u r i n g erection multiple 2.5.2 item h; 3 . 3 . 3 e a r t h i n g (PME) Q,R Record k e e p i n g 1.6; 2.5.1 Reference tests continuity of protective metallic enclosures conductors 2.6.4; 2.6.5; Fig 2.1 ; Fig 2.2; Table 3.4; 3.10.3a a s protective 2.6.5 conductors 2.6.5 test m e t h o d s 1 a n d 2 continuity of r i n g f i n a l circuit conductors 2.6.6; Fig 2.2; Fig 2.19; Fig 2.20; Table 3.4 insulation resistance test 2.6.7; 3.10.3b resistance o f f l o o r s a n d w a l l s 2.6.11 s e q u e n c e of 2.6.4 Relevant criteria 2.1 Rented accommodation R e p o r t , Electrical I n s t a l l a t i o n Condition 1.3.2; 3.7 1.3.1; 1.3.2; 3.11; Section 5 Residual c u r r e n t d e v i c e s (RCDs) f o r a d d i t i o n a l protection 2.5.2 item h notice 2.5.2 item p test method testers R e s i s t a n c e of c o n d u c t o r s Routine checks 196 G u i d a n c e Note 3 : I n s p e c t i o n & Testing © The Institution of Engineering and Technology 2.6.18; Table 2.17; Table 3.4 4.7 Appx B 3 . 5 ; Table 3.1; Table 3.2 Index Routing of cables 2.5.2 item c Rule of thumb earth fault loop impedance 2.6.15 3-phase prospective fault current 2.6.16 S Safety during testing Sampling Schedule of Circuit Details 1.1;2.6.15; 3.3.2; 3.8.2 3.8.3;Table 3.3 5.4 Schedule of Inspections 1 .3.1 ; 2.6.2; 5.1; 5.3 Schedule of Test Results 1.3.1; 2.6.2; 5.1; 5.4 SELV 2.5.1; 2.5.2 item c; 2.5.2 item h ; 2.6.4; 2.6.8; Table 2.12; Table 2.13; 2.6.10; 3.9.1; 4.4 Separation of circuits 2.5.2 item h; 2.6.4; 2.6.8; 2.6.9 Shock hazards 1.1 Signs see Notices Socket outlets Specialized systems Specification Surge protection devices (SPDs) Surveying, thermographic 2.5.3 1.7; 2.5.2 item h Introduction 2.5.2 item 1;2.5.2 item p 4.9 T Terminal connections 2.5.2 item a Test instruments 1.1; Section 4 Thermal effects 2.5.2 items g, n; 3.9.1 Thermographic equipment 4.9 U Utilization categories, switchgear 2.5.2 item j; Table 2.7 V Verification, initial Voltage drop, verification Section 2 2.6.4; 2.6.20; 4.5 W Working at height 1.1 X,Y, Z No entries Guidance N o t e 3 : Inspection & Testing © The Institution of Engineeringand Technology 197 W r i t t e n b y industry e x p e r t s a t t h e IET (directly involved w i t h developments to B S 7671) and peer-reviewed by industry, the IET Guidance N o t e s series comprises eight b o o k s t h a t e x p a n d upon and simplify essential p a r t s of t h e l E T W i r i n g Regulations, ensuring h i g h q u a l i t y guidance t h a t i s simple t o f o l l o w a n d specific t o key topics. The Guidance N o t e s series has n o w been u p d a t e d t o BS7671:2O18+A2:2O22. Other books in t h i s series include: Guidance Note 1 Selection & Erection Guidance Note 2 Isolation & Switching Guidance Note 4 Protection Against Fire Guidance N o t e 5 Protection Against Electric Shock Guidance N o t e 6 Protection Against Overcurrent Guidance N o t e 7 Special Locations Guidance Note 8 Earthing & Bonding ISBN 9 7 8 - 1 - 8 3 9 5 3 - 2 3 6 - 8 9 9 > The Institution of Engineering and Technology Michael Faraday House Six Hills Way Stevenage Herts SG12AY www.theiet.org ISBN 978-1-83953-236-8